Allied Air 92G1DF Installation Instructions Manual page 37

Warm air gas furnace / downflow air discharge
Table of Contents

Advertisement

Burner Orifice Conversion Kits at Varying Altitudes
(0 - 2,286 m)
Natural
Unit
to
Size
LP/Propane
All
68W75*†
* Conversion requires installation of a gas valve regulator spring which is provided with the gas conversion kit.
† LP kit includes low line pressure switch.
A93 and 92G1 Pressure Switches at Varying Altitudes
Unit
0 - 4,500 ft
Size
(0 - 1,373 m)
All
No Change
Pressure switch is factory set. No adjustment necessary.
All models use the factory installed pressure switch from 0 - 7,500 feet.
A95 and 95G1 Pressure Switches at Varying Altitudes
Unit
0 - 4,500 ft
Size
(0 - 1,373 m)
045
No Change
070
No Change
090
No Change
110
No Change
135
No Change
Pressure switch is factory set. No adjustment necessary.
All models use the factory installed pressure switch from 0 - 4,500 feet.
506725-01
0 - 7,500 ft
LP/Propane
to
Natural
73W80*
4,501 - 7,500 ft
(1,373 - 2,286 m)
No Change
4,501 - 7,500 ft
(1,373 - 2,286 m)
No Change
77W43
77W42
77W43
77W42
7,501 - 10,000 ft
(2,286 - 3,038 m)
High Altitude
Natural
Burner Orifice
Burner Orifice
Kit
51W01
7,501 - 10,000 ft
(2,286 - 3,038 m)
74W91
7,501 - 10,000 ft
(2,286 - 3,038 m)
74W90
73W22
73W22
73W22
73W22
TABLE 14
Issue 1109
High Altitude
LP/Propane
Kit
68W70*†
Page 37 of 48