Gree GMV-335WL/C1-X Owner's Manual
Gree GMV-335WL/C1-X Owner's Manual

Gree GMV-335WL/C1-X Owner's Manual

Dc inverter multi vrf system

Advertisement

Owner's Manual
Original Instructions
Commercial Air Conditioners
DC Inverter Multi VRF System
Models:
GMV-H224WL/A-X
GMV-H280WL/A-X
GMV-H335WL/A-X
GMV-224WL/C-X
GMV-280WL/C-X
GMV-335WL/C-X
GMV-280WL/C1-X
GMV-335WL/C1-X

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GMV-335WL/C1-X and is the answer not in the manual?

Questions and answers

Summary of Contents for Gree GMV-335WL/C1-X

  • Page 1 Owner's Manual Original Instructions Commercial Air Conditioners DC Inverter Multi VRF System Models: GMV-H224WL/A-X GMV-H280WL/A-X GMV-H335WL/A-X GMV-224WL/C-X GMV-280WL/C-X GMV-335WL/C-X GMV-280WL/C1-X GMV-335WL/C1-X...
  • Page 2 (7) The final right to interpret for this instruction manual belongs to Gree Electric Appliances, Inc. of Zhuhai.
  • Page 3 Exception Clauses Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following reasons: (1) Damage the product due to improper use or misuse of the product. (2) Alter, change, maintain or use the product with other equipment without abiding by the instruction manual of manufacturer.
  • Page 4 Contents 1 Safety Notices (Please be sure to abide them) ............1 2 Product Introduction ....................3 2.1 Names of Main Parts ......................3 2.2 Combinations of Indoor and Outdoor Units ............... 4 2.3 Operating Range ......................4 3 Preparation before Installation ................. 4 3.1 Standard Parts ........................
  • Page 5 DC Inverter Multi VRF System 1 Safety Notices (Please be sure to abide them) WARNING: If not abide them strictly, it may cause severe damage to the unit or the people. NOTE: If not abide them strictly, it may cause slight or medium damage to the unit or the people.
  • Page 6 DC Inverter Multi VRF System Diameter of power cord When the power cord is should be large enough. The connected, please fix the damaged power cord and electric box cover properly to connection wire must be avoid safety accidents. replaced with special cables. Never fail to comply with the Never short circuit or cancel nitrogen-charging welding...
  • Page 7: Product Introduction

    Gree Electric Appliances, Inc. of Zhuhai will not assume responsibility for any personal injury or property loss caused by improper installation, improper debugging, unnecessary repair or not following the instructions of this manual.
  • Page 8: Combinations Of Indoor And Outdoor Units

    GMV-H335WL/A-X GMV-224WL/C-X GMV-280WL/C-X GMV-335WL/C-X GMV-280WL/C1-X GMV-335WL/C1-X (3) Can be connected to various indoor units. When any one of the indoor units receives operating command, outdoor unit will start operation as per required capacity. When all indoor units stop, outdoor unit will be shut off.
  • Page 9: Installation Site

    DC Inverter Multi VRF System Parts for Outdoor Unit Name Appearance Remark Please refer to section 4.5.2 for Magnetic ring the detailed operation method. 3.2 Installation Site Forbidden item! Improper operation might lead to personal injury or even death. Item needs to be followed. Improper operation might lead to personal injury or property damage. Select a location which is strong The installation position should enough to hold unit’s weight so...
  • Page 10: Piping Work Requirements

    NOTE: Graphics here are only for reference. Please refer to actual products. Unspecified dimensions are all in mm. 4.1 Dimension of Outdoor Unit and Mounting Hole Unit Outline and Installation Dimension(mm). Fig.4.1 Unit: mm Model GMV-H224WL/A-X 1430 GMV-H280WL/A-X 1615 GMV-H335WL/A-X 1615 GMV-224WL/C-X 1430 GMV-280WL/C-X 1615 GMV-335WL/C-X 1615 GMV-280WL/C1-X 1615 GMV-335WL/C1-X 1615...
  • Page 11: Connection Pipe

