Dear customer, We are pleased that you have decided to purchase an ACV burner. The burner model BMV is a modern generation flame burner. The advantage of this burner construction is the extensive energy saving operation with very low emissions (Sampling test according to EN 267:1999-11 Class 3, German environmental label “Blue Angel”...
*H = max. intake height in m (low sulphur fuel oil EL, oil temperature >10 °C, up to 700 m above sea level, 1 filter, 1 check valve, 6x 90° bends). Figure 11 One-line system Pure two-line system Figure 12 BMV1 / BMV2 / BMV1-FV / BMV2-FV : 662Y0800 • A...
Venting of the oil pump and the oil line system must be carried out via the manometer connection of the oil pump (see fig. 15). Caution : Do not allow the oil pump to operate without oil. Figure 15 BMV1 / BMV2 / BMV1-FV / BMV2-FV : 662Y0800 • A...
(see fig. 18). The photo-current must be between 55 μA and 100 μA at 230 V~ while in operation. Measuring adapter MA 2 (see fig. 18) available on request. Figure 18 BMV1 / BMV2 / BMV1-FV / BMV2-FV : 662Y0800 • A...
– Design of the chimney and effective chimney height The design and version of the chimney are to be determined according to DlN 4705 and DlN 18160. Mixing unit BMV1 / BMV1-FV BMV2 / BMV2-FV Figure 20 BMV1 / BMV2 / BMV1-FV / BMV2-FV : 662Y0800 • A...
Main switch White LDS Photocell Y/Gr Yellow / Green OFV Oil Pre-heater Operating hours counter Temperature or pressure limiter Temperature or pressure controller Ignition unit Magnetic valve Europlug (7 poles) BMV1 / BMV2 / BMV1-FV / BMV2-FV : 662Y0800 • A...
Replace fan wheel Fan wheel incorrectly positioned Correctly position fan wheel Loud noise during fan operation Fan wheel damaged Replace fan wheel Air flap incorrectly installed Correctly install air flap BMV1 / BMV2 / BMV1-FV / BMV2-FV : 662Y0800 • A...