Español Mode On/Off Menu Cancel Speed MODEL BRC1NRV71 Be sure to read this installation manual before installing this product. Veillez à lire ce manuel d’installation avant d’installer ce produit. Asegúrese de leer este manual de instalación antes de instalar este producto.
WARNING Only qualified personnel must carry out the installation work. Consult your Daikin dealer regarding relocation and reinstallation of the remote controller. Improper installation work may result in electric shocks or fire. Electrical work must be performed in accordance with relevant local and national regulations and with instructions in this installation manual.
Page 5
CAUTION Keep water out of the remote controller. To avoid electric shock due to entry of water or insects, fill the wiring through-hole with putty. Do not wash the remote controller with water as it may result in electrical shocks or fire. Do not touch the remote controller buttons with wet fingers.
2. Accessories The following accessories are included. Operation Installation Drywall screw Drywall anchor Wire tie Wiring retainer manual manual (2 pcs.) (2 pcs.) (1 pc.) (1 pc.) (1 pc.) (1 pc.) 3. Remote Controller Installation Procedure 3-1 Determine where to install the remote controller. Safety Considerations Make sure to follow the when determining the location.
Page 7
3-4 Determine the location where the wiring will enter the remote controller (back, left side, top left, top center). 3-4-1 Back outlet 3-4-2 Left outlet Cut off resin area (notched area). Cut the plastic at the notched area and remove any remaining burrs. 3-4-3 Top left outlet 3-4-4 Top center outlet Cut the plastic at the notched area and...
Page 8
Prepare the wiring for connection to the remote controller following these instructions: Approx. 3/8 inch (10 mm) To simplify the wiring, maintain a 3/8 inch (10 mm) difference Remove the wire jacket between the length of the two and insulation conductors.
Page 9
3-5-2 Left outlet To the Unit P1P2 Lower case Upper case Printed-circuit board 3-5-3 Top left outlet Wiring retainer Wiring retainer Upper case As shown to the left, Wire install the furnished wiring retainer to prevent the wires from being pinched Cross-section during installation.
Page 10
NOTE • To prevent electrical noise and possible communication errors, avoid installing the remote controller wiring parallel to or in the vicinity of line voltage circuits. 3-6 Installation procedure for the lower case. When wiring the remote controller through the top center or rear access points, attachment of the wire to the lower case is required before it is wall mounted.
Page 11
3-7 Install the upper case. • Align the upper case with tabs of the lower case (6 points), insert and install the upper case. • Install the wiring with care to prevent pinching. • Peel off the protective membrane which overlays the upper case. English...
4. Functions and Menu Items of Remote Controller Buttons 4-1 Functions and menu items (1) Operation mode selector button (11) LCD (with backlight) (4) Up button (5) Down button (6) Right button (7) Left button (9) Operation lamp (8) On/Off button Mode On/Off (3) Menu/OK button...
Page 13
(7) Left button Service Settings menu • Used to highlight items to the left of the Test Operation currently selected item. • Display contents are changed to Maintenance Contact *Blower Speed previous screen per page. Field Settings (8) On/Off button *Energy Saving Options Press once to operate, and press once Prohibit Function...
5. Power-on • Check for completion of indoor/outdoor unit wiring (SkyAir and VRV only). • Ensure that covers have been replaced on electrical component boxes for all units prior to restoring power. NOTE If construction activities are planned within the space following the test operation procedure, recommend to the customer that the unit is not operated to prevent contamination from paints, drywall dust and other airborne materials.
6. Field Settings • There are 2 setting ways for field settings when the unit is group controlled. One is individual setting, and another is group setting. • Group Control is only for VRV and SkyAir. Press and hold Cancel button for <Basic screen>...
Page 16
Press Menu/OK button. Setting confirmation screen is displayed. <Setting confirmation screen> and press Menu/OK Select Field Settings button. Setting details are Save the settings? determined and field settings screen returns. Setting In the case of multiple setting changes, repeat “ ”...
Page 18
Notes) 1. Field settings are normally applied to the entire remote control group, however if individual indoor units in the remote control group require specific settings or for confirmation that settings have been established, utilize the mode number in parenthesis. 2.