    DC Inverter Multi VRF System 4.2 Connection Pipe 4.2.1 Schematic Diagram of Piping Connection Fig.4.2...
  • Page 12 Fig.4.3: NOTE:Equivalent length of one Y-type branch is 0.5m. Fig.4.3 Allowable Length and Height Difference of Connection Pipe Piping parameters of GMV-H224WL/A-X, GMV-H280WL/A-X, GMV-H335WL/A-X, GMV-224WL/C-X, GMV-280WL/C-X, GMV-335WL/C-X, GMV-280WL/C1-X, GMV-335WL/C1-X: — Allowable value Fitting pipe Total length (actual length) of fitting pipe...
  • Page 13 Φ9.52 GMV-280WL/C-X Φ22.2 Φ9.52 GMV-335WL/C-X Φ25.4 Φ12.7 Welding connection GMV-280WL/C1-X Φ22.2 Φ9.52 GMV-335WL/C1-X Φ25.4 Φ12.7 4.2.4 Selection of Indoor Branches Select indoor branches according to the total capacity of downstream indoor units. If the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
  • Page 14 DC Inverter Multi VRF System 4.2.5 Dimension of Pipe between Indoor Branches Select pipe between indoor branches according to the capacity of downstream indoor units; If the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails. Fig.4.6 Total capacity of downstream indoor units C (kW) Gas pipe(mm) Liquid pipe(mm)
  • Page 15: Installation Of Connection Pipe

    DC Inverter Multi VRF System 4.3 Installation of Connection Pipe 4.3.1 Precautions for the Installation of Connection Pipe (1) Conform to the following principles during pipe connection: Connection pipe should be as short as possible, so is the height difference between indoor and outdoor units. Keep the number of bends as little as possible.
  • Page 16 DC Inverter Multi VRF System (2) Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared nut tightly by hand, as in Fig.4.11 (Make sure indoor pipe is correctly connected. Improper location of the center will prevent flared nut from being securely twisted. Thread of nut will get damaged if the flared nut is twisted forcibly).
  • Page 17 Fig.4.13 Fig.4.14 (2) Pipe connection for GMV-H280WL/A-X, GMV-H335WL/A-X, GMV-280WL/C-X, GMV-335WL/C-X, GMV-280WL/C1-X, GMV-335WL/C1-X: 1) If connection pipe is connected at the front, no special treatment is needed. You can weld the pipeline directly to connection pipe 1 and connection pipe 2.
  • Page 18 DC Inverter Multi VRF System Fig.4.15 Fig.4.16 4.3.6 Installation of Y-type Branch (1) Y-type Branch. Fig.4.17 (2) Y-type branch has several pipe sections with different dimension, which facilitates to match with various copper pipes. Use pipe cutter to cut in the middle of the pipe section that is of proper dimension and remove burrs as well.
  • Page 19: Thermal Insulation For Pipeline

    DC Inverter Multi VRF System Fig.4.18 (4) Branch shall be isolated by insulating material that can bear 120°C or even higher temperature. The attached foam of branch cannot be taken as insulating material. 4.3.7 Thermal Insulation for Pipeline (1) For multi VRF system, every copper pipe should be labeled so as to avoid misconnection. (2) At the branch inlet, leave at least 500mm straight pipe section.
  • Page 20: Vacuum Pumping, Refrigerant Adding

    GMV-H335WL/A-X GMV-224WL/C-X Refrigerant Qty (kg) Model GMV-280WL/C-X GMV-335WL/C-X GMV-280WL/C1-X GMV-335WL/C1-X Refrigerant Qty (kg) NOTES: ① The refrigerant amount charged before delivery doesn’t include the amount that needs to be added to indoor units and the connection pipeline. ② Length of connection pipe is decided on site. Therefore, the amount of additional refrigerant shall be decided on site according to the dimension and length of field-installed liquid pipe.
  • Page 21: Electric Wiring

    DC Inverter Multi VRF System Quantity of additional refrigerant = ∑length of liquid pipe × quantity of additional refrigerant per meter. Quantity of additional refrigerant per meter for liquid pipe(kg/m) Pipe size(mm) Φ22.2 Φ19.05 Φ15.9 Φ12.7 Φ9.52 Φ6.35 Quantity of additional 0.35 0.25...
  • Page 22: Wiring Diagram

