Binder KBF 470 Operating Manual

Constant climate chambers with program control
Table of Contents

Advertisement

Quick Links

Operating Manual
Translation of the original operating manual
KBF/KBF-UL (E7)
Constant climate chambers with program control
Model
KBF 130
KBF 130-UL
KBF 260
KBF 260-UL
KBF 470
KBF 470-UL
KBF 720
KBF 720-UL
KBF 1060
KBF 1060-UL
KBF 1600
KBF 1600-UL
KBF PRO (E7)
Constant climate chambers with program control
with enlarged temperature and humidity range
Model
KBF PRO 130
KBF PRO 260
KBF PRO 470
KBF PRO 720
KBF PRO 1060
KBF PRO 1600
BINDER GmbH
 Address: Post office box 102, 78502 Tuttlingen, Germany  Phone: +49 7462 2005 0
 Fax: +49 7462 2005 100  Internet: http://www.binder-world.com
 Service Hotline: +49 7462 2005 555  Service Fax: +49 7462 2005 93 555
 Service Hotline USA: +1 866 885 9794 or +1 631 224 4340 x3
 Service Hotline Asia Pacific: +852 390 705 04 or +852 390 705 03
Issue 01/2025
Art. No.
9020-0478, 9120-0478
9020-0494, 9120-0494
9020-0479, 9120-0479
9020-0495, 9120-0495
9020-0480, 9120-0480
9020-0496, 9120-0496
9020-0481, 9120-0481
9020-0497, 9120-0497
9020-0482, 9120-0482
9020-0498, 9120-0498
9020-0483, 9120-0483
9020-0499, 9120-0499
Art. No.
9020-0439, 9120-0439
9020-0440, 9120-0440
9020-0441, 9120-0441
9020-0442, 9120-0442
9020-0443, 9120-0443
9020-0444, 9120-0444
Art. No. 7001-0569

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KBF 470 and is the answer not in the manual?

Questions and answers

Summary of Contents for Binder KBF 470

  • Page 1 BINDER GmbH  Address: Post office box 102, 78502 Tuttlingen, Germany  Phone: +49 7462 2005 0  Fax: +49 7462 2005 100  Internet: http://www.binder-world.com  Service Hotline: +49 7462 2005 555  Service Fax: +49 7462 2005 93 555 ...
  • Page 2: Table Of Contents

    4.6.3 Connection kit for connecting the chamber to the water main ..........38 4.6.4 Safety kit: Hose burst protection device with reflux protection device (available via BINDER INDIVIDUAL customized solutions) ..................38 Electrical connection ......................... 40 FUNCTIONAL OVERVIEW OF THE MB2 CHAMBER CONTROLLER ....41 Operating functions in normal display ....................
  • Page 3 Controller menu structure ........................47 5.5.1 Main menu ..........................48 5.5.2 “Settings” submenu ......................... 49 5.5.3 “Service” submenu ........................49 Principle of controller entries ......................50 Performance during and after power failures ..................50 Performance when opening the door ....................51 START UP ......................
  • Page 4 11.6 Value entry for a program section ..................... 78 11.6.1 Set-point ramp and set-point step modes ................78 11.6.2 Weekday ..........................79 11.6.3 Start time ..........................79 11.6.4 Setpoint entry .......................... 80 11.6.5 Special controller functions ..................... 80 12. NOTIFICATION AND ALARM FUNCTIONS ............81 12.1 Notification and alarm messages overview ..................
  • Page 5 23.1 General information, personnel qualification................... 134 23.2 Maintenance intervals, service ......................134 23.3 Simple troubleshooting ........................135 23.4 Sending the chamber back to BINDER GmbH ................138 24. DISPOSAL......................139 24.1 Disposal of the transport packing ....................139 24.2 Decommissioning ..........................139 24.3 Disposal of the chamber in the Federal Republic of Germany ............
  • Page 6 25.4 KBF / KBF-UL Technical Data ......................143 25.5 KBF PRO Technical Data ....................... 146 25.6 Equipment and options (extract) ..................... 148 25.7 Accessories and spare parts (extract) .................... 149 25.8 Dimensions............................151 26. CERTIFICATES AND DECLARATIONS OF CONFORMITY ......157 26.1 EU Declaration of Conformity for KBF ....................
  • Page 7: Safety

    In no event shall BINDER be held liable for any damages, direct or incidental arising out of or related to the use of this manual.
  • Page 8: Intellectual Property

    35 U.S.C. § 287(a). Products and services listed on the BINDER website may be sold individually or as part of a combination product. Additional patent applications may also be pending in the U.S.
  • Page 9: Safety Alert Symbol

    NOTICE Indicates a potentially hazardous situation which, if not avoided, may result in damage to the product and/or its functions or of a property in its proximity. 1.4.2 Safety alert symbol Use of the safety alert symbol indicates a risk of injury. Observe all measures that are marked with the safety alert symbol in order to avoid death or in- jury.
  • Page 10: Word Message Panel Structure

    Observe the prescribed freshwater quality (next to water inlet on the rear of the chamber; on the optional freshwater can) Information QR-Code and URL to contact the BINDER Support Center KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 10/172...
  • Page 11 Figure 1: Position of labels on the chamber front Figure 2: Position of labels on the chamber rear Keep safety labels complete and legible. Replace safety labels that are no longer legible. Contact BINDER Service for these replacements. KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 11/172...
  • Page 12: Type Plate

    Made in Germany Figure 4: Type plate (example KBF 260-UL regular chamber 9020-0495) Indications of the type plate (example) Indication Information BINDER Manufacturer: BINDER GmbH KBF 260 Model designation Constant climate chamber Device name Serial No. 00000000000000 Serial no. of the chamber...
  • Page 13: Ukca Label

    Indication Information Max. operating pressure 11 bar Max operating pressure in the refrigerating system R600A – 0,095 kg Refrigerant type and filling weight Contains hydrocarbon gases Information on hydrocarbon gases Intended for use in commercial, industrial, or institutional Unit intended for commercial, Industrial, occupancies as defined in the Safety Standard for Refriger- institutional use acc.
  • Page 14: General Safety Instructions On Installing And Operating The Chambers

    (for Germany: DGUV guidelines 213-850 on safe working in laborato- ries, issued by the employers’ liability insurance association). BINDER GmbH is only responsible for the safety features of the chamber provided skilled electricians or qualified personnel authorized by BINDER perform all maintenance and repair, and if components relating to chamber safety are replaced in the event of failure with original spare parts.
  • Page 15 ∅ DO NOT continue to operate the chamber if the alarm message “Humidity system” ap- pears. ∅ DO NOT acknowledge the “Humidity system” alarm message.  Turn off the chamber when the alarm message “Humidity system” appears and contact BINDER service. KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 15/172...
  • Page 16: Intended Use

