Potterton Performa 24 Eco HE Installation & Service Instructions Manual page 19

Condensing combination boiler
Table of Contents

Advertisement

Vertical
Flues
(Twin Pipe)
Y
X
Vertical
Flues
Y
X
Total Equivalent Length =
A+B+C+1x90°Bend
All vertical and angled runs must be included,
measured from the boiler adaptor (point X) to the
joint with the flue terminal (point Y). One 91.5°
bend or two 135° bends can be included without
reduction of the flue length.
If further elbows are required the flue length must
be reduced by the following amounts:-
1 metre for each 91.5° bend
0.5 metre for each 135° bend
A
X
© Baxi Heating UK Ltd 2009
Roof
Terminal
Y
C
B
This bend is equivalent to
1 metre
8.0 Flue Options
8.2
Twin & Vertical Flue Systems
1. Maximum permissible equivalent flue lengths are:-
Vertical Concentric
Vertical Twin Pipe
* Both the air and flue duct can be up to 12 metres
long each.
2. Any additional "in line" bends in the flue system must
be taken into consideration. Their equivalent lengths
are:-
Concentric Pipes:
Twin Flue Pipe
The elbow supplied with the standard horizontal flue is
not included in any equivalent length calculations
NOTE: Flue length is measured from point X to Y
as shown.
IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.
660mm
1m extension
45°bend
91.5°bend
1m extension
45°bend
91.5°bend
4m
12m*
45° bend
0.5 metres
93° bend
1.0 metres
45° bend
0.25 metres
91.5° bend
0.50 metres
The total equivalent
length for this example
is = 6.5 metres.
AIR DUCT
Equivalent
N
o
of
Length Value
fittings/pipes
1m
5
0.25m
2
2
0.5m
Equivalent Length Air Duct = 6.5m
FLUE DUCT
Equivalent
N
o
of
Length Value
fittings/pipes
1m
5
2
0.25m
0.5m
2
Equivalent Length Flue Duct = 6.5m
Sub total
5.0m
0.5m
1.0m
Sub total
5.0m
0.5m
1.0m
19