24ACB7
Comfortt17 2---Stage Air Conditioner
with Puronr Refrigerant
1---1/2 to 5 Tons
CONNECTION DIAGRAM
*SR
2
1
(NOTE #8)
5
*CHS
*CH
BLK
or
BLK
RED
(NOTE #9)
RED or BLK
L1
208/230 1Ø
POWER
L2
SUPPLY
EQUIP GND
RED
CS
YEL/ PNK
BRN/YEL
BLU
BLK
Y2
Y1
INDOOR THERMOSTAT (NOTE #6)
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
CONDUCTOR ON CIRCUIT BOARD
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
PLUG RECEPTACLE
CAPACITOR
CAP
*CH
CRANKCASE HEATER
NOTES:
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
5. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF).
6. Connection for typical cooling only thermostat. For other arrangements see Installation
Instructions.
7. If indoor section has a transformer with a grounded secondary, connect the grounded
side to the BRN/YEL lead.
8.
When start relay and start capacitor are installed, start thermistor is not used.
9.
CH not used on all units.
10.
If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to
equalize between high and low side before starting.
Wiring Diagram
BLU
*SC
CAP
BRN
YEL
H
C
BLK
F
COMP
BLK
YEL
BLK
YEL
CONT
11
21
BRN
23
23
BLK
YEL
BLK
*CTD
VIO
T2
LOGIC
T3
*HPS
*LPS
YEL/ PNK
BLU/PNK
*LLS
BLK
C
R
G
INDOOR BLOWER MOTOR
*CHS
CRANKCASE HEATER SWITCH
COMP
COMPRESSOR
CONTACTOR
CONT
COMPRESSOR SOLENOID
CS
COMPRESSOR TIME DELAY
*CTD
HIGH PRESSURE SWITCH
*HPS
INDOOR FAN RELAY
IFR
*LLS
LIQUID LINE SOLENOID VALVE
*LPS
LOW PRESSURE SWITCH
OFM
OUTDOOR FAN MOTOR
*SC
START CAPICATOR
*SR
START RELAY
* MAY BE FACTORY INSTALLED
Fig. 1 – Wiring Diagram — Model sizes 2 - - 5 tons, 208/230- -1
SCHEMATIC DIAGRAM (LADDER FORM)
*CHS
L1
CONT
BLU
11
21
EQUIP
GND
S
C
R
OFM
C
*LPS
Y2
Y1
G
T1
R
INDOOR THERMOSTAT
BLU/PNK
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
REQUIRED LIQUID LINE TEMPERATURE
EXTERNAL
POWER
Liquid
Required Subcooling
C
SUPPLY
Pressure
R
24 V
Temperature (ºF)
at Service
(NOTE #3)
Valve (psig)
6
8
10 12 14 16
251
78
76
74
259
80
78
76
266
82
80
78
274
84
82
80
283
86
84
82
291
88
86
84
299
90
88
86
308
92
90
88
317
94
92
90
326
96
94
92
335
98
96
94
345
100
98
96
354
102
100 98
364
104
102 100 98
374
106
104 102 100 98 96
384
108
106 104 102 100 98
395
110
108 106 104 102 100
406
112
110 108 106 104 102
416
114
112 110 108 106 104
427
116
114 112 110 108 106
439
118
116 114 112 110 108
450
120
118 116 114 112 110
462
122
120 118 116 114 112
474
124
122 120 118 116 114
1. Compressor damage may occur if system is over charged.
2. This unit is factory charged with R-410A in accordance with the amount shown
on the rating plate. The charge is adequate for most systems using matched
coils and tubing not over 15 feet long. Check refrigerant charge for maximum
efficiency. See Product Data Literature for required Indoor air Flow Rates and
for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant before system repair or final
disposal. Use all service ports and open all flow-control devices, including
solenoid valves.
4. Never vent refrigerant to atmosphere. Use approved recovery equipment.
*CH
COMP
R
C
S
CAP
*SR
H
5
2
*SC
CONT
C
1
23
23
OFM
F
CS
* CTD
*HPS
T2
CONT
LOGIC
T1
T3
*LLS
IFR
C
R
EXTERNAL POWER SUPPLY 24 V
COOLING ONLY
CHARGING PROCEDURE
1. Only use subcooling charging method
when OD ambient is greater than 70ºF
and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF,
and line set is less than 80 ft.
72
70 68
2. Operate unit a minimum of 15 minutes
74
72 70
before checking the charge.
76
74 72
3. Measure liquid service valve pressure
78
76 74
by attaching an accurate gauge to the
80
78 76
service port.
82
80 78
4. Measure the liquid line temperature by
84
82 80
attaching an accurate thermistor type
86
84 82
or electronic thermometer to the
88
86 84
liquid line near the outdoor coil.
90
88 86
5. Refer to unit rating plate for required
92
90 88
subcooling temperature.
94
92 90
6. Find the point where the required
96
94 92
subcooling temperature intersects the
96 94
measured liquid service valve pressure.
7. To obtain the required subcooling
temperature at specific liquid line
pressure, add refrigerant if liquid line
temperature is higher than indicated.
When adding refrigerant, charge in
liquid form using a flow restricting
device into suction service port.
Recover refrigerant if temperature is
lower. Allow a tolerance of +/- 3ºF.
CAUTION
3 3 6 3 2 3 -1 0 1 R E V . B
L2
Need help?
Do you have a question about the 24ACB7 Comfort and is the answer not in the manual?
Questions and answers