    Such ingredients include in particular acids and halides. Any corrosive damage caused by such ingredients is excluded from liability by BINDER GmbH. The chamber does not dispose of any measures of explosion protection.
  • Page 17: Foreseeable Misuse

    The requirements described in the Operating Manual for installation site and ambient conditions (Chap. 3.4) must be met. WARNING: If customer should use a BINDER chamber running in non-supervised continu- ous operation, we strongly recommend in case of inclusion of irrecoverable specimen or samples to split such specimen or samples and store them in at least two chambers, if this is feasible.
  • Page 18: Residual Risks

    • Continued operation of the chamber during an obvious malfunction • Insertion of objects, particularly metallic objects, in louvers or other openings or slots on the chamber • Human error (e.g. insufficient experience, qualification, stress, exhaustion, laziness) To prevent these and other risks from incorrect operation, the operator shall issue operating instructions. Standard operating procedures (SOPs) are recommended.
  • Page 19: Operating Instructions

    • Absence of a plausibility check to rule out erroneous inscription of electrical components • Performance of repair work by untrained/insufficiently qualified personnel • Inappropriate repairs which do not meet the quality standard specified by BINDER • Use of replacement parts other than BINDER original replacement parts •...
  • Page 20 • Non-ionizing radiation Non-ionizing radiation is not intentionally produced, but released only for technical reasons by electrical equipment (e.g. electric motors, power cables, solenoids). The machine has no permanent magnets. If persons with active implants (e.g. pacemakers, defibrillators) keep a safe distance (distance of field source to implant) of 30 cm, an influence of these implants can be excluded with high probability.
  • Page 21: Resistance Of The Humidity Sensor Against Harmful Substances

    1.14 Resistance of the humidity sensor against harmful substances The following list of harmful substances refers only to the humidity sensor and does not include any other materials incorporated in the chamber or prohibited substances in relation to explosion protection. Some gases - especially clean gases - do not have any influence on the humidity sensor.
  • Page 22: Chamber Description

    Humidity control: A resistance humidifying system humidifies the air. For this purpose, use deionized (demineralized) water. The option BINDER Pure Aqua Service allows using the chamber with any degree of water hardness. Water supply for humidification Several possibilities of water supply are available.
  • Page 23 COM™ 4 Multi Management Software (accessory, chap. 21.1). The chamber comes equipped with an Ethernet serial interface for computer communication. In addition, the BINDER APT-COM™ 4 Multi Man- agement Software permits networking up to 100 chambers and connecting them to a PC for controlling and programming, as well as recording and representing temperature and humidity data.
  • Page 24: Chamber Overview

    Chamber overview chamber size 260 chamber size 720 Figure 6: Constant climate chamber Triangular instrument panel (chamber sizes 130, 260) Signal triangle (chamber sizes 470, 720, 1060, 1600) Ergonomically adjustable control terminal (chamber sizes 470, 720, 1060, 1600) Door handle Outer chamber door(s) Inner glass door(s) (not shown) Machine room cover (refrigerating machine and humidity generation module)
  • Page 25: Triangular Instrument Panel (Chamber Sizes 130, 260)

    2.2 Triangular instrument panel (chamber sizes 130, 260) 5,7" controller display with touchscreen USB interface Pilot lamp Figure 7: Triangular instrument panel with MB2 program controller and USB interface 2.3 Signal triangle (chamber sizes 470, 720, 1060, 1600) Figure 8: Display of the signal triangle (operation without any problems) The signal triangle with light-up status display provides a visual display of chamber status through light in different colors on the sides of the triangle •...
  • Page 26: Ergonomically Adjustable Control Terminal (Chamber Sizes 470, 720, 1060, 1600)

    Ergonomically adjustable control terminal (chamber sizes 470, 720, 1060, 1600) Figure 9: Control terminal with MB2 program controller and USB interface The control terminal is adjustable in different angles so that operation is always ergonomic for people of different sizes and enables the optimal operating angle for chamber settings and control. KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 26/172...
  • Page 27 Positioning The control terminal can be securely fixed in three positions using a locking mechanism: Vertical position, suitable for smaller people and recom- mended when not in use / transport 30° position, suitable for medium-sized people 60° position, suitable for tall people Repositioning to the starting position Fold the control terminal up to 90°.
  • Page 28: Control Panel On The Chamber Rear

    2.5 Control panel on the chamber rear Figure 10: Control panel with connections on the chamber rear, with optional equipment Connector for analog outputs (option) Connector for zero-voltage relay alarm output (option) Connector for compressed air dryer (option) Power connection: IEC power connector C20 Data Bus to connect ICH Q1B light module or CO control module (accessories) Ethernet interface...
  • Page 29: Rear View With Water Connections

    Rear view with water connections (IN) (OUT) Figure 11: Rear view of the chamber with water connections Socket for optional freshwater can (chap. 21.6.1) (IN) Freshwater connection “IN” with screw thread ¾’’ for hose ½“, with union nut (OUT) Wastewater connection “OUT” with hose olive for hose ½“ KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 29/172...
  • Page 30: Completeness Of Delivery, Transportation, Storage, And Installation

    Note on second-hand chambers (Ex-Demo-Units): Second-hand chambers are chambers that were used for a short time for tests or exhibitions. They are thoroughly tested before resale. BINDER ensures that the chamber is technically sound and will work flaw- lessly. Second-hand chambers are marked with a sticker on the chamber door. Please remove the sticker before commissioning the chamber.
  • Page 31: Guidelines For Safe Lifting And Transportation

    • If the steam humidifying system has NOT been emptied: +3 °C / 37.4 °F to +60 °C / 140 °F. • After BINDER Service has emptied the steam humidifying system: -10 °C / 14 °F to +60 °C / 140 °F.
  • Page 32: Location Of Installation And Ambient Conditions

    37.4 °F with filled steam humidifying system. Damage to the chamber.  Contact BINDER Service before any storage below +3 °C / 37.4 °F. Permissible ambient humidity: max. 70 % r.h., non-condensing. After extensive operation at humidity levels > 70% r.h., condensation from excessive humidity can lead to corrosion during storage.
  • Page 33: Ambient Conditions

    Ambient conditions • Permissible ambient temperature range during operation: +18 °C / 64.4 °F to +32 °C / 89.6 °F. At ele- vated ambient temperature values, fluctuations in temperature can occur. The ambient temperature should not be substantially higher than the indicated ambient tem- perature of +22 °C +/- 3 °C / 71.6 °F +/- 5.4 °F to which the specified technical data relate.
  • Page 34: Installation And Connections

    Installation and connections Spacer for wall distance (from size 260 on) Please fix both spacers with the supplied screws at the chamber rear. This serves to ensure the prescribed minimum distance to the rear wall of 100 mm / 3.94 in. Figure 12: Spacer for wall distance Figure 13: Chamber rear with mounted spacers Mounting the flexible tilt protection kit (chambers sizes 130 and 470)
  • Page 35: Racks With U-Rails Or With Telescopic Rails (Accessory)

