Aspen DA Series Installation Manual

Cased/uncased upflow/downflow aluminum coils

Advertisement

Quick Links

Product designed and manufactured to
!
WARNING
permit installation in accordance with lo-
cal and national building codes. It is the
installer's responsibility to ensure that product is installed
in strict compliance with the aforementioned codes. Manu-
facturer assumes no responsibility for damage (personal,
product or property) caused due to installations violating
regulations.
Certied technicians or those individuals
!
WARNING
meeting the requirements specied by
NATE may use this information. Property
and product damage or personal injury hazard may occur
without such background.
All power sources should be discon-
!
WARNING
nected prior to servicing. Failure to do
so may cause personal injury or property
damage.
2. Inspection
ü On receiving the product, visually inspect it for any major shipping
related damages. Shipping damages are the carrier's responsibility.
Inspect the product labels to verify the model number and options
are in accordance with your order. Manufacturer will not accept dam-
age claims for incorrectly shipped product.
3. Installation Preparation
ü Read all the instructions in this guideline carefully while paying
special attention to the WARNING and CAUTION alerts. If any of
the instructions are unclear, clariy with a certiied technician beore
proceeding. Gather all tools needed for successful installation of the
unit prior to beginning the installation. Check coils for leaks prior
to installation.
4. Condensate Drain Preparation
ü Aspen recommends an auxiliary drain pan be provided and in-
stalled by the installing contractor, which should be properly sloped,
installed according to code, and terminated in an area visible to the
home owner. The auxiliary pans provide extra protection to the area
under the unit should the primary and secondary drain plug up and
overow.
1. Saety Instruction
Potential safety hazards are alerted using the following symbols. The symbol is used in conjunction with terms
that indicate the intensity of the hazard.
WARNING
!
This symbol indicates a potentially hazardous situation, which if not avoided,
could result in serious injury, property damage, product damage or death.
!
This symbol indicates a potentially hazardous situation, which if not avoided,
CAUTION
may result in moderate injury or property damage.
INSTALLATION GUIDE
DA Series - Uncased Uplow/Downlow Aluminum Coils
DC Series - Cased Uplow/Downlow Aluminum Coils
DE Series - Cased Multi-Position Aluminum Coils
DM Series - Uncased Downflow Aluminum Coils For Use With
Manufactured Home Furnaces
As expressed in our product warranty;
WARNING
!
ASPEN WILL NOT BE BILLED FOR ANY
STRUCTURAL DAMAGES CAUSE BY
FAILURE TO FOLLOW THIS INSTALLATION REQUIREMENT.
Drain lines from the auxiliary drain pan
!
CAUTION
should NOT be connected to the primary
drain line of the coil.
Do NOT install coils with standard
WARNING
!
temperature drain pan with oil furnaces
or applications where temperature of the
drain pan might exceed 290 ºF. A high-temp plastic
or metal pan should be installed.
ü Install coils with the drain pan and/or casing on a at, level sur-
face. Slope the coil 1/4" towards the drain. Condensate lines must
be installed in accordance with building codes. It is the contractor's
responsibility to ensure proper condensate drainage at the time of
the installation; Aspen bears no responsibility for damages caused
by improper condensate management.
Some coils have primary and secondary
!
CAUTION
drain ports on both sides of the pan to
ofer installation exibility, so ensure all
threaded plugs are in present and tightened in any unused
drain ports. These may be hidden behind the coil casing
access door. Failure to do so may result in property water
damage; it is the contractor's responsibility to ensure these
plugs are present and tight.
ü The drain lines must be installed with ¼" per foot pitch to provide
free drainage. A condensate trap MUST be installed on the primary
drain line to ensure proper drainage of the condensate. The trap
must be installed in the drain line below the bottom of the drain pan.
Fig. 4-1 illustrates the typical drain trap installation. Prior to instal-
lation, ensure drain pan hole is not obstructed. Additionally, Aspen
recommends the drain lines be insulated to prevent sweating and
dripping.
Fig 4-1. Typical drain line trap set up
1
2" MIN.
3" MIN.

Advertisement

loading
Need help?

Need help?

Do you have a question about the DA Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Aspen DA Series

  • Page 1 4. Condensate Drain Preparation 2” MIN. ü Aspen recommends an auxiliary drain pan be provided and in- stalled by the installing contractor, which should be properly sloped, installed according to code, and terminated in an area visible to the home owner.
  • Page 2: Coil Installation

    ü Can be installed in either an upow or a downow application. Coil should be installed on the discharge CAUTION side of the furnace Aspen coils may include a Schrader valve CAUTION on the suction manifold. Ensure that the Schrader valve and valve core (where present) are protected from heat to prevent leakage.
  • Page 3: Installation

    WARNING while hot. Severe burns may result. 7. Metering Devices/Liquid Line Conection Aspen coils are available with two kinds o metering devices a) ow- rator or b) TXV. The following instructions are separated into sec- tions by metering device. Fig 5B-1. Horizontal Left Application 7A.
  • Page 5 II-8. Tighten the nut to a torque o approximately 10 t-lbs. Do NOT It is recommended that the TXV bulb be installed parallel to the overtighten the nut. Overtightening could crack the nut and/or ground (on a horizontal plane). The bulb position should be at impede the piston movement during operation.
  • Page 7: System Charging

    Using a non-bleed expansion valve may re- CAUTION Aspen cased coils are equipped with a two-piece panel door to allow quire the use of a hard-start kit. Follow the for cleaning and maintenance access. Remove one or both doors to outdoor unit manufacturer’s guidelines.
  • Page 8 373 Atascocita Rd. Humble, TX 77396 Phone: 281.441.6500 Toll Free: 800.423.9007 Fax: 281.441.6510 www.aspenmg.com Revised 05/26/2023. Subject to change without notice and without incurring obligation. © Copyright 2023 Aspen Manuacturing. All Rights Reserved...