Bryant 345MAV Installation, Start-Up, And Operating Instructions Manual page 29

Series f 4-way multipoise fixed-capacity condensing gas furnace
Table of Contents

Advertisement

D
E
V
B
V
V
VENT TERMINAL
Item
Clearance Descriptions
A
Clearance above grade, veranda, porch, deck, balcony, or
anticipated snow level
B
Clearance to a window or door that may be opened
C
Clearance to a permanently closed window
D
Vertical clearance to a ventilated soffit located above the
terminal within a horizontal distance of 2´(61cm) from the
centerline of the terminal
E
Clearance to an unventilated soffit
F
Clearance to an outside corner
G
Clearance to an inside corner
H
Clearance to each side of the centerline extended above
electrical meter or gas service regulator assembly
I
Clearance to service regulator vent outlet
J
Clearance to non--mechanical air supply inlet to building or
the combustion air inlet to any other appliance
K
Clearance to a mechanical air supply inlet
L
Clearance under a veranda, porch, deck, or balcony
M
Clearance to each side of the centerline extended above or
below vent terminal of the furnace to a dryer or water heater
vent, or other appliance's direct vent intake or exhaust.
N
Clearance to the vent terminal of a dryer vent, water heater
vent, or other appliances direct vent intake or exhaust.
O
Clearance from a plumbing vent stack
(1.) In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
(2.) In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
#
18˝ (46 cm) above roof surface
+
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
*
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the
Manufacturer's installation instructions.
Notes:
1. The vent for this appliance shall not terminate
a. Over public walkways; or
b. Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nusiance or hazard or property damage; or
c. Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
2. When locating vent terminations, consideration must be given to prevailing winds, location, and other c onditions which may cause recirculation of the combustiob products of adjacent vents.
Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.
B
C
V
B
B
F
B
X
AIR SUPPL Y INLET
12˝ (30cm) #
6˝ (15 cm) for appliances
cm) for appliances > 10,000 Btuh (3 kW) and 100,000 Btuh
(30 kW), 36˝ (91 cm) for appliances > 100,000 Btuh (30 kW)
*
*
*
*
*
3´ (91 cm) within 15´(4.5 m) above the meter/regulator
assembly
3´ (91 cm)
6˝ (15 cm) for appliances 10,000 BTUH (3kW), 12˝ (30
cm) for appliances > 10,000 Btuh (3 kW) and 100,000 Btuh
(30 kW), 36˝ (91 cm) for appliances > 100,000 Btuh (30 kW)
6´ (1.83 m)
12˝ (30 cm) +
*
*
*
Table 8—Other than Direct Vent Termination Clearance
—29—
Y
H
I
B
L
X
J
A
Canadian Installation (1)
10,000 BTUH (3kW), 12˝ (30
O
Y
G
X
V
K
A
AREA WHERE TERMINAL IS NOT PERMITED
U.S. Installation (2)
12˝ (30 cm)
4˝ (1.2 m) below or to the side of the opening. 1 ˝ (30 cm)
above the opening.
*
*
*
*
*
3´ (91 cm) within 15´(4.5 m) above the meter/regulator
assembly
*
4´ (1.2 m) below or to the side of opening: 1´(30 cm) above
opening.
3´ (91 cm) above if within 10´(3m horizontally)
*
*
*
*
M
N
V
25--24--65--2
A03228

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Series fF series

Table of Contents