    Mounting on wall side • Fix two of the supplied tilt protection holders in the appropriate distance, each with two screws Ø 6mm suitable for the wall (c) Connection with the securing straps • On each side, thread one of the supplied securing straps through the provided slots of a device side and a wall side tilt protection holder Figure 14: Rear chamber (KBF 470) and mounting the flexible tilt protection kit Racks with U-rails or with telescopic rails (accessory)
  • Page 36: Wastewater Connection (Kbf / Kbf-Ul From Size 260 On, Kbf Pro)

    Figure 15: Condensate collection pan Installation of the condensate collection pan Hang the condensate collection pan on the chamber rear and guide the hose through the latch of the holder. Figure 16: KBF 130 with mounted condensate collection pan (detail) Wastewater connection (KBF / KBF-UL from size 260 on, KBF PRO) Fasten the wastewater hose to the wastewater connection “OUT”...
  • Page 37: Freshwater Supply

    1 µS/cm (ultrapure water), may cause acid corrosion due to its low pH). • Water treated by the optional water treatment system BINDER Pure Aqua Service (disposable system). A reusable measuring equipment to assess the water quality is included (chap. 21.7).
  • Page 38: Manual Freshwater Supply Via External Freshwater Can (Option)

    Then slowly open the water tap. 4.6.4 Safety kit: Hose burst protection device with reflux protection device (available via BINDER INDIVIDUAL customized solutions) A safety kit with a hose burst protection device and a reflux protection device is available for protection of the drinking water system, and against flooding caused by burst water hoses.
  • Page 39 We recommend connecting the hose as the last step in order to avoid twisting it while screwing on the safety kit. Open the water tap slowly in order to avoid actuating the hose burst protection device. Figure 17: Assembly of the connection kit (hose burst protection device with reflux protection device) Release of the reflux protection device: In case the burst protection device has interrupted the water supply, first find the reason and remove it as necessary.
  • Page 40: Electrical Connection

    • Only use original connection cables from BINDER according to the above specification. KBF-UL: Use only a UL Listed Power supply cord (UL category ELBZ), SJT 3x14 AWG (2.08 mm²);...
  • Page 41: Functional Overview Of The Mb2 Chamber Controller

    The MB2 program controller permits programming temperature and humidity cycles, and specifying the fan speed and special controller functions for each program section. You can enter values or programs directly at the controller or use the APT-COM™ 4 Multi Management Software (accessory) specially developed by BINDER. Operating mode Temperature values...
  • Page 42: Operating Functions In Normal Display

    Operating functions in normal display Current operating mode Text list for information icons Date, time, authorization level of the logged-in user, memory Quick setpoint entry Continue to next screen Back to Normal display Information Program start Setpoint entry Event list Display of active alarms Access to main menu Figure 19: Operating functions of the MB2 controller in normal display (example values)
  • Page 43: Display Views: Normal Display, Program Display, Chart-Recorder Display

    Display views: Normal display, program display, chart-recorder display Press the Change view icon to toggle between normal display, program display and chart-re- corder display. Press the Normal display icon to return from program display and chart recorder display back to Normal display. Normal display (actual values / setpoint values) Program display (example: time program) Chart recorder display...
  • Page 44: Controller Icons Overview

    Controller icons overview Navigation icons in Normal display Icon Signification Function Main menu Access from Normal display to the main menu Alarm Access from Normal display to the list of active alarms Event list Access from Normal display to the event list Access from Normal display to the setpoint entry menu: set- point entry for Fixed value operation, turning on/off humidity Setpoint setting...
  • Page 45 Functional icons in the chart recorder display Icon Signification Function Show legend Show legend Hide legend Hide legend Switch between legend pages Switch legend Show indications Show indication “Door open” (B2) Hide indication “Door open” (B2) Hide indications Pause chart recorder and change to history display. Data recording History display continues.
  • Page 46: Operating Modes

    Operating modes The MB2 program controller operates in the following operating modes: • Idle mode The controller is not functional, i.e., there is no heating or refrigeration and no humidification or dehu- midification. The fan is off. The chamber approximates ambient values. You can activate and deactivate this operating mode with the “Idle mode”...
  • Page 47: Controller Menu Structure

    Controller menu structure Use the navigation icons in the screen footer in Normal display to access the desired controller functions. The available functions depend on the current authorization level “Service”, “Admin” or “User” (chap. 14.1). This is selected either during login or can be available without password protection. Main menu: program settings, further information, “Service”...
  • Page 48: Main Menu

    • Access to service data, controller reset to factory settings (chap. 5.5.3) • Available only for users with “Service” and “Admin” authorization level. Full functional range only for BINDER Service (users with “Service” authorization level). “Programs” submenu • Access to the controller’s program functions (chap. 8, 10, 11)
  • Page 49: Settings" Submenu

    5.5.3 “Service” submenu The “Service” submenu is available for users with “Service” or “Admin” authorization level. When logged-in with “Admin” authorization level the user will find information to tell the BINDER Service in service case. Path: Main menu > Service Serial number of the chamber, setup version chap.
  • Page 50: Principle Of Controller Entries

    Principle of controller entries In the selection and entry menus there are icons displayed in the footers which you can use to take over the entry or cancel it. Selection menu (example) Entry menu (example) After completing the settings there are the following possibilities: Press the Confirm icon to take over the entries and exit the menu or continue the menu se- quence.
  • Page 51: Performance When Opening The Door

    To reduce odors quickly we recommend running the disinfection program once or twice and in a well- ventilated location. WARNING: If customer should use a BINDER chamber running in non-supervised continu- ous operation, we strongly recommend in case of inclusion of irrecoverable specimen or samples to split such specimen or samples and store them in at least two chambers, if this is feasible.
  • Page 52: Turning On/Off Humidity Control

    Locked operation Provided that the user administration has been activated by the assignment of passwords for the different authorization types, the controller operation is first locked after turning on the unit, recognizable by the closed lock icon in the header. In the locked view the controller provides all display functions.
  • Page 53: Set-Point Entry In "Fixed Value" Operating Mode

    Set-point entry in “Fixed value” operating mode In Fixed value operating mode, you can enter a temperature set-point, a humidity set-point, the fan speed, and the switching-state of special controller functions. All settings made in Fixed value operating mode remain valid until the next manual change. They are saved also when turning off the chamber or in case of toggling to Idle Mode or Program Mode.
  • Page 54: Set-Point Entry For Temperature, Humidity, And Fan Speed Through The "Setpoints" Menu

    Set-point entry for temperature, humidity, and fan speed through the “Set- points” menu Press the Setpoint setting icon to access the “Setpoints” setting menu from Normal display. “Setpoints” menu. Select “Fixed value operation setpoints” to access the individual parameters. • Select the field “Temperature” and enter the desired temperature setpoint. KBF / KBF-UL setting range: -5 °C up to 70 °C, KBF PRO setting range: -20 °C up to 100 °C.
  • Page 55: Direct Setpoint Entry For Temperature And Humidity Via Normal Display

