TJERNLUND WHK2 MILLIVOLT APPLIANCE INTERLOCK INST. (NOT COMPATIBLE WITH UC1) 8504026 REV A 0600 Manual

Water heater control module for models: hs115, gpak, hsul, ss1, hst, draft, gpak-t, inducers,
Hide thumbs Also See for WHK2 MILLIVOLT APPLIANCE INTERLOCK INST. (NOT COMPATIBLE WITH UC1) 8504026 REV A 0600:

Advertisement

Quick Links

TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
IMPORTANT: This gas pressure switch is an updated version with only one 1/4" aluminum
tubing connection to the pressure tap port of gas valve. The atmospheric vent connection
is no longer required, as on the Old-Style Switch. Disregard the "Gas Pressure Switch"
installation section of your VP-2/3, WHK-2, WHKE instruction manual if the old style switch
is referenced, (See Discontinued Old-Style Switch Diagram). If you are replacing an Old-
Style gas pressure switch with the new style gas pressure switch follow the instructions
below. The new style switch is compatible with any previous Old-Style Switch installations.
Qty (1) gas pressure switch
Qty (1) 1/8-NPT black pipe tee
Qty (2) #10 x ½" self-tapping screws
The gas pressure switch is mounted on the casing of the water heater adjacent to the heater's thermostat/gas control valve. It
should be mounted close enough so that the supplied 1/4" tubing will reach from the gas pressure switch fitting to the thermo-
stat/gas valve pressure tap port. The two provided screws are self-tapping and drilling. The screws do not require the use of a
drill and their 1/2" length assures that the inner tank will not be penetrated.
1. Mount the gas pressure switch by securing it to the heater casing with a screw in each of the two mounting holes.
IMPORTANT: Mount gas pressure switch so that diaphragm is in a VERTICAL position, (See New Switch Diagram).
2. Install the supplied 1/8"-NPT pipe plug to the 90
thread sealant, do not over tighten.
3. Install the 1/8-NPT black pipe tee to the gas pressure switch, (See New Switch Diagram). Use thread sealant, do not over
tighten. CAUTION: Utilize the hex nut on the gas pressure switch when attaching the black pipe tee.
4. Install the supplied Brass 1/8-NPT male x ¼" compression fitting to the 1/8-NPT black pipe tee, (See New Switch Diagram ).
Use thread sealant, do not over tighten.
5. Remove the PRESSURE TAP plug from the underside of the thermostat/gas control valve and install the supplied Brass
1/8-NPT male x ¼" compression fitting, (See New Switch Diagram). Use thread sealant, do not over tighten.
IMPORTANT: DO NOT alter the heater's PILOT GAS LINE, (See New Switch Diagram).
6. Using a tube cutter, cut the appropriate length of the supplied 1/4" tubing to reach from the gas pressure switch fitting to the
PRESSURE TAP PORT fitting of the thermostat/gas control valve. Make sure each end of the tubing is not pinched closed.
7. Use the 1/4" tubing to connect gas pressure switch fitting to the PRESSURE TAP PORT fitting on the thermostat/gas control valve.
8. Conduct a gas leakage test of all connections as outlined in the latest edition of NFPA 54, ANSI Z223.1, part 4. or local codes.
NOTE: A "gauge port" can be accessed by removing the 1/8-NPT pipe plug that is on the 1/8-NPT black pipe tee (attached to
the gas pressure switch).
GAS PRESSURE SWITCH
COMMON
NORMALLY OPEN
Qty (1) 1/8-NPT pipe plug
Qty (2) brass 1/8-NPT male x ¼" compression fitting (Only (1) included in 950-2080 kit)
Qty (1) section of ¼" outside diam. aluminum tubing (Not included in 950-2080 kit)
NEW STYLE GAS PRESSURE SWITCH INSTALLATION
port of the supplied 1/8-NPT black pipe tee, (See New Switch Diagram). Use
o
New-Style Gas Pressure
Switch Installation
MOUNTING HOLES
1/4" OUTSIDE DIAMETER
ALUMINUM TUBING - CONNECT
TO PRESSURE TAP FITTING OF
THERMOSTAT / GAS CONTROL
VALVE.
©2004 TJERNLUND PRODUCTS, INC. ALL RIGHTS RESERVED
THERMOSTAT/
GAS CONTROL VALVE
GAS SUPPLY
THERMOCOUPLE
BURNER GAS LINE
Discontinued Old-Style Switch
IMPORTANT:
DO NOT ALTER
PILOT GAS LINE
INSTALL BRASS 1/8-NPT MALE
x 1/4" COMPRESSION FITTING
INTO PRESSURE TAP PORT.
FIGURE 700S107
P/N: 8505022
2/13/04

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WHK2 MILLIVOLT APPLIANCE INTERLOCK INST. (NOT COMPATIBLE WITH UC1) 8504026 REV A 0600 and is the answer not in the manual?

