Certified technicians or those individuals
!
WARNING
meeting the requirements specified by
NATE may use this information. Property
and product damage or personal injury hazard may occur
without such background.
All power sources should be disconnect-
WARNING
!
ed prior to servicing. Failure to do so may
cause personal injury or property dam-
age.
Product designed and manufactured to
!
WARNING
permit installation in accordance with lo-
cal and national building codes. It is the
installer's responsibility to ensure that product is installed
in strict compliance with national and local codes. Manufac-
turer takes no responsibility for damage (personal, product
or property) caused due to installations violating regula-
tions. In absence of local/state codes, refer to National Elec-
tric Code: NFPA 90A & 90B Uniform Mechanical Code.
When this unit is installed in an enclosed
!
WARNING
area, such as a garage or utility room with
any Carbon Monoxide producing devices
(i.e. automobile, space heater, water heater etc.) ensure that
the enclosed area is properly ventilated.
Only factory authorized kits and acces-
!
CAUTION
sories should be used when installing or
modifying this unit unless it is so noted in
these instructions. Some localities may require a licensed
installer/service personnel.
Unit is not approved for outdoor installa-
WARNING
!
tions.
The unit is designed for operation with
!
WARNING
208/240 V, single phase, 60 Hz power sup-
ply. Aspen will not be reponsible for dam-
ages caused due to modification of the unit to operate with
alternative power sources.
# 123119
AAM and AEM Series - Multi-Position
Air Handler (Electric Heat)
1. Safety Instruction
Potential safety hazards are alerted using the following symbols. The symbol is used in conjunction with terms
that indicate the intensity of the hazard.
WARNING
!
This symbol indicates a potentially hazardous situation, which if not avoided,
could result in serious injury, property damage, product damage or death.
!
This symbol indicates a potentially hazardous situation, which if not avoided,
CAUTION
may result in moderate injury or property damage.
INSTALLATION GUIDE
2. Introduction
The AAM Series air handlers are versatile multi-positionable units.
These air handlers have the following standard features:
I. Application Versatility
Upflow or horizontal right as shipped (field-convertible for down-
flow or horizontal left applications). Can be ARI matched with most
brands of air conditioners or heat pumps for use with either R22 or
R410a when proper metering device is used.
II. Cabinet
Sturdy, galvanized steel cabinet with painted front panels. Cabinet
fully insulated with 1/2" faced insulation to prevent sweating and
mold growth, to encapsulate glass fibers, and to provide excellent R-
value. Stick pins ensure insulation remains in place. Units ship with
disposable filter in filter rack.
III. Modular Heat Kits
Heat kits available with either circuit breakers or terminal blocks.
Available from 3 to 30 KW. Models with electric heat include se-
quencers and temperature limit switches for safe, efficient operation.
Modules are easily installed in the field using molex plugs or can be
ordered factory-installed. Controls are accessible from the front for
easy service. Electrical connections can be made from the top or left.
Disconnect does not protrude through the wall panel. Fan time delay
relay standard for increased efficiency.
IV. Electronic Circuit Board
Electronic circuit board provides 30 secs ON/OFF blower time delay
extracting more heat/cool from the coil.
V. Blower
Direct drive multi-speed blowers circulate air quietly and efficiently.
3-speed motors allow for precise air volume selection. Motor speeds
can be easily selected via motor terminals. Blowers mounted on rails
so they can be easily removed for service.
VI. DX Coil
High efficiency rifled copper tubes/enhanced aluminum fins provide
maximum heat transfer. All coils immersion tested at 500 psi then ni-
trogen pressurized and factory sealed for maximum reliability. Liquid-
line Schrader allows pre-installation pressure testing. Available with
1