Power Flame ('C' Series) Burner Adapter Plate
Boiler Model
Part No.
MPC4 thru MPC7
602263401
MPC8 thru MPC14
602263411
MPC15 thru MPC18
602263421
Power Flame ('JR' Series) Burner Adapter Plate
Boiler Model
Part No.
MPC4 thru MPC7
602263451
MPC8 thru MPC11 602263461
1. In most cases the burner adapter plate carton for the
specified burner will be provided by Burnham.
2. If adapter is provided by Burnham, open carton
and remove contents. Apply four (4) small dabs
of silastic on rear surface of adapter plate to
temporarily hold gasket in place. Hold adapter plate
in position against burner swing door, align holes
and secure with four (4) 3/8" lock washers and
3/8" - 16 x 7/8" lg. cap screws.
3. If adapter is furnished with burner, follow
manufacturer's instructions using gasket material
and hardware provided with burner.
4. USE A HOLE SAW OR KNIFE TO CUT BURNER
SWING DOOR INSULATION TO MATCH
HOLE SIZE ON BURNER ADAPTER PLATE.
After cutting, remove any and all loose pieces of
insulation which may become lodged or interfere
with the head of the burner air tube after insertion.
5. Secure burner to adapter plate with four (4) ½" lock
washers and four (4) ½" - 13 hex nuts provided.
Figure 6: Burner Adapter Plate Options
I.D.
'A'
'B'
No.
40
7-1/2
10-1/4
41
9
12
42
10-3/8 14-1/8
I.D.
'A'
'B'
No.
45
6-3/8
10-1/4
46
8-3/8
11-11/16
Beckett ('CF' Series) Burner Adapter Plate
Boiler Model
Part No.
MPC4 thru MPC7
602263001
MPC8 thru MPC15
602263011
MPC16 thru MPC18
602263021
Beckett ('CG' Series) Burner Adapter Plate
Boiler Model
Part No.
MPC4 and MPC5
602263031
MPC6 and MPC7
602263041
MPC8 thru MPC11
602263071
MPC12 thru MPC18
602263081
CAUTION
Failure to properly fill all gaps between the
insulation and burner blast tube may result in
damage to the burner.
6. Confirm that hole in insulation fits snugly around
burner blast tube. If hole is oversized, open burner
swing door (with burner attached) to access burner
blast tube. Use additional fiberglass rope gasket
provided with burner to fill in any space between
insulation and blast tube. If additional rope gasket
is not provided with the burner, use 3/8" fiberglass
rope rated for 2300°F (provided by others).
When finished, close burner swing door and secure
hardware.
P.
Connect Internal Control / Safety Circuit Wiring
Harness to Burner Controls, see Figures 25 and 37.
Also, refer to Burner Installation Manual and wiring
diagrams provided with burner.
I.D.
'A'
'B'
No.
00
6-3/4
10
01
8-1/4
10
02
10-1/4
11
I.D.
'A'
'B'
No.
03
5
10
04
6
10
07
7-1/4
10
08
8-1/8
11
51