Installation For Vertical Termination - Desa (V)T32N SERIES Owner's Operation And Installation Manual

Direct-vent fireplace ng/lp “tudor” models
Table of Contents

Advertisement

VENTING INSTALLATION
INSTRUCTIONS
Continued
INSTALLATION FOR vERTICAL
TERMINATION
Note: Vertical restrictor must be installed in all
vertical installations.
1. Determine the route your vertical venting
will take. If ceiling joists, roof rafters or other
framing will obstruct the venting system,
consider an offset (see Figure 19) to avoid cut-
ting load bearing members. Note: Pay special
attention to these installation instructions for
required clearances (air space) to combustibles
when passing through ceilings, walls, roofs,
enclosures, attic rafters, etc. Do not pack air
spaces with insulation. Also note maximum
vertical rise of the venting system and any
maximum horizontal offset limitations.
2. Set the fireplace in desired location. Drop a
plumb line down from the ceiling to the posi-
tion of the fireplace exit flue. Mark the center
point where the vent will penetrate the ceiling.
Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof
to the locating hole in the ceiling. Mark the
center point where the vent will penetrate the
roof. Drill a small locating hole at this point.
Wall Strap
Figure 19 - Offset with Wall Strap and 45°
Elbows
14
Roof Flashing
45° Elbow
Ceiling Firestop
www.desatech.com
Flat Ceiling Installation
1. Cut a 10" square hole in the ceiling using the
locating hole as a center point. The opening
should be framed to 10" x 10" inside dimen-
sions, as shown in Figure 9 on page 9 using
framing lumber the same size as the ceiling
joists. If the area above the ceiling is an insu-
lated ceiling or attic space, nail firestop from
the top side. This prevents loose insulation from
falling into the required clearance space. If the
area above the ceiling is a living space, install
firestop below the framed hole. The firestop
should be installed with no less than three nails
per side (see Figure 20).
2. Assemble the desired lengths of pipe and
elbows necessary to reach from the fireplace
flue up through the firestop. Be sure all pipe
and elbow connections are fully twist-locked
(see Figure 8, page 9).
3. Cut a hole in the roof using the locating hole as
a center point. (Cover any exposed open vent
pipes before cutting hole in roof.) The 10" x 10"
hole must be measured on the horizontal; actual
length may be larger depending on the pitch of
the roof. There must be a 1" clearance from the
vent pipe to combustible materials. Frame the
opening as shown in Figure 9, page 9.
4. Connect a section of pipe and extend up
through the hole.
Note: If an offset is needed to avoid obstruc-
tions, you must support the vent pipe every 3
feet. Use wall straps for this purpose (see Fig-
ure 19). Whenever possible, use 45° elbows
instead of 90° elbows. The 45° elbow offers
less restriction to the flow of the flue gases
and intake air.
If area above is an attic or insulated area,
install firestop above framed hole.
If area above is a living space, install
firestop below framed hole.
Figure 20 - Installing Firestop
111986-01D

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vt32p seriesT32n seriesT32p seriesChdv32nr series

Table of Contents