    Direct setpoint entry for temperature and humidity via Normal display Alternatively you can also enter the setpoints directly via Normal display. Normal display. Select the setpoint you want Example: “Temperature” entry menu. Enter the to change. desired setpoint and confirm entry with Confirm icon.
  • Page 56: Timer Program: Stopwatch Function

    Use the “Setpoints” menu to configure the controller functions. “Setpoints” menu. “Functions on/off” entry menu with options. Select the field “Functions on/off”. Mark / unmark the checkbox to activate / deacti- vate the desired function and press the Confirm icon Activated controller function: switching status “1”...
  • Page 57: Performance During Program Delay Time

    • In the field “Program type” select “Timer program”. • Select the field “Program duration” and enter the desired program duration. Press the Confirm icon. • Select the field “Program start” and enter the desired start time of the program in the “Program start” entry menu.
  • Page 58: Hot-Air Disinfection

    Please refer to the operating instructions art. no. 7001-0577 for the ICH-Q1B Light Mod- ule. Note for chambers with the BINDER LED Plant Light Module accessory: The light cas- settes must be removed from the chamber before hot air disinfection is carried out.
  • Page 59: Time Programs

    Time programs The MB2 program controller permits programming time programs with real-time reference. It offers 25 pro- gram memory positions with up to 100 program sections each. Hot-air disinfection is always program 1. For each program section you can enter a temperature set-point, a humidity set-point, the fan speed, sec- tion duration, type of temperature and humidity transition (ramp or step) and the tolerance range.
  • Page 60: Performance During Program Delay Time

    10.1.1 Performance during program delay time During the configured program delay time until program start, the controller equilibrates to the current set- points of Fixed value operation mode. Modifications of these setpoints are effective. When the configured moment for program start is reached, the program delay time ends and the program starts running. 10.2 Stopping a running time program 10.2.1 Pausing a running time program Press the Program pause icon to interrupt the program.
  • Page 61: Creating A New Time Program

    10.4 Creating a new time program Path: Main menu > Programs > Time program “Time program” menu: Enter the program name and, if desired, addi- overview of the existing programs. tional program information in the corresponding fields. Select an empty program place. Press the Confirm icon.
  • Page 62: Deleting A Time Program

    Program editor: “Edit program” menu Select the desired function and press the Confirm icon. The program editor offers following options: • Change the program name • Copy program • Replace program: Replacing an new or an existing program with the copied program. This menu point is visible only after a program has been copied.
  • Page 63: Section Editor: Section Management

    10.6 Section editor: section management Path: Main menu > Programs > Time program Select the desired program.    Program view. Section view (example: section 1). Select the desired program section There are the following options: (example: section 1) ...
  • Page 64: Add A New Program Section

    10.6.1 Add a new program section Section editor: “Edit section” menu. Select “Create new section” and press the Con- firm icon. Then select whether to insert the new section be- fore or after the current section. Press the Confirm icon. The new section opens. 10.6.2 Copy and insert or replace a program section Program view.
  • Page 65: Deleting A Program Section

    Press the Edit icon to open the section editor if you want the current section to be replaced or the copied section to be inserted before or after it Program view. Section view (example: section 1). Select the section to be replaced or before or Press the Edit icon to open the section editor after which the copied section shall be in- serted (example: section 2) and press the...
  • Page 66: Value Entry For A Program Section

    10.7 Value entry for a program section Path: Main menu > Programs > Time program Select the desired program and section. The section view gives access to all parameters of a program section. You can enter or modify the values. Program name and section number Section duration Type of setpoint transition: ramp or step...
  • Page 67: Set-Point Ramp And Set-Point Step

    10.7.2 Set-point ramp and set-point step You can define the type of temperature and humidity transitions for each individual program section. “Ramp” mode: Gradual changes of temperature and humidity The set-point of a given program section functions as the section’s start temperature. During the section’s duration, the set-point gradually passes to the set-point of the subsequent program section.
  • Page 68: Special Controller Functions

    “Ramp” and “Step” mode example (representation of a temperature course) W/°C t/min. Corresponding program table Duration Temperature Humidity Section No. Ramp or Step [hh:mm:ss] [°C] [% rH] 00:10:00 40.0 xxxx xxxx Step 00:20:00 60.0 xxxx xxxx Step 00:10:00 80.0 xxxx xxxx Step 00:20:00...
  • Page 69: Setpoint Entry

    Use the “Setpoints” menu to configure the controller functions. Section view. “Functions on/off” entry menu with options. Select the field “Functions on/off”. Mark / unmark the checkbox of the desired function to activate / deactivate it and press the Confirm icon. The controller returns to the section view.
  • Page 70: Tolerance Range

    10.7.5 Tolerance range You can specify a temperature and humidity program tolerance range for each program section with differ- ent values for the tolerance minimum and maximum. When the actual value exceeds the given threshold, the program is paused. This is indicated on the display (see below). When the actual temperature is situated again within the entered tolerance limits, the program automatically continues.
  • Page 71: Saving The Time Program

    Section view, showing the repetition function • Select the field “Number of repetitions” and enter the desired number of repetitions. Setting range: 1 to 99, and -1 for infinite. Confirm entry with Confirm icon. The controller returns to the section view. •...
  • Page 72: Week Programs

    Week programs The MB2 program controller permits programming week programs with real-time reference. It offers 5 week program places in total with up to 100 shift points for each week program. Path: Main menu > Programs> Week program 11.1 Starting an existing week program In Normal display press the Program start icon to access the “Program start”...
  • Page 73: Creating A New Week Program

    11.3 Creating a new week program Path: Main menu > Programs > Week program Enter the program name and, if desired, addi- “Week program” menu: tional program information in the correspond- overview of the existing programs. ing fields. Select an empty program place. Select the set-point course “Ramp”...
  • Page 74: Program Editor: Program Management

    11.4 Program editor: program management Path: Main menu > Programs > Week program    “Week program” menu: Program view (example: program 1). overview of the existing programs. If a new program has been created, there is Select an existing program (example: pro- just one program section.
  • Page 75: Deleting A Week Program

    To add a new section, select “Create new Program view. section” and press the Confirm icon. With a new section no weekday is specified. There- The program view opens. fore, the section is first marked in red and cannot be saved.
  • Page 76: Section Editor: Section Management

    11.5 Section editor: section management Path: Main menu > Programs > Week program Select the desired program.    Program view. Section view (example: section 1). Select the desired program section There are the following options: (example: section 1) ...
  • Page 77: Add A New Program Section