    DC Inverter Multi VRF System (4) All electrical installation must be performed by qualified technicians in accordance with local laws, regulations and this user manual. (5) Caliber of the power cord must be large enough. A damaged power cord or connection wire must be replaced by specialized electrical cords.
  • Page 23 × Min sectional cord × Min sectional area (mm area (mm GMV-335WL/C-X 380-415V 3N~ 50/60Hz 1×2.5 4×2.5 GMV-280WL/C1-X 380-415V 3N~ 50/60Hz 1×2.5 4×2.5 GMV-335WL/C1-X 380-415V 3N~ 50/60Hz 1×2.5 4×2.5 NOTES: ① Selection of circuit breaker and power cord in the above table is based upon unit’s maximum power (maximum current).
  • Page 24 DC Inverter Multi VRF System Fig. 4.24 Fig. 4.25 5 Check Items after Installation and Test Operation 5.1 Check Items after Installation Check items Possible conditions due to improper stallation Check Each part of the unit is installed securely? Unit may drop, shake or emit noise. Gas leakage test is taken or not? Insufficient cooling (heating) capacity.
  • Page 25: Test Operation And Debugging

    DC Inverter Multi VRF System Check items Possible conditions due to improper stallation Check Is the electric wiring and pipe connection installed Unit may have malfunction or components may correctly? get damaged. Unit is securely grounded or not? Electrical leakage. Unit may have malfunction or components may Power cord meets the required specification? get damaged.
  • Page 26 DC Inverter Multi VRF System 5.2.2 Test Operation and Debugging Description of test operation procedures and main board display of ODU. Description of each stage of debugging progress — Debugging code Progress code Status code LED1 LED2 LED3 Code meaning and operation method Progress Display Display...
  • Page 27 DC Inverter Multi VRF System Description of each stage of debugging progress — Debugging code Progress code Status code LED1 LED2 LED3 Code meaning and operation method Progress Display Display Display Code Code Code status status status Communication between master ODU and driver has error.
  • Page 28 DC Inverter Multi VRF System Description of each stage of debugging progress — Debugging code Progress code Status code LED1 LED2 LED3 Code meaning and operation method Progress Display Display Display Code Code Code status status status Preheat time for compressor is less than 8 hours.
  • Page 29 DC Inverter Multi VRF System Description of each stage of debugging progress — Debugging code Progress code Status code LED1 LED2 LED3 Code meaning and operation method Progress Display Display Display Code Code Code status status status Debugging for cooling mode. If no malfunction occurs for 20min when compressor is running, then system will start progress 17;...
  • Page 30: Common Malfunctions And Troubleshooting

    ① If an abnormal situation (such as peculiar smell) occurs, please stop the operation immediately and turn off the main power supply, and then contact Gree authorized maintenance center. If the unit continues to operate under abnormal situation, the air conditioner will be damaged and an electric shock or fire accident may result.
  • Page 31 Reduce heat resources. Filter is blocked and dirty. Clean the filter. NOTE: If problem cannot be solved after checking the above items, please contact Gree service center and describe the cases and models. ● Following circumstances are not malfunctions. Phenomenon...
  • Page 32: Error Indication

    DC Inverter Multi VRF System Phenomenon Causes This sound can be heard when other indoor units When the indoor unit stops running, are running. This is to prevent oil and refrigerant a faint “sa——” sound or “gurgling” from staying in the indoor unit, and to keep a small sound can be heard.
  • Page 33 DC Inverter Multi VRF System Error Code Content Error Code Content Malfunction of exit-tube temperature Malfunction of humidity sensor sensor Malfunction of jumper cap Web address of IDU is abnormal PCB of wired controller is abnormal Abnormal setting for capacity button Malfunction of air-outlet temperature Malfunction of indoor CO sensor (fresh air...
  • Page 34: Maintenance And Care

    DC Inverter Multi VRF System Error Code Content Error Code Content Driving board of fan operates abnormally Voltage protection of driving board power of (uniform) fan (uniform) Reset protection of driving module of fan Drive PFC protection of fan Over-current protection of inverter fan —...
  • Page 35: Outdoor Heat Exchanger

    Otherwise, it may lead to danger. Use nitrogen or refrigerant to conduct the tests. 9 After-sales Service If there’s quality defect or other problems in the product, please contact Gree local after-sales service department for help. Warranty must be based on the following conditions.

Table of Contents

Save PDF