ELECTRICAL DATA

Unit Size ---
OPER VOLTS*
V/PH
Voltage,
Series
MIN
24--- 31
36--- 31
208 ---230/1
253
48--- 31
60--- 31
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310 ---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
}
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
A- -WEIGHTED SOUND POWER (dBA)
Unit Size ---
Standard Rating
Voltage, Series
71 --- High Stage
24--- 31
65 --- Low Stage
68 --- High Stage
36--- 31
66 --- Low Stage
69 --- High Stage
48--- 31
66 --- Low Stage
69 --- High Stage
60--- 31
68 --- Low Stage
NOTE: Tested in accordance with AHRI Standard 270 ---08. (Not listed with AHRI).
CHARGING SUBCOOLING (TXV- -TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES
24--- 31
36--- 31
48--- 31
60--- 31

ACCESSORY CONTROLS

PART NUMBER
SYSTXCCITN01
Infinity Touch Control (non ---Wi---Fi)
SYSTXCCITW01
Infinity Touch Control with Wi---Fi & Wireless Access Point
SYSTXCC4ZC01
Infinity 4 ---Zone Damper Control Module (Wall ---mounted control for a four ---zone system.)
SYSTXCCSMS01
Infinity Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.)
SYSTXCCRRS01
Infinity Remote Room Sensor (Monitors temperature in an individual zone.)
SYSTXCCRCT01 or
Infinity System Remote Access Module (Hardware for wireless access and control via internet.)
SYSTXCCRWF01
SYSTXCCNIM01
Infinity Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on non ---zoning applications.)
COMPR
MAX
LRA
RLA
58.3
11.1
83.0
15.3
197
104.0
21.2
152.9
28.8
(dBA)
125
250
49.5
56.0
47.0
52.0
47.5
53.0
46.5
54.5
49.0
61.5
48.5
59.5
50.8
57.5
48.0
56.0
MIN
MIN
FAN
WIRE
WIRE
MCA
SIZE{
SIZE{
FLA
60 C
75 C
1.8
15.7
14
2.0
21.1
12
2.7
29.2
10
2.7
38.7
8
Typical Octave Band Spectrum (dBA, without tone adjustment)
500
1000
60.5
67.5
56.5
60.5
60.0
60.0
56.0
56.5
62.0
62.0
59.0
59.5
60.5
63.0
59.0
62.0
REQUIRED SUBCOOLING _F (_C)
DESCRIPTION
5
MAX
MAX
LENGTH
LENGTH
ft. (m)}
ft. (m)}
60 C
75 C
14
50 (15.2)
48 (14.6)
12
59 (18.0)
56 (17.1)
10
68 (20.7)
65 (19.8)
8
80 (24.4)
76 (23.2)
2000
4000
58.0
53.5
55.0
50.0
56.0
52.0
53.0
50.0
59.5
54.5
56.5
51.5
59.5
57.5
57.5
55.5
10 (5.6)
11 (6.1)
12 (6.7)
14 (7.8)
MAX
FUSE** or
CKT BRK
AMPS
25
30
40
60
8000
53.0
49.0
51.0
48.0
49.5
48.5
54.5
52.0