    11.5.1 Add a new program section Section editor: “Edit section” menu. Program view. With a new section no weekday is specified. There- Select “Create new section” and press the fore, the section is first marked in red and cannot be Confirm icon.
  • Page 78: Deleting A Program Section

    Select “Replace section” to replace the selected sec- tion with the copied section Select “Insert section” to additionally add the copied section. Press the Confirm icon. If you selected “Insert section” the sections are auto- matically arranged in the correct chronological order. Section editor: “Edit section”...
  • Page 79: Weekday

    “Change program name” menu. In the field “Course” select the desired setting “Ramp” or “Step” and press the Confirm icon. 11.6.2 Weekday In the field “Weekday” select the desired weekday. With “Daily” selected, this section will run every day Section view. at the same time.
  • Page 80: Setpoint Entry

    11.6.4 Setpoint entry • Select the field “Temperature” and enter the desired temperature setpoint. KBF / KBF-UL setting range: -5 °C up to 70 °C, KBF PRO setting range: -20 °C up to 100 °C. Confirm entry with Confirm icon. The controller returns to the section view. •...
  • Page 81: Notification And Alarm Functions

    Notification and alarm functions 12.1 Notification and alarm messages overview 12.1.1 Notifications Notifications are indicated by information icons displayed in the screen header in Normal display An information icon serves as an indication of a certain condition. If this condition persists, in some cases an alarm will be triggered after a fix or configurable interval. As long as the condition persists, the information icon therefore continues to be displayed also in state of alarm.
  • Page 82: Alarm Messages

    Start after condition Condition and measures Message occurred The humidity module is defective. Take the chamber out of service and contact BINDER service. “Humidity system” immediately The alarm message must NOT be acknowledged! The humidity module cannot fill up. In case of freshwater supply via water pipe: The water tap is closed, or the chamber is defective “Freshwater...
  • Page 83: State Of Alarm

    The humidity module cannot empty the condensate tank. Wastewater tube obstructed. Check the length and “Wastewater” immediately location of the wastewater tube. If appropriate contact BINDER service. “Evap. outlet sen- KBF: Sensor at the compressor outlet is defective immediately sor”...
  • Page 84: Resetting An Alarm, List Of Active Alarms

    12.3 Resetting an alarm, list of active alarms Normal display in state of alarm (example). List of active alarms. Press the Alarm icon Press the Reset alarm icon. Pressing the Reset alarm icon mutes the buzzer for all active alarms. The icon then disappears. •...
  • Page 85: Activating / Deactivating The Audible Alarm (Alarm Buzzer)

    The user cannot restart the device again. The protective cut-off device is located internally. Only a service specialist can replace it. Therefore, please contact an authorized service provider or BINDER Service. KBF / KBF-UL / KBF PRO (E7) 01/2025...
  • Page 86: Overtemperature Safety Controller Class 2 / 3.3

    13.2 Overtemperature safety controller class 2 / 3.3 The chambers are regularly equipped with an adjustable electronic safety controller. It serves to protect the chamber, its environment and the contents against exceeding the maximum permissible temperature. Please observe the regulations applicable to your country (for Germany: DGUV guidelines 213-850 on safe working in laboratories, issued by the employers’...
  • Page 87: Selecting Between Safety Controller Class 2 (Temperature Limiter) Or Class 3.3 (Temperature Protection)

    • Undertemperature safety controller class 3.2 (undertemperature protection) The class 3.2 safety controller ensures that a minimum temperature value is not fallen below. If the current temperature is below the selected trigger value, the safety controller switches off the refrigerating system.
  • Page 88: Safety Controller Modes

    13.2.2 Safety controller modes You can set the safety controller mode to “Limit” or “Offset”. • Limit: Effective for class 2 / 3.1 overtemperature protection Limit value, absolute maximum permitted temperature value This setting offers high safety as a defined temperature limit will not be exceeded. It is important to adapt the safety controller set-point after each modification of the temperature set-point.
  • Page 89: Setting The Safety Controller Limit Value For Overtemperature

    • In the field “Mode” select the desired setting “Limit” or “Offset”. After completing the settings, press the Confirm icon to take over the entries and exit the menu, or press the Close icon to exit the menu without taking over the entries. Regularly check the safety controller setting for set-point type “Limit”...
  • Page 90: Setting The Safety Controller Value For Undertemperature Protection With Safety Controller Mode "Limit

    13.3.1 Setting the safety controller value for undertemperature protection with safety con- troller mode “Limit” Path: Main menu > Settings > Various Submenu “Various”. • Select the field “Limit (low)” and enter the desired safety controller limit value for undertemperature. Confirm entry with Confirm icon.
  • Page 91: Function Check

    • All passwords can be changed in the “log out” submenu (chap. 14.3). “Service” authorization level • Authorization level only for BINDER service • Extensive authorization for controller operation and configuration, access to service data • The passwords for “Service”, “Admin” and “User” authorization levels can be changed in the “log out”...
  • Page 92 As soon as a password has been assigned for an authorization level, the access to this level and the related controller functions are only available after log-in with the appropriate password. If for an authorization level no password is assigned, the related controller functions of this level are avail- able for every user without login.
  • Page 93 Information window To check the authorization level of the user currently logged-in, select in Normal display the arrow far right in the display header. The information window shows date and time, the controller’s free memory space and under “Authorization” the authorization level of the current user. If passwords have been assigned for all authorization levels, a user without login (password entry) has no authorization.
  • Page 94: Log In

    14.2 Log in Path: Main menu > User > Log in Controller with- out a user logged-in Selection of user type (example) All selection possibilities are password protected Controller with logged-in user After completing the settings, press the Confirm icon to take over the entries and exit the menu, or press the Close icon to exit the menu without taking over the entries.
  • Page 95: Log Out

    14.3 Log out Path: Main menu > User > Log out User logoff with “Admin” authorization Controller Controller with without a user logged-in user logged-in User logoff with “User” authorization Controller Controller with without a user logged-in user logged-in 14.4 User change If the password function has been deactivated (chap.14.5.2) this function is not available.
  • Page 96: Password Assignment And Password Change

    User selection (example) All selection possibilities are password protected Controller with logged- in user 14.5 Password assignment and password change This function is not available for a user logged-in with “User” authorization. 14.5.1 Password change A logged-in user can change the passwords of his current level and of the next lower level(s). Example: A user with “Admin”...
  • Page 97 Selection of the authorization level Enter desired password. If desired, press the Change (example: view with “Admin” authorization) keyboard icon to access other entry windows. In the “Keyboard switch” window you can select different keyboards to enter uppercase and lowercase letters, digits, and special characters.
  • Page 98: Deleting The Password For An Individual Authorization Level

    14.5.2 Deleting the password for an individual authorization level A user logged-in with “Service” or “Admin” authorization can delete the passwords of his current level and of the next lower level(s). To do this no password is entered during a password change. Path: Main menu >...
  • Page 99: New Password Assignment For "Service" Or "Admin" Authorization Level When The Password Function Was Deactivated