7. Setting Addresses • This section describes how to set Group Address, Indoor unit Airnet Address, Outdoor unit Airnet Address, Indoor unit Label and Outdoor unit Label. Group Address (Group) for VRV This menu is displayed when multizone controller or BACnet MS/TP adaptor is connected. Press and hold Cancel button for 4 <Basic screen>...
Page 20
Group Address (Unit) (VRV only) This menu is displayed when multizone controller or BACnet MS/TP adaptor is connected. Press and hold Cancel button for 4 <Basic screen> seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> Select Group Address in the Service...
Page 21
Indoor unit Airnet Address (VRV only) Press and hold Cancel button for 4 <Basic screen> seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> Select Indoor unit Airnet Address the Service settings menu, and press Service Settings Test Operation Menu/OK button.
Page 22
Outdoor unit Airnet Address (VRV only) This address menu is displayed when the Outdoor unit is recognized from the indoor unit. Press and hold Cancel button for 4 <Basic screen> seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen>...
Page 23
Group Address/Airnet Address (Rooftop unit only) Press and hold Cancel button <Basic screen> for 4 seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> Select Group Address/ Service Settings Min Setpoints Differential Airnet Address in the Service Group Address/Airnet Address Unit Operation Hours...
Page 24
Select the address you want to Group Address/Airnet Address set by using buttons. Unit No 0 Release Group Address 1-00 Press Menu/OK button. Change Address using Outdoor unit AirNet Address The indication changes from (Up/Down) button. Indoor unit AirNet Address “Release”...
Page 25
Indoor unit Label (VRV only) Press and hold Cancel button for 4 <Basic screen> seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> Select Indoor unit Label in the Service settings menu, and press Service Settings Min Setpoints Differential Menu/OK button.
Page 26
Outdoor unit Label (VRV only) This address menu is displayed when the Outdoor unit is recognized from the indoor unit. Press and hold Cancel button for 4 <Basic screen> seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen>...
8. Procedure for Checking Error History Press and hold Cancel button for <Basic screen> 4 seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> Service Settings Select Error History in the service Outdoor unit AirNet Address settings menu, and press Menu/OK Error History Indoor Unit Status...
9. Adding Maintenance Contact Information • Registration of the maintenance contact. Press and hold Cancel button for <Basic screen> 4 seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> Service Settings Select Maintenance Contact in the Test Operation service settings menu, and press...
10. Confirming Registered Details 10-1 Press Menu/OK button in the basic <Basic screen> screen. 10-1 Main menu is displayed. Cool Select Maintenance Information in the Set to main menu, and press Menu/OK button. Press Menu/OK button. Return Setting 10-2 Press Cancel button twice. The basic screen returns.
11-3 Select year, month, day and time by 11-3 Date & Time using (Left/Right) button and set 11-4 Year 2020 by using (Up/Down) button in the Month date & time screen. Press and hold the Thursday 12:00 button for continuous change of the Press Menu/OK button.
13. Unit Status (Rooftop unit only) 13-1 Press and hold Cancel button for 13-1 <Basic screen> 4 seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> 13-2 13-2 Service Settings Select Unit Status in the service Outdoor unit AirNet Address settings menu, and press Menu/OK...
14. Blower Speed (Rooftop unit only) • The appropriate setting is shown on the manual of the unit. 14-1 Press and hold Cancel button for 14-1 <Basic screen> 4 seconds or longer in the basic screen. Service settings menu is displayed.
15. Unit Operation Hours (Rooftop unit only) • Runtime is displayed and some of them are resettable. 15-1 Press and hold Cancel button for 15-1 <Basic screen> 4 seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen>...
16. Prohibit Function 16-1 Press and hold Cancel button for 16-1 <Basic screen> 4 seconds or longer in the basic screen. Service settings menu is displayed. <Service settings menu screen> 16-2 16-2 Service Settings Select Prohibit Function in the service Test Operation settings menu, and press Menu/OK Maintenance Contact...
17. Certification COMPLIANCE WITH FCC RULES AND REGULATIONS 15.21 You are cautioned that changes or modifications not expressly approved by the part responsible for compliance could void the user’s authority to operate the equipment. 15.105(b) This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.