INSTALLING
Continued
102664
INSTALLATION CLEARANCES
Maintain the minimum clearances. If you can, provide greater
clearances from floor, ceiling, and adjoining wall.
Carefully follow the instructions below. This will ensure safe installation.
Minimum Wall and Ceiling Clearances (see Figure 7)
A. Clearances from the side of the fireplace opening to any combustible wall should
not be less than 16 inches for a cabinet mantel or 12 inches for a corner installation.
B. Clearances from the top of the fireplace opening to the ceiling should not be
less than 42 inches.
Note: Clearances
are the same if
using optional
cabinet mantel or
built-in installation.
Figure 7 - Minimum Clearance to Wall and Ceiling
CONVENTIONAL FIREPLACE INSTALLATION
Conventional installation of this fireplace involves installing fireplace along with
the cabinet mantel and hearth base accessory against a wall in your home. Follow
the instructions below to install the fireplace in this manner.
For conventional installation, it is recommended you use the
cabinet mantel or hearth bases specified in this manual. Surface
clearances may not be sufficient with other cabinet mantels and
hearth bases. This may create a fire hazard. See Accessories,
page 38 for correct mantels and hearth bases.
Note:
The instructions below show installation using the GMC11F/GMC12U
cabinet mantel and the GC3333F/GC3334U hearth base accessory. The hearth
base accessory shown is optional for this installation. You can install fireplace and
cabinet mantel directly on the floor.
1. Assemble cabinet mantel and hearth base. Assembly instructions are included
with each accessory.
WARNING
WARNING ICON
G 001
MINIMUM CLEARANCE
Side Wall - 16 "
42"
Ceiling - 42"
Floor - 0"
16"
WARNING
WARNING ICON
G 001
Continued
11