Installation Requirements For The Commonwealth Of Massachusetts - Kenmore 33204 - Power Vent, 40 Gallon Owner's Manual

Gas water heater power vented gas models with hot surface ignition
Table of Contents

Advertisement

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed
in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by
the Commonwealth
and where the side walt exhaust vent termination
is tess than seven (7) feet above finished grade in the
area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:_
INSTALLATION
OF CARBON
MONOXIDE
DETECTORS
At the time of installation
of the side walt horizontal
vented
gas
fueled
equipment,
the installing
plumber
or gasfitter
shall observe
that a hard wired
carbon
monoxide
detector
with an alarm
and battery
back-up
is installed
on the floor level where
the gas equipment
is to be installed
In addition,
the installing
plumber
or gasfitter
shall observe
that a battery
operated
or hard wired
carbon
monoxide
detector
with
an alarm
is installed
on each
additional
level of the dwelling,
building
or structure
served
by the sidewall
horizontal
vented
gas fueled
equipment
It shall
be the responsibility
of the property
owner to secure
the services of qualified
licensed
professionals
for the installation
of hard
wired carbon
monoxide
detectors
In the event that the side walt horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a bat-
tery operated carbon monoxide detector with an alarm shall be installed.
APPROVED CARBON MONOXIDE DETECTORS
Each carbon monoxide detector as required in accordance with the above
provisions shall comply with NFPA 720 and be ANSl/UL 2034 listed and CSA certified
SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appli-
ance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS."
INSPECTION
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54
as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building, or structure used in whole or in part for residential purposes.
MANUFACTURER
REQUIREMENTS
- GAS EQUIPMENT
VENTING
SYSTEM
PROVIDED
When the manufacturer
of Product
Approved
side wall horizontally
vented
gas equipment
provides
a venting
system design
or venting
system components
with
the equipment,
the instructions
provided
by the manufacturer
for installation
of the equipment
and the venting
system shall
include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
MANUFACTURER
REQUIREMENTS
- GAS
EQUIPMENT
VENTING
SYSTEM
NOT PROVIDED
When
the manufacturer
of
a Product Approved
side walt horizontally
vented
gas fueled
equipment
does not provide
the parts for venting
the flue gases,
but identifies
"special
venting
systems,"
the following
requirements
shall be satisfied
by the manufacturer:
1. The referenced
"special venting system" instructions
shall be included with the appliance
or equipment
installation
instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally
vented gas fueled equipment,
all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or
equipment at the completion of the installation.