Electro Industries'
Hydronic System Interface
TS Series Boiler Compatible
Installation & Operating Instructions
This model is designed and equipped to handle various combinations of zone pumps, various zone valve
types, actuators, etc. The one control board has wiring arrangements for all zone operating devices.
A major feature is built-in automatic stage shedding based upon the capacity of each active zone. This
compensates for any mixture of large and small zones.
Note: Capacity and SIZE dial switches must be set during installation.
Convenience of an attractive wiring center, all connections at easily accessed terminal blocks, LED's, and
simplified zone system installation are also basic to this model.
Special automatic or built-in shift to higher water temperature for priority zone 1. In many combination
temperature installations this feature eliminates mixing valve or injection pump temperature control.
Features
Dual Control Temperature, Priority Zone
Garage Priority Zone Option
Digital or Standard Thermostat Compatible
Compatible with Zone Pumps, Zone Valves (4, 3, 2 Wire Devices), Actuators, Etc.
Fuse Protected, Control Board and Zone Pump Connections
Nineteen Onboard Lights, Each Stat and Zone Output, Diagnostic and Basic Power
Includes Its Own Enclosure
One 120V Hookup Allows For Simple Installation
Remote Data Communication to Boiler Control Board
Drawings: BH031, BH032, XX017
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE
PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
05/08/2012
Zone Controller
Models: EB-ZE*8 and EB-ZT*8
BI013

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EB 27 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Electro Industries EB 27 Series

  • Page 1 Electro Industries’ Zone Controller Hydronic System Interface TS Series Boiler Compatible Installation & Operating Instructions Models: EB-ZE*8 and EB-ZT*8 This model is designed and equipped to handle various combinations of zone pumps, various zone valve types, actuators, etc. The one control board has wiring arrangements for all zone operating devices.
  • Page 2: Table Of Contents

    Table of Contents Page Basic Product Description Placement & Mechanical Information Safety Consideration Product Configurator Specification Table Electrical Data Installation Requirements Installation Overview, Required System Components Mechanical Installation Overview Electrical Hookup Additional Hookup or Special Equipment Concerns Field Setup or Programming Operational Indicators Power On, Start Up Troubleshooting Helps...
  • Page 3 Required Accessories – Electro Industries TS Boiler Model Series Boiler If you are using this zone controller and do not plan on using an Electro Industries’ TS Series Boiler, all unique functions detailed in this manual will not apply. Call the factory for more details.
  • Page 4: Basic Product Description

    Placement & Mechanical Information Locate the unit on a dry indoor wall near the Electro Industries’ TS Series Boiler. There are 4 mounting holes in the rear of the Electro Industries Zone Controller. Using proper fasteners (not provided), and utilize these mounting holes to secure the cabinet to the wall of the structure.
  • Page 5: Product Configurator

    Product Configurator EB-Z*** 4 = 4 Zone 8 = 8 Zone S = Zone Valves, 24V Class 2 A = Zone Pumps, 120V E = with enclosure T = without enclosure Specification Table Electrical Data Maximum Load Model Voltage Static Amps Maximum Source Amps* EB-Z*A8...
  • Page 6: Installation Requirements

    2. At Electro Industries the safety of the installer and the end user is of highest priority. Remember, safety is the installer’s responsibility and the installer must know this product well enough to instruct the end user on its safe use.
  • Page 7: Mechanical Installation Overview

    Dual Fuel Boiler Comments: If the Electro Industries Boiler is being used in a dual fuel application, it must be noted that this zone controller will send hot water to correct calling zone (thermostat) as well as prioritize based on zone controller setting while in standby (non-electric heating mode).
  • Page 8: Electrical Hookup

    Electrical Hookup Installation/Hookup – EB-Z*A8 1. This model has its own enclosure with 40VA transformer. 2. Transformer power – internal transformer has primary taps for 120, 208, 240 volts, 60 hertz, single phase. Route appropriate source to left compartment and connect to transformer wires.
  • Page 9: Additional Hookup Or Special Equipment Concerns

    Boiler Circulator/Pump Information The pump connection and operation to the main boiler depends upon the zone arrangement detailed in the previous section. 1. With zone pumps, you do not use or wire to the zone pump terminal block in the boiler itself. 2.
  • Page 10: Field Setup Or Programming

    Field Setup or Programming Setup – Zone Sizes and Boiler Stage Sizes On the EB-Z**8 zone controller board there are 9 dial switches. Eight relate to each zone and one relates to boiler size information. If all eight zones are not present or used, set the unused dials to 0. From building design information and/or zone capacity calculations, installer must know the approximate Btu/h capacity of each zone.
  • Page 11 Multiple Boilers, Using EB-C-STG5 Staging Relay It is assumed the zoning arrangement has one or two small zones which can be handled by the first boiler and primarily large zones which will require stepping up to the next boilers. There are three boiler size settings and the first decision relates to proper zone connection and discerning the large zones wired into this zone controller.
  • Page 12 7. With stat 1 input and priority switch on, the boiler outlet temperature will regulate at one of two preset values: 150° F or 180° F. At the boiler main control board (hinged door) approximate center left side is a 2-pin jumper associated with the markings J7.
  • Page 13: Operational Indicators

    The number of stages will depend upon capacity calculations from the settings. The capacity dial switch position has an assigned value: 15,000 Btu/h = 0 30,000 Btu/h = 1 45,000 Btu/h = 2 60,000 Btu/h = 3 As the zone stats turn on and off these are added for a boiler staging sum. This sum value controls stage per: 1 = Stage 1 2 = Stage 2...
  • Page 14: Power On, Start Up

    Power On, Start Up Operational Test 1. Thermostat and zone reaction – as each thermostat is turned up there should be an appropriate reaction from the zone pump connected to the correct zone output number and zone thermostat. LED’s for stat input, mode of operation (see diagnostic LED) and bulb lights for zone outputs should follow their appropriate inputs.
  • Page 15: Troubleshooting Helps

    Troubleshooting Helps Troubleshooting 1. The LED’s on this zone control board should provide adequate indication of inputs and outputs. 2. See previous description on priority and dual temp arrangement. 3. If troubleshooting the complete boiler system indicates the desire to unplug the remote bus connector to verify whether or not the zone controller is interacting with the main boiler board, the main boiler must be reset (power off and on) whenever the remote bus cable is unplugged or plugged back in.
  • Page 16 Zone Board Functions, 5406 Stat W inputs – external contact between R and W 1 through 8 terminal block. R to W1 can be priority, if priority switch is on. With priority switch on and W1-in:  K11 form C priority AUX relay contacts ...
  • Page 17: Accessories/Options

    Stat W4 special – depending upon the Electro-Boiler size and associated size dial position, this zone Btu dial switch may be assigned a 2X Btu value. EB-C series Electro-Boiler size positions may also have other Btu/h multipliers. Accessories/Options ES-24-BR – Electro Industries slab sensing thermostats. 05/08/2012 BI013...
  • Page 22: Xx017

    Limited Product Warranty Effective November 1, 2009 Electro Industries warrants to the original owner, at the original installation site, for a period of two (2) years from date of original purchase, that the product and product parts manufactured by Electro...
  • Page 23 Remedies under this warranty are limited to repairing or replacing alleged defective product or product parts. The decision whether to repair or, in the alternative, replace products or product parts shall be made by Electro Industries or its authorized representative.

Table of Contents