Desa VTN25R Safety Information And Installation Manual page 11

Unvented (vent-free) infrared gas heater
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION
Continued
Pressure
Regulator
Heater
Cabinet
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Tee
Pipe
Joint Nipple
Sediment Trap
Figure 13 - Gas Connection
* A CSA design-certified equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. Purchase the optional CSA
design-certified equipment shutoff valve from your
dealer. See Accessory, page 22.
113261-01C
Equipment
Shutoff
Valve *
3"
(76 mm)
Min.
Cap
Natural Gas
From Gas Meter
[7" (1.8 kPa) WC to
10.5" (2.6 kPa) WC
Pressure]
Propane/LP
From External Regulator
[11" (2.7 kPa) WC to 14"
(3.5 kPa) WC Pressure]
www.desatech.com
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply
a noncorrosive leak detection
fluid to all joints. Bubbles form-
ing show a leak. Correct all leaks
at once.
CAUTION: For propane/LP
gas, make sure external regula-
tor has been installed between
propane/LP supply and heater.
See guidelines under Connect-
ing to Gas Supply, page 10.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main
gas valve (control valve) and equipment
shutoff valve from gas supply piping system.
Pressures in excess of 1/2 psig (3.5 kPa) will
damage heater regulator.
2. Cap off open end of gas pipe where equipment
shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas
or using compressed air.
4. Check all joints of gas supply piping system.
Apply a noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to
gas supply. Check reconnected fittings for leaks.
11