    14.5.3 New password assignment for “service” or “admin” authorization level when the password function was deactivated If the password protection for an authorization level has been deactivated, i.e., no password is assigned, no login for this level is possible. Therefore, access to this authorization level is available without login. If the password for the “Service”...
  • Page 100: Activation Code

    14.6 Activation code Certain functions of the controller can be unlocked with a previously generated activation code. The activation code enables access to functions available only in the “Service” authorization level by users without a “Service” authorization. Such functions include e.g., adjustment or extended configurations. The activation code is available in authorization levels.
  • Page 101: General Controller Settings

    General controller settings Most of the general settings can be accessed in the “Settings” submenu, which is available for users with “Service” or “Admin” authorization level. It serves to enter date and time, select the language for the con- troller menus and the desired temperature unit and to configure the controller’s communication functions. 15.1 Selecting the controller’s menu language The MB2 program controller communicates by a menu guide using real words in German, English, French, Spanish, and Italian.
  • Page 102 Or later: Path: Main menu > Settings > Date and time “Date and time” submenu. “Date / time” entry menu. Select the field “Date / time”. Enter date and time and press the Confirm icon. “Date and time” submenu. “Date and time” submenu. In the field “Daylight saving time switch”...
  • Page 103: Selecting The Temperature Unit

    15.3 Selecting the temperature unit Following start-up of the chamber: Or later: Path: Main menu > Settings > Chamber Select the desired temperature unit and press the Confirm icon. Change of the temperature unit between °C and °F. If the unit is changed, all values are converted accordingly C = degree Celsius 0 °C = 31°F...
  • Page 104: Touchscreen Calibration

    • Select the field “Brightness”. Move the grey slide to the left or right to define the brightness of the display • left = darker (minimum value: 0) • right = brighter (maximum value: 100) Press the Confirm icon. • Select the field “Wait time for screen saver” and enter the desired waiting time for the screen saver in seconds.
  • Page 105: Network And Communication

    15.5 Network and communication For these settings at least the “Admin” authorization level is required. 15.5.1 Ethernet 15.5.1.1 Configuration Path: Main menu > Settings > Ethernet “Ethernet” submenu. • In the field “IP address assignment” select the desired setting “Automatic (DHCP)” or “Man- ual”.
  • Page 106: E-Mail

    15.5.1.2 Display of MAC address Path: Main menu > Device info > Ethernet “Ethernet” submenu (example). 15.5.2 E-Mail As soon as an alarm was triggered, an e-mail is sent to the configured e-mail address. Path: Main menu > Settings > Email E-mail address entry: “Email”...
  • Page 107: Usb Menu: Data Transfer Via Usb Interface

    • In the field “Authentication” select the desired setting “None” or “SMTP auth“. With the setting “SMTP auth”, you can enter a password under “Email password”. • Select the field “Email user name” and enter the desired user name. Confirm entry with Confirm icon. •...
  • Page 108: General Information

    Function Explanation Import configuration and programs Import configuration and timer / time / week programs Export configuration and programs Export configuration and timer / time / week programs Import programs Import timer / time / week programs Export service data Export service data (including self-test data, chap.
  • Page 109: Event List

    (chap. 17.2) the Event list is cleared. 16.4 Technical chamber information Path: Main menu > Device info Chamber name and setup Versions of CPU, I/O module and safety for BINDER controller Service Information on digital and analog inputs for BINDER and outputs and phase angle outputs...
  • Page 110: Self-Test Function

    The results of the self-test are stored in the service recorder of the controller. You can export them using the controller’s USB interface and send them to BINDER Service (use function “Export service data” to USB stick, chap. 15.6). BINDER Service will evaluate the data using an analyzing tool.
  • Page 111 Alarm message “Self-test active”. “Active alarms” menu. The self-test program is running. The indicated The zero-voltage relay alarm output is not acti- set-points are non-functional. vated with the alarm message “Self-test active”. With enabled buzzer: the buzzer sounds. Press the Reset alarm icon to mute the buzzer. Press the Alarm icon to access the “Active alarms”...
  • Page 112: Chart Recorder Display

    Chart recorder display This view offers graphic representation of the measurement course. Data representation imitates a chart recorder and allows recalling any set of measured data at any point of time taken from the recorded period. 17.1 Views Press the Change view icon to access the pen recorder display. 17.1.1 Show and hide legend Show legend Hide legend...
  • Page 113: Show And Hide Specific Indications

    17.1.3 Show and hide specific indications Show indications Hide indications Press the Show indications icon to display the indication “Door open” (B2). Indication “Door open” displayed. 17.1.4 History display History display Press the History display icon to change to the history display. History display.
  • Page 114 History display: Curve selection Curve selection Press the Curve selection icon to access the “Curve selection” submenu. “Curve selection” submenu. Select the curves to be displayed by checking the checkbox of the corresponding parameter. Press the Confirm icon History display: Search the required instant Search Press the Search icon to access the “Search”...
  • Page 115 History display: Zoom function Zoom Press the Zoom icon to access the “Zoom” submenu. “Zoom” submenu. Select the zoom factor and press the Confirm icon History display: Show and hide scroll buttons to scroll to an instant Show scroll buttons Hide scroll buttons Press the Show scroll buttons icon to access the “Page selection”...
  • Page 116: Setting The Parameters

    17.2 Setting the parameters This menu allows setting the storage interval, the type of values to be shown and the scaling of the tem- perature and humidity charts. Path: Main menu > Settings > Measurement chart “Measurement chart” submenu (with options) •...
  • Page 117: Humidification / Dehumidification System

    Humidification / dehumidification system The chamber is equipped with a capacitive humidity sensor. This results in a control accuracy of up to +/- 3,5 % r.h. of the set point. The temperature-humidity diagrams (Figure 20) show the possible working ranges for humidity. •...
  • Page 118 Heat emission of electrical devices connected inside the chamber may modify the tempera- ture and humidity range. The chambers are equipped with a door heating system to prevent condensation in the door area. If the set points for temperature or humidity are outside the optimum range, condensation can arise in the door area.
  • Page 119: Function Of The Humidifying And Dehumidifying System

    • Water intake temperature NOT below +5 °C / 41 °F and not exceeding 40 °C / 104 °F. BINDER GmbH is NOT responsible for the water quality provided by the customer. Any problems and malfunctions that might arise following use of water of deviating quality is excluded from liability by BINDER GmbH.
  • Page 120: Dehumidifying System

    For error indications concerning water supply and humidity system, see chap. 12.1.3 and 23.3. Defrosting at refrigerating operation BINDER constant climate chambers are very diffusion-proof. To ensure high temperature precision there is no automatic cyclic defrosting device. The refrigerating system largely avoids icing of the evaporator.
  • Page 121: Anti-Condensation Protection

