Details of Exhaust Piping Terminations for Non-Direct
Vent Applications
Exhaust pipe may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is preferred.
Figures 34 through 37 show typical terminations.
1. Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
Table 8. The specified pipe size ensures proper velocity
required to move the exhaust gases away from the
building.
2. On field supplied terminations for side wall exit, exhaust
piping may extend a maximum of 12 inches (305 mm)
for 2" PVC and 20" (508 mm) for 3" (76 mm) PVC beyond
the outside wall. See Figure 35.
3. If exhaust piping must be run up a sidewall to position
above snow accumulation or other obstructions, piping
must be supported every 24" (610 mm) as shown in
Figure 36. When exhaust piping must be run up an
outside wall, any reduction in exhaust pipe size must be
done after the final elbow.
NON−DIRECT VENT ROOF TERMINATION KIT
12" (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
INSULATION IF REQUIRED
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
FIGURE 34
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE (IF REQUIRED)
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
SIZE TERMINATION
PIPE PER TABLE 8.
FIGURE 35
506725-01
(15F75 or 44J41)
SIZE TERMINATION
PIPE PER TABLE 8.
1/2" (13mm) FOAM
UNCONDITIONED
ATTIC SPACE
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
1/2" (13mm)
ARMAFLEX
INSULATION
(IF REQUIRED)
PVC REDUCER
12" MIN.
(305mm)
Above Grade or
average snow
accumulation
NON−DIRECT VENT FIELD SUPPLIED WALL
UNCONDITIONED
SPACE
*WALL SUPPORT
OUTSIDE WALL
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE (IF REQUIRED)
*Use wall support every 24" (610). Use two supports if extension is
greater than 24" but less than 48".
NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION
PIPE PER TABLE 8.
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
INSULATE
TO FORM
SEAL
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
Issue 1109
TERMINATION EXTENDED
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
6" (152mm)
Max
ABOVE GRADE OR
AVERAGE SNOW
ACCUMULATION
1/2" (13mm) FOAM
INSULATION (IF REQUIRED)
FIGURE 36
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION (IF REQUIRED)
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
EXTERIOR
PORTION OF
CHIMNEY
FIGURE 37
SIZE TER-
MINATION
PIPE PER
TABLE 8.
12" (305mm)
Page 25 of 48