Fire-Lite M302(A Installation Instructions page 4

Two-wire conventional detector monitor module

Advertisement

SPECIFICATIONS
Temperature:
Humidity:
Weight:
Dimensions:
Test Features:
Accessories:
Communication Line – Terminals 1 & 2
Voltage:
Current:
Communication Line
Loop Impedance:
External Power Supply Requirements – Terminals 3 & 4
Voltage:
Ripple:
Current:
Power must be interrupted to reset detectors. The monitor module must have a minimum of 18.8 VDC at termi-
nals 3 and 4 to function properly. Minimum supply current and maximum wire resistance formulas are provided for a
riser circuit on page 3. Ground fault detection must be accomplished by the control panel.
Initiating Device Circuit (IDC) – Terminals 6, 7, 8, & 9
Voltage:
Current:
IDC Loop Impedance:
Standby Current:
Detector Current in Standby:
Alarm Current:
Style:
EOL Resistance:
Detector loop current is sufficient to ensure operation of one alarmed detector per zone. For compatible detec-
tors refer to the Fire-Lite detector compatibility chart.
F400-09-00
32° to 120° F (0° to 49° C)
10% to 93% Noncondensing
.5 lbs (232 gm)
4-1/2 " H, 4 " W, 1-1/4 " D
(Mounts to 4 " square by 2-1/8 " deep electrical boxes.)
Magnetically activated reed switch.
SMB500
Surface Mount Box for 300 series modules
M02-04-00
Test Magnet for testing devices
15 – 32 VDC
200 µA Max (Standby)
1.3 mA Max (Style D enabled)
5.1 mA Max @ 24V (LED latched on)
40
Max
22.2 – 25.5 VDC (Filtered, Regulated, and Power-Limited)
100mV RMS Max
90 mA per module
16 – 28 VDC (Ripple: 100mV RMS Max)
90 mA Max
25
Max
10.0 mA Max
Up to 2.4 ma
20 mA minimum
Style B (class B) / Style D (class A)
3.9K ohm nominal
4
I56-631-06