Bottom Closure Panel; Gas Piping - Bryant 355MAV Installation, Start-Up, And Operating Instructions Manual

Series h deluxe 4-way multipoise variable-capacity direct vent condensing gas furnace
Table of Contents

Advertisement

To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove 2 screws holding front
filler panel. (See Fig. 26.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
WASHABLE
FILTER
Fig. 24—Filter Installed for Side Inlet
17
1 2
-IN. WIDE
CASINGS ONLY:
INSTALL FIELD-SUPPLIED
FILTER FILLER STRIP
UNDER FILTER.
3
1
24
/
2
1
FILTER
SUPPORT
Fig. 25—Bottom Filter Arrangement
FILTER
RETAINER
A93045
21-IN. WIDE
CASINGS ONLY:
SUPPORT RODS (3)
EXTEND 1/4" ON EACH
SIDE OF FILTER AND
REST ON CASING FLANGE
WASHABLE
FILTER
FILTER
RETAINER
A00290
4. Reinstall front filler panel and screws.
G. Gas Piping
Gas piping must be installed in accordance with national and local
codes. Refer to NFGC in the U.S. Canadian installations must be
made in accordance with NSCNGPIC and all authorities having
jurisdiction. Gas supply line should be a separate line running
directly from meter to furnace, if possible. Refer to Table 3 for
recommended gas pipe sizing. Risers must be used to connect to
furnace and to meter. Support all gas piping with appropriate
straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint
compound (pipe dope) should be applied sparingly and only to
male threads of joints. Pipe dope must be resistant to propane gas.
TABLE 3—MAXIMUM CAPACITY OF PIPE*
NOMINAL
IRON
INTERNAL
PIPE
DIAMETER
SIZE
(IN.)
1/2
0.622
3/4
0.824
1
1.049
1-1/4
1.380
1-1/2
1.610
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
9-2 NFPA 54-2002.
CAUTION: Connect gas pipe to furnace using a backup
wrench to avoid damaging gas controls.
WARNING: Gas valve shutoff switch MUST be facing
forward or tilted upward. Failure to follow this warning
could result in property damage or death.
WARNING: Never purge a gas line into a combustion
chamber. Never test for gas leaks with an open flame. Use
a commercially available soap solution made specifically
for the detection of leaks to check all connections. A
failure to follow this warning could result in fire, explo-
sion, personal injury, or death.
FRONT FILLER
PANEL
Fig. 26—Removing Bottom Closure Panel
—18—
LENGTH OF PIPE (FT)
(IN.)
10
20
30
175
120
97
360
250
200
680
465
375
1400
950
770
2100
1460
1180
BOTTOM
CLOSURE
PANEL
40
50
82
73
170
151
320
285
660
580
990
900
A93047