Installation Instructions Techn. Documentation Electronic tank monitoring devices with data messaging Tankspion LX-NET / LX-Q-NET / e-litro T NET Tankspion LX-GSM / LX-Q-GSM / e-litro T GSM Tankspion LX-EDGE / LX-Q-EDGE Content: Page: GENERAL MOUNTING INSTRUCTIONS MOUNTING OF LEVEL PROBE...
GENERAL The electronical tank content display device of LX-Serie is to be used for monitoring of tank levels in pressureless liquid tanks. This documentation is to be used for the LX-(Q)-Edge, LX-(Q)-GSM and LX-NET / LX-Q-NET. For the ‘Edge’ devices, everything is the same as for the ‘GSM’ version. Beside the liter monitoring several other functions are available, in most cases with an extra module or adaptor.
MOUNTING INSTRUCTIONS Only qualified persons are allowed to install the measuring probe and to connect the display de- vice. Follow the regulation for each liquid, especially for the risk of water pollution and for flam- mable liquids. Condition for proper operation of measuring device is a professional installation. Follow the tech- nical rules for planning, construction and operation of the entire facility.
Page 4
- in manhole pit (buried tanks) - in damp locations. The probe box must be wa- tertight and ventilated (for pressure balance of the hydrostatic level probe). Tecson part no.: 12080 P. 4 LX-(Q)-NET / GSM / EDGE Techn. Docum. + Installation 03-2025...
ELECTRIC INSTALLATION Interconnection of measuring probe to display device Probe supply: Low-voltage DC Connection: Connect the 2-wire probe cable as follows: Refer to the figure on the Red(+) => clamp 1 , Black (-) => clamp 2. following page. Air capillary: The air capillary must have ventilation to atmosphere.
CONNECTION CLAMPS If LX-GSM and LX-NET Relay connection: The LX-GSM and LX-NET devices do have a double output relay. By this relay two separate elec- tric circuits can be switched simultaneously, e.g. a signalling device on/off and an electric valve off/on too. Under initial conditions the relay contacts 7-8 are closed and relay contacts 9-10 are opened.
For LX-(Q)-GSM: Clamps and SIM and push-buttons on LX-GSM device DEVICE MESSAGES / DEVICE PARAMETERS If the device is connected to OilView, also with the use of the app, everything is configured and managed in the OilView system, including the alarm forwarding. In this case, there is no need for manual configuration using SMS commands.
INITIAL SETUP The initial setup is carried out after completed mounting. Determine the tank data and enter them into the mode: You find 3 push buttons (blue) on the PCB positioned between the connection clamps. Ø Press ENTER => Device enters the setup mode Displayed step „1.
FUNCTION CHECK After fueling or once a year please check if the displayed liters are correct. MAINTANCE It is recommended to check once year if the displayed liters are correct. If there is a suspicion of a discrepancy, for a simple check lift the level probe by the cable so that the probe is above the liquid level.
For LX-NET / LX-Q-NET : NETWORK CONNECTION Netzwork connection: The LX-(Q)-NET device has a directly connectivety to LAN/Ethernet network with 10 / 100 Mbit TCP/IP protocol. Inside the housing you find the RJ45 jack for connecting a CAT-5 network cable. The plug of the network cable has to be pushed through the inlet at bottom side of the housing.
BROWSER ACCESS Show content in browser: Entering the IP address in your browsers address line the device will be called: P. 12 LX-(Q)-NET / GSM / EDGE Techn. Docum. + Installation 03-2025...
Page 13
Parameter setup via Browser: Clicking the ’CONFIG’ button opens a next page in the browser. Here you can setup serveral parameters for the device. Password: The inital passwort for config access at the device is: tank The password is changeable here. It is recommended to store an individual device password.
ERROR CODES Error code Meaning Error E 1 Invalid value setup. Error E 2 Measuring value of the probe is too low ! If current is less than 3.5 mA => Probe error. Measuring value too high for probe offset/zero calibration. The probe must not be Error E 3 plunged! A probe’s current above 4.5 mA is invalid as zero point.
Page 15
LX-(Q)-NET: Error-Messages at network communication Error N1 No network communication. A problem with the internal network module. The device automatically executes an internal ’Reset’ and retrys initial communications. Try disconnection of network plug, wait… and remount the network plug. Error N2 Error at the network comm..
TECHNICAL DATA Display device Supply voltage: Type AC : 230 V 50 Hz (standard) Type DC : 12V or 24V version Power consumption: <= 4 VA, typically 2 VA 4 - 20mA; U ca. 20V Measuring input: Resolution 12 Bit Accuracy: ±...
Content management of oil tanks Refer to by the tecson app. https://www.tecson.de/oil- smartview-app.html LABELING The manufacturer TECSON declares the compliance with the valid safety and test guidelines (CE Declaration). For Conformity Declaration refer to website www.tecson.de at menu item ‘Documentation’. Disposal: After dismantling all parts need to be disposed properly with regard to their material.