    In case of heavy condensation, check tightness of the door gasket. After one- or two-days operation at a set-point < 0 °C / 32 °F a thin ice layer can cover the inner chamber door and the front margins of the inner chamber. The amount depends of the ambient temperature and humidity.
  • Page 122: Options And Accessories

    APT-COM™ 4 Basic Edition is included with the chamber. APT-COM™ 4 is available for download on the BINDER website. Upon registering the chamber, you will receive a license key with which you can activate the functionality of the Basic Edition for your downloaded version.
  • Page 123: Zero-Voltage Alarm Contacts For Collective Alarm Output (Option)

    The connection is realized as a socket (I) in the control panel on the chamber rear as follows: ANALOG OUTPUT 4-20 mA DC PIN 1: Temperature – PIN 2: Temperature + PIN 3: Humidity – PIN 4: Humidity + Temperature range: -30 °C / -22 °F to +120 °C / 248 °F Humidity range: 0 % r.h.
  • Page 124: Internal Led Light (Option)

    The alarm message on the controller display remains displayed during transmission of an alarm via the zero-voltage relay outputs. As soon as the cause of the alarm is rectified, or the alarm message has been reset, the alarm transmission via the zero-voltage relay outputs is reset together with the alarm message on the controller display.
  • Page 125: Activating/Deactivating Object Temperature Control

    The object temperature data are put out together with the data of the temperature / humidity controller and can be documented by the APT-COM™ 4 Multi Management Software (option, chap. 21.1) developed by BINDER. 21.5.1 Activating/deactivating object temperature control The controller function “Object temp. control” serves to activate this function in Fixed value operation (chap.
  • Page 126: Setting The Maximum Deviation

    Path: Main menu > Settings > Various Submenu “Various” with object temperature control option and the setting parameters • Select the field “Obj. contr. sensitiv.” and enter the desired sensitivity value. Setting range: 1% up to 100%. Confirm entry with the Confirm icon. 21.5.3 Setting the maximum deviation The purpose of setting the maximum deviation is to ensure that the interior of the chamber or the load does not become too hot due to the ambient interior temperature while the set-point temperature inside the load...
  • Page 127: External Freshwater And Wastewater Cans (Accessories)

    21.6 External freshwater and wastewater cans (accessories) If no suitable in-house water connection is available, you can manually supply water by filling the optional external freshwater can. There is an additional external water can for the wastewater. Volume: 20 liters / 0.71 cu.ft.
  • Page 128 KBF / KBF-UL / KBF PRO Figure 24: Connection diagram of the cans to the constant climate chamber (R) (Q1) (Q2) (P) Front and connections Rear view with magnets Figure 25: Pump box (R) Cable connection to the floating switch (P) Cable connection to the socket(O) on the rear chamber wall (Q1) Hose connection (Q1) for freshwater from the freshwater can (Q2) Hose connection (Q2) for freshwater to the chamber...
  • Page 129: Connections Of The Freshwater Can And The Pump Box

    21.6.1 Connections of the freshwater can and the pump box Hose connections from the freshwater can to the pump box Connect the fresh water hose to the hose connection (Q) on top of the fresh water can and secure it with a hose clamp.
  • Page 130: Connecting The Wastewater Can

    Hose connection from the pump box to the constant climate chamber Plug the freshwater hose on the hose connection (Q2) on the right side of the pump box and secure it with a hose clamp. You can use a section of the standard supplied water hose. Screw the hose nozzle (brass) to the free edge of the hose and screw it directly onto the freshwater con- nection “IN”...
  • Page 131: Binder Pure Aqua Service (Accessory)

    21.7 BINDER Pure Aqua Service (accessory) The optional BINDER water treatment system (disposable system) is available to treat tap water. The life- time depends on water quality and the amount of treated water used. The measuring equipment to assess the water quality is reusable.
  • Page 132 Do not use cleaning agents that may cause a hazard due to reaction with components of the device or the loading material. If there is doubt regarding the suitability of cleaning products, please contact BINDER service. We recommend using the neutral cleaning agent Art. No. 1002-0016 for a thorough cleaning.
  • Page 133: Decontamination / Chemical Disinfection

    For chemical disinfection, we recommend using the disinfectant spray Art. No. 1002-0022. Any corrosive damage that may arise following use of other disinfectants is excluded from lia- bility by BINDER GmbH. With every decontamination / disinfection method, always use adequate personal safety con- trols.
  • Page 134: Maintenance And Service, Troubleshooting, Repair, Testing

    For personnel requirements please refer to the Service Manual. • Repair Repair of the chamber can be performed by BINDER Service or by BINDER qualified service partners or technicians, in accordance with the description in the Service Manual. After maintenance, the chamber must be tested prior to resuming operation.
  • Page 135: Simple Troubleshooting

    If there are is a technical fault or shortcoming, take the chamber out of operation and inform BINDER Service. If you are not sure whether there is a technical fault, proceed ac- cording to the following list. If you cannot clearly identify an error or there is a technical fault, please contact BINDER Service.
  • Page 136 (chap. 4.7). Chamber without function. Check chamber fuse and replace Chamber fuse has responded. it if appropriate. If it responds again, contact BINDER service. Controller defective. Nominal temperature exceeded by Contact BINDER service. 10° due to chamber failure. Over temperature protective device (class 1) responds.
  • Page 137 Main power switch turned off. Turn on the main power switch. Log in with the required higher Menu functions not available with authorization. or contact BINDER Menu functions not available. current authorization level. service to obtain an activation code (chap. 14.6).
  • Page 138: Sending The Chamber Back To Binder Gmbh

    23.4 Sending the chamber back to BINDER GmbH If you return a BINDER product to us for repair or any other reason, we will only accept the product upon presentation of an authorization number (RMA number) that has previously been issued to you. An au- thorization number will be issued after receiving your complaint either in writing or by telephone prior to your sending the BINDER product back to us.
  • Page 139: Disposal

    (Elektro- und Elektronikgerätegesetz, ElektroG from 20 October 2015, BGBl. I p. 1739) or contact BINDER service who will organize taking back and disposal of the cham- ber according to the German national law for electrical and electronic equipment (Elektro- und El- ektronikgerätegesetz, ElektroG from 20 October 2015, BGBl.
  • Page 140 Elektronikgerätegesetz, ElektroG from 20 October 2015, BGBl. I p. 1739).  Instruct BINDER Service to dispose of the device. The general terms of payment and delivery of BINDER GmbH apply, which were valid at the time of purchasing the cham- ber.
  • Page 141: Disposal Of The Chamber In The Member States Of The Eu Except For The Federal Republic Of Germany

    According to Annex I of Directive 2012/19/EU of the European Parliament and of the Council on waste electrical and electronic equipment (WEEE), BINDER devices are classified as “monitoring and control instruments” (category 9) only intended for professional use”. They must not be disposed of at public col- lecting points.
  • Page 142: Disposal Of The Chamber In Non-Member States Of The Eu

