Setting Up the Switch Using Mounting Ears

To install and operate the switch successfully, ensure that the following requirements are met:
For power supply information, refer to
Verify that a minimum of 47 cubic feet/minute (79.8 cubic meters/hour) of air flow is available to
the air intake vents on the nonport side of the switch.
Verify that the ambient air temperature does not exceed 40
the ambient humidity remains between 10 percent and 85 percent while the switch is operating.
If installing the switch in a cabinet:
For additional installation, electrical, environmental, and other considerations, refer to the
SilkWorm Switch Safety Guide.
Setting Up the Switch Using Mounting Ears
The Brocade 5000 is shipped with mounting ears already installed on the switch. If you need to
replace the mounting ears, or reattach them to the Brocade 5000 switch, perform the following
steps:
6
-
In an EIA cabinet using the mounting ears provided with the switch. This is the
recommended installation method. For instructions and more information, refer to
"Setting Up the Switch Using Mounting Ears"
-
As a standalone unit on a flat surface. For instructions and more information, refer to
"Setting Up the Brocade 5000 as a Standalone Unit"
-
In an EIA cabinet using the Fixed Rack Mount Kit. The Fixed Rack Mount Kit is optional and
can be purchased separately. For detailed installation instructions, refer to the Fixed Rack
Mount Kit Installation Procedure.
-
In an EIA cabinet using the Slide Rack Mount Kit.The Slide Rack Mount Kit is optional and
can be purchased separately. For detailed installation instructions, refer to the Slide Rack
Mount Kit Installation Procedure.
-
The primary AC input is 100-240 VAC (switch autosenses input voltage), 47-63 Hz.
-
The primary outlet is correctly wired, protected by a circuit breaker, and grounded in
accordance with local electrical codes.
-
The supply circuit, line fusing, and wire size are adequate, as specified by the electrical
rating on the switch nameplate.
-
The cabinet must be a standard EIA cabinet.
-
Plan a cabinet space that is 1 rack unit high (1.75 inches; 4.44 cm), 19 inches (48.3 cm)
wide, and at least 24 inches (61cm) deep.
-
Ground all equipment in the cabinet through a reliable branch circuit connection and
maintain ground at all times. Do not rely on a secondary connection to a branch circuit,
such as a power strip.
-
Ensure that airflow and temperature requirements are met on an ongoing basis,
particularly if the switch is installed in a closed or multirack assembly.
-
Verify that the additional weight of the switch does not exceed the cabinet's weight limits
or unbalance the cabinet in any way.
-
Secure the cabinet to ensure stability in case of unexpected movement.
on page 6.
on page 7.
Power Supply Specifications on page
°
Celsius (104
Brocade 5000 Hardware Reference Manual
4-25.
°
Fahrenheit) and that