Desa VGL18NRA Owner's Operation And Installation Manual page 10

Unvented (vent-free) gas log heater also design-certified as vented decorative appliances when not used with hand-held thermostat remote
Table of Contents

Advertisement

INSTALLATION
Continued
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the informa-
tion below.
You must have noncombustible material(s) above the
fireplace opening. Noncombustible materials (such as
slate, marble, tile, etc.) must be at least 1/2 inch thick.
With sheet metal, you must have noncombustible
material behind it. Noncombustible material must
extend at least 8" up (for all models). If noncombus-
tible material is less than 12", you must install the
fireplace hood accessory (24" and 30" models only).
See Figure 5 for minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
flue damper open. Go to Installing Damper Clamp
Accessory for Vented Operation, page 12.
Noncombustible
Material
Distance (A)
12" or more
Between 8" and 12" Install fireplace hood
Less than 8"
Heat Resistant
Material
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
10
Requirements
for Safe
Installation
Noncombustible
material okay.
accessory (GA6050,
GA6052 or GA6053,
see Accessories,
page 29).
Noncombustible
material must be
extended to at least
8". See Between 8"
and 12", above. If
you cannot extend
material, you must
operate heater with
flue damper open.
(A)
www.desatech.com
If Using Mantel
You must have noncombustible material(s) above
the fireplace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombustible
material must extend at least 8 inches up (for all
models). If noncombustible material is less than
12", you must install the fireplace hood accessory
(24" and 30" models only). Even if noncombustible
material is more than 12", you may need the hood
accessory to deflect heat away from your mantel
shelf. See Figure 5 and Figures 6 and 7 on page 11
for minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
flue damper open. Go to Installing Damper Clamp
Accessory for Vented Operation, page 12.
MANTEL CLEARANCES
In addition to meeting noncombustible material
clearances, you must also meet required clearances
between fireplace opening and mantel shelf. If
you do not meet the clearances listed below, you
will need a hood.
Determining Minimum Mantel Clearances
If you meet minimum clearance between mantel
shelf and top of fireplace opening, a hood is not
required (see Figure 6, page 11).
Determining Minimum Mantel Clearances
When Using a Hood
If minimum clearances in Figure 6, page 11 are not
met, you must have a hood. When using a hood
there are still certain minimum mantel clearances
required. Follow minimum clearances shown in
Figure 7, page 11 when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels be-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem-
peratures meet the requirements
of the national product standard.
Follow all minimum clearances
shown in this manual.
112882-01D

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vgl30praVgl18praVgl24nraVgl24praVgl30nra

Table of Contents

Save Article as PDF