TESTING
The M302(A) monitor module can be tested with a test magnet available from Fire-Lite (M02-04-00, see Figure 1). The magnet
test checks the module's electronics and connections to the control panel. Interfaced two-wire detectors must be tested inde-
pendently. Test two-wire detectors per manufacturer's installation instructions.
M302(A) MONITOR MODULE WIRING DIAGRAMS
CONNECT MODULES TO LISTED
COMPATIBLE ADDRESSABLE FIRE-LITE
CONTROL PANELS ONLY.
PREVIOUS DEVICE
LISTED BATTERY BACK-UP, SWITCHED
DC POWER SUPPLY.
SEE REQUIREMENTS ON PAGE 4.
POWER TO THE MONITOR MODULE
MUST BE EXTERNALLY SWITCHED TO
RESET THE DETECTORS. A C300
CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
UL LISTED POWER SUPPLY - SEE FIGURE 5.
Figure 3. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA STYLE B
CONNECT MODULES TO LISTED
COMPATIBLE ADDRESSABLE FIRE-LITE
CONTROL PANELS ONLY.
LISTED BATTERY BACK-UP,
SWITCHED DC POWER SUPPLY.
SEE REQUIREMENTS ON PAGE 4.
POWER TO THE MONITOR MODULE
MUST BE EXTERNALLY SWITCHED TO
RESET THE DETECTORS. A C300
CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
UL-LISTED POWER SUPPLY - SEE FIGURE 5.
Figure 4. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA STYLE D
F400-09-00
(–)
FROM PANEL OR
(+)
(SHIELD)
(–)
(+)
(–)
(+)
OPTIONAL BRANCH CIRCUIT
TO NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
COMMUNICATION LINE
(-)
FROM PANEL OR
(+)
PREVIOUS DEVICE
(SHIELD)
(-)
(+)
(-)
(+)
OPTIONAL BRANCH CIRCUIT
TO NEXT MONITOR MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
COMMUNICATION LINE
32 VDC MAX.
REFER TO FIRE-LITE PRODUCT MANUAL
FOR WIRE SPECIFICATIONS.
(–)
TO NEXT
(+)
DEVICE
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
(SHIELD)
MONITOR
IDC INSTALLATION WIRING MUST NOT EXCEED
MODULE
M302(A)
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
(–) 9
1 (–)
(+) 8
2 (+)
(+) 7
3 (–)
(–) 6
4 (+)
5
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO ENSURE SUPERVISION OF CONNECTIONS.
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE.
INSTALL MODULE PER MANUFACTURER'S
ALL WIRING SHOWN IS SUPERVISED.
TERMINAL WIRING MUST BE POWER LIMITED.
32 VDC MAX.
REFER TO FIRE-LITE PRODUCT
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE D
MANUAL FOR WIRE SPECIFICATIONS
(-)
TO NEXT
(+)
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
DEVICE
(SHIELD)
MONITOR
MODULE
M302(A)
(-) 9
1 (-)
(+) 8
2 (+)
(+) 7
3 (-)
(-) 6
4 (+)
5
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO ENSURE SUPERVISION OF CONNECTIONS.
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE.
INSTALL DETECTORS PER MANUFACTURER'S
ALL WIRING SHOWN IS SUPERVISED.
2
TERMINAL WIRING MUST BE POWER LIMITED.
2-WIRE CONVENTIONAL DETECTOR
POWER LIMITED: 90ma MAX; 28 VDC MAX
25 OHMS, 12 - 18 AWG.
+
+
INSTALLATION INSTRUCTIONS.
2-WIRE CONVENTIONAL DETECTOR
POWER LIMITED: 90ma MAX; 28 VDC MAX
IDC INSTALLATION WIRING MUST NOT EXCEED
25 OHMS, 12 - 18 AWG.
OR SECURITY DEVICES ON THE SAME MODULE.
3.9K EOL RESISTOR
REQUIRED AT TERMINALS
8 & 9 (INCLUDED)
+
+
-
-
INSTALLATION INSTRUCTIONS.
3.9K EOL
RESISTOR
(INCLUDED)
A78-2394-631
A78-2395-631
I56-631-06