    (certified since December 1996 by TÜV CERT). All test equipment used is subject to the administration of measurement and test equipment that is also a constituent part of the BINDER QM DIN EN ISO 9001 systems. They are controlled and calibrated to a DKD-Standard at regular intervals.
  • Page 143: Definition Of Usable Volume

    25.3 Definition of usable volume The usable volume illustrated below is calculated as follows: A, B, C = internal dimensions (W, H, D) a, b, c = distance to wall a = 0.1*A b = 0.1*B c = 0.1*C = (A - 2 * a) * (B - 2 * b) * (C - 2 * c) Figure 29: Determination of the useable volume The technical data refers to the defined usable volume.
  • Page 144 Chamber size 1060 1600 Interior dimensions (continued) 400 / 575 / 575 / 575 / 850 / 850 / Depth mm / inch 15.75 22.64 22.64 22.64 33.46 33.46 467 / 719 / 1063 / 1594 / Interior volume l / cu.ft. 130 / 4.59 262 / 9.25 16.49 25.39...
  • Page 145 +22 °C +/- 3°C / 71.6 °F +/- 5.4 °F and a power supply voltage fluctuation of +/-10%. Specification of the sound pressure level +/- 1 dB(A). Technical data is determined in accordance to BINDER Factory Standard Part 2:2015 and DIN 12880:2007.
  • Page 146: Kbf Pro Technical Data

    Refrigerating performance decreases while operating the chamber at temperatures < 0 °C / 32 °F due to icing of the evaporators. For this reason, defrost the chamber regularly, e.g. once a week. Bringing a source of humidity into the inner chamber will affect the minimum humidity specifi- cation and may affect the humidity accuracy.
  • Page 147 +22 °C +/- 3°C / 71.6 °F +/- 5.4 °F and a power supply voltage fluctuation of +/-10%. Specification of the sound pressure level +/- 1 dB(A). Technical data is determined in accordance to BINDER Factory Standard Part 2:2015 and DIN 12880:2007.
  • Page 148: Equipment And Options (Extract)

    25.6 Equipment and options (extract) To operate the chamber, use only original BINDER accessories or accessories / components from third-party suppliers authorized by BINDER. The user is responsible for any risk arising from using unauthorized accessories. Regular equipment...
  • Page 149: Accessories And Spare Parts (Extract)

    25.7 Accessories and spare parts (extract) BINDER GmbH is responsible for the safety features of the chamber only, provided skilled electricians or qualified personnel authorized by BINDER perform all maintenance and repair, and if components relating to chamber safety are replaced in the event of failure with original spare parts.
  • Page 150 (18 measuring points temperature, 1 measuring point humidity) Spatial temperature and humidity measurement including certificate DL300327 (27 measuring points temperature, 1 measuring point humidity) For information on components not listed here, please contact BINDER Service. KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 150/172...
  • Page 151: Dimensions

    25.8 Dimensions Dimensions size 130: [mm] KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 151/172...
  • Page 152 Dimensions size 260: [mm] KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 152/172...
  • Page 153 Dimensions size 470: [mm] KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 153/172...
  • Page 154 Dimensions size 720: [mm] KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 154/172...
  • Page 155 Dimensions size 1060: [mm] KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 155/172...
  • Page 156 Dimensions size 1600: [mm] KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 156/172...
  • Page 157: Certificates And Declarations Of Conformity

    Certificates and declarations of conformity 26.1 EU Declaration of Conformity for KBF KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 157/172...
  • Page 158 KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 158/172...
  • Page 159 KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 159/172...
  • Page 160: Eu Declaration Of Conformity For Kbf Pro

    26.2 EU Declaration of Conformity for KBF PRO KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 160/172...
  • Page 161 KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 161/172...
  • Page 162 KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 162/172...
  • Page 163: Ukca Declaration Of Conformity For Kbf

    26.3 UKCA Declaration of Conformity for KBF KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 163/172...
  • Page 164: Ukca Declaration Of Conformity For Kbf Pro

    26.4 UKCA Declaration of Conformity for KBF PRO KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 164/172...
  • Page 165: Certificate For The Gs Mark Of Conformity Of The "Deutsche Gesetzliche Unfallversicherung E.v." (German Social Accident Insurance) Dguv

    26.5 Certificate for the GS mark of conformity of the “Deutsche Gesetzliche Un- fallversicherung e.V.“ (German Social Accident Insurance) DGUV KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 165/172...
  • Page 166 KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 166/172...
  • Page 167: Contamination Clearance Certificate

    Contamination clearance certificate 27.1 For chambers located outside USA and Canada Declaration regarding safety and health Erklärung zur Sicherheit und gesundheitlichen Unbedenklichkeit The German Ordinance on Hazardous Substances (GefStofV), and the regulations regarding safety at the workplace, require that this form be filled out for all products that are returned to us, so that the safety and the health of our employees can be guaranteed Die Sicherheit und Gesundheit unserer Mitarbeiter, die Gefahrstoffverordnung GefStofV und die Vorschriften zur Si- cherheit am Arbeitsplatz machen es erforderlich, dass dieses Formblatt für alle Produkte, die an uns zurückgeschickt...
  • Page 168 Transportweg/Spediteur: Transport by (means and name of transport company, etc.) Versendung durch (Name Spediteur o.ä.) ___________________________________________________________________________________ Date of dispatch to BINDER GmbH / Tag der Absendung an BINDER GmbH ___________________________________________________________________________________ KBF / KBF-UL / KBF PRO (E7) 01/2025 Seite 168/172...
  • Page 169 We hereby commit ourselves and guarantee that we will indemnify BINDER GmbH for all damages that are a consequence of incomplete or incorrect information provided by us, and that we will exempt BINDER GmbH from eventual damage claims by third parties./ Wir versichern, dass wir gegenüber BINDER für jeden...
  • Page 170: For Chambers Located In Usa And Canada

    Please complete this form and the Customer Decontamination Declaration (next 2 pages) and attach the required pictures. E-mail to: IDL_SalesOrderProcessing_USA@binder-world.com After we have received and reviewed the complete information we will decide on the issue of a RMA num- ber. Please be aware that size specifications, voltage specifications as well as performance specifications are available on the internet at www.binder-world.us...
  • Page 171 Customer (End User) Decontamination Declaration Health and Hazard Safety declaration To protect the health of our employees and the safety at the workplace, we require that this form is com- pleted by the user for all products and parts that are returned to us. (Distributors or Service Organizations cannot sign this form) NO RMA number will be issued without a completed form.
  • Page 172 4.5 Shipping laws and regulations have not been violated. I hereby commit and guarantee that we will indemnify BINDER Inc. for all damages that are a con- sequence of incomplete or incorrect information provided by us, and that we will indemnify and hold harmless BINDER Inc.

Table of Contents