Questions and answers

Summary of Contents for TJERNLUND WHK2 MILLIVOLT APPLIANCE INTERLOCK INST. (NOT COMPATIBLE WITH UC1) 8504026 REV A 0600

  • Page 1 1/4" OUTSIDE DIAMETER x 1/4" COMPRESSION FITTING ALUMINUM TUBING - CONNECT BURNER GAS LINE INTO PRESSURE TAP PORT. TO PRESSURE TAP FITTING OF THERMOSTAT / GAS CONTROL VALVE. FIGURE 700S107 2/13/04 ©2004 TJERNLUND PRODUCTS, INC. ALL RIGHTS RESERVED P/N: 8505022...
  • Page 2: Control Module

    CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL INJURY OR PROPERTY DAMAGE. DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE AT JOB SITE FOR FUTURE REFERENCE. Copyright © 1997, Tjernlund Products, Inc. All rights reserved. P/N 8504026...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Pilot Outage..................................1 General Cautions & Installation Restrictions.......................1, 2 Installation Actuation & Safety Controls..........................2 Solenoid Valve ..............................2 Gas Pressure Switch ............................2, 3 Linear Limit Spill Switch............................3 Electrical Wiring 115VAC interlock with HSUL, GPAK Power Venters or Draft Inducers with 950-1040 24/115 VAC Relay..4 115VAC interlock with HST, GPAK-T Power Venters or Draft Inducers with 950-1067 Relay/Timer ....5 115VAC interlock with HS115 Series Power Venters or Draft Inducers............6 System Schematic/WHK-2 Operation .......................6...
  • Page 4: Actuation & Safety Controls

    2. This device must be installed by a qualified professional installer in accordance with all local codes or in their absence in accordance with the National Electrical Code and the Occupational Safety and Health Act (OSHA) when applicable. 3. “Qualified Installer” shall mean an individual properly trained and licensed. 4.
  • Page 5: Linear Limit Spill Switch

    5. Measure and cut an appropriate length of tubing to reach from the fitting marked “warning” to the burner of the heater on Gas Pressure Switch. Connect to Gas Pressure Switch and route to burner area. NOTE: The Gas Pressure Switch has a built in pressure tap marked “gauge port” for future gas pressure testing, (See Diagram D). DIAGRAM C DIAGRAM D LINEAR LIMIT SPILLAGE SENSING SWITCH...
  • Page 6: 115Vac Interlock With Hsul, Gpak Power Venters Or Draft Inducers With 950-1040 24/115 Vac Relay

    WHK-2 WATER HEATER CONTROL MODULE INSTALLATION AND 115 VAC WIRING NOTE: If 115 VAC has already been wired into the Power Venter/Draft Inducer, discon- DIAGRAM G nect and follow the appropriate 115 VAC wiring instructions shown on pages 4-6 of this manual.
  • Page 7: 115Vac Interlock With Hst, Gpak-T Power Venters Or Draft Inducers With 950-1067 Relay/Timer

    5. Connect the WHITE lead from the WHK-2 to the WHITE motor lead. Secure with a wire connector, (See Diagram N). DIAGRAM N 6. Replace both electrical box covers. NOTE: When using the HSUL or GPAK Series for a water heater only, the ORANGE, YELLOW and BLUE wires in the Power Venter are not used.
  • Page 8: 115Vac Interlock With Hs115 Series Power Venters Or Draft Inducers

    115 VAC INTERLOCK WITH HS115 - SERIES POWER VENTERS AND 115 VAC CONTROLLED DRAFT INDUCERS 1. Connect the GRAY wire from the WHK-2 Module to the BLACK 115 VAC motor lead of the Power Venter or Draft Inducer. NOTE: Cut the quick connect and cap with wire connector. 2.
  • Page 9: Whk-2/Hsul Or Gpak Series Furnace Or Boiler & Water Heater Connection Diagram

    WHK-2 CONNECTED TO AN HSUL, GPAK - SERIES POWER VENTER OR DRAFT INDUCER WITH 950-1040 24/115 VAC RELAY (FURNACE OR BOILER AND WATER HEATER COMMON VENTED) WHK-2 CONNECTED TO AN HST, GPAK-T SERIES POWER VENTER OR DRAFT INDUCER WITH 950-1067 RELAY/TIMER (FURNACE OR BOILER AND WATER HEATER COMMON VENTED) NOTE: On the GPAK-T Series the wire color from terminal # 4 of Relay/Timer is BLUE.
  • Page 10: Whk-2/Sideshot Furnace Or Boiler & Water Heater Connection Diagram

    WHK-2 CONNECTED TO AN SS1 (FURNACE OR BOILER AND WATER HEATER COMMON VENTED) 24 VAC CONNECTION TO WATER HEATER CONTROLS Route the 25’ control cable to the water heater. Route control cable back to the heater controls along the ceiling or joists, taking care not to come closer than 6”...
  • Page 11: Operation Circuit Check

    OPERATION CIRCUIT CHECK 1. Place water heater in operation. A. The Power Venter should operate. 2. Turn gas pilot knob to “pilot”. B. The Power Venter should continue to operate for approximately 1 minute. The length of the post-purge cycle can be varied by adjusting the post purge control. See “Post Purge Timer Adjustment” on bottom of page. 3.
  • Page 12: Troubleshooting

    Venter or Draft Inducer with 950-1040 24/115 VAC Relay. At several steps throughout the guide you will be required to measure voltage. Extreme caution must be exercised to prevent injury. If you are unable to determine the defective part with the use of this guide, call your Tjernlund distributor or Tjernlund Products direct at 1-800-255-4208 for further assistance. SYMPTOM 1: HSUL, GPAK - SERIES POWER VENTER OR DRAFT INDUCER OPERATES CONTINUOUSLY.
  • Page 13 Gray and thin Black wires from the Venter Relay tance. and check for continuity between the terminals which the Gray and thin Black wires wire connected to. There should be continuity. Contact Tjernlund Replace Venter Relay. Products, Inc. at 1-800- Part #950-1040 255-4208 for assistance.
  • Page 14: Warranty Claim Procedure

    Tjernlund Products, Inc. will issue credit or provide a free part to replace one that becomes defective during the one year warranty peri- od. If the part is over 18 months old, proof of date of the installation in the form of the contractor sales/installation receipt is necessary to prove the unit has been in service for under one year.
  • Page 15: Typical Applications

    TYPICAL APPLICATION FURNACE OR BOILER WITH MILLIVOLT WATER HEATER MILLIVOLT WATER HEATER...

Table of Contents