Diagrams and images are not contractual. Cheminées de Chazelles reserves the right to modify or delete them in order to improve understanding. Notice d’installation et d’utilisation. Tout droit de reproduction interdit. Septembre 2012 version 2.0 TAM...
Page 2
Dimensions of the inserts VE600 VE800 VE1000 Notice d’installation et d’utilisation. Tout droit de reproduction interdit. Septembre 2012 version 2.0 TAM...
3.2 Laying out the underbase ..............10 2.1.4 Layout .................... 6 3.3 Installation of the underbase ..............10 3.4 Combustion air inlets for Chazelles VE inserts ........10 2.1.4.1 Bricked flue ............... 6 3.5 Installation of a Chazelles VE insert ............11 2.1.4.2...
Page 4
5.1 Wooden beam ..................18 6.7.1 Removing ashes ................23 5.1.1 General points ................18 6.7.2 Cleaning the window ..............23 5.1.2 Special precautions ..............18 6.7.3 End of season cleaning ............... 23 5.1.3 Upper and lower ventilation ............18 6.7.4 Sweeping..................
General Points Warning 2.1 Flue Set-up of a fireplace equipped with a Chazelles insert must be 2.1.1 General points carried out in compliance with the regulations in force and with all documents supplied with the appliance. The instructions apply Flues must be in compliance with the 1969 directive and with the rules only to construction of a fireplace equipped with an insert using regarding NF DTU 24.1 of February 2006.
2.1.5 Flue discharge end 2.1.2 Dimensioning 2.1.5.1 Stack outlet on roofing The flue must be dimensioned in compliance with the EN 13384- 1 standard, using: The stack outlet must be located 0.4 metres above any part of the building less the abacuses issued by the CSTB, than eight metres distant.
2.1.7 Flue covering 2.2 Safety distance 2.1.7.1 Occupied or habitable areas 2.2.1 General points The surface temperature of the outside facing of the flue must not The element’s safety distance must be greater than that stated by the exceed 50°C in habitable areas. If it does, the flue must either be manufacturer for its anticipated operating temperature, and the minimums in protected by an insulating covering or concealed in boxing or a the NF DTU 24.1 standard.
2.3 Fireplace surround Ventilates air space 2.3.1 General points Thermal insulation All combustible materials must be removed from the fireplace surround. 2.3.2 Flooring The floor must have adequate weight-bearing capacity at the spot selected for the fireplace. It must be flat and incombustible. If this is not the case –...
2.4 Combustion air supply The concrete slab must absolutely be unobstructed for the connection of air inlet duct on the flange of the appliance (see∫3.5.1page 11) 2.4.1 General points 2.4.2 Dimensioning The functioning of a fireplace equipped with an insert requires more air supply than the air which is necessary to renew the air in The combustion air inlet must have a cross-section of at least the house.
3.4 Combustion air inlets for Chazelles VE inserts You must ensure that you comply with all regulations for the combustion air inlet. The appliance is equipped with a direct outside connection in option. In the other 3.3 Installation of the underbase...
For controlling the fire, see the paragraph ‘Instructions for use’ Connection of the box (Option) : §3.5.2.5p14 Unauthorised modification of any kind to a Chazelles insert is Secondary air handle prohibited. Damper Handle Primary air handle...
3.5.2.2.2 Secondary air mechanism Option foyer caréné : la lame d'air entre le carénage et l'isolant doit être de 30 mm minimum. The purpose of the mechanism regulating the secondary air damper is to ensure sweeping of the window to minimise sooting Fireplace with fairing option: The air gap between the fairing and the isolating up and maintain a reduced speed of combustion.
Page 13
- Put the flanges in the right position like on Fig 1 - Kix the flanges with the auto perforating screws and the Fig.3 washers - Fixer les collerettes avec les vis auto-perforantes et les rondelles. 2/ Sides fixations - Assembly the stops thanks to the auto-perforating screws by positioning them like on Fig 3.
- 1 box - 1 flange Ø100 - 1 screw pack - 1 installation manual Feet assembly - Turn over the appliance. - Place the feet as indicate on fig 5 - Assembly the feet with the screws (Fig 6) - Put the fairing on the appliance - Fixed the fairing to the appliance 3.5.2.5...
fig. 8 3.6 Installing the jambs and corbels The appliance must be placed on a stable, flat incombustible base (concrete, for example). It is important to check that a space of between 3 and 5 mm exists between the appliance’s facade and the dressing, allowing for free expansion as well as providing - Embed the elements thanks to glue-cement (glue for gyps-tiles for example) the space necessary for air to pass (30 mm minimum) between...
(equivalent to 30 mm of fibrous insulator of a density less than 100 kg/m with aluminium foil or self-supporting high-temperature Connecting ducts for Cheminées de Chazelles inserts must be metal. structural insulators made of calcium silicate). Aluminium-plated steel must not be used. The diameter of the connecting duct must be at least equal to that of the appliance’s pipe or sleeve.
4.2 Variation of cross section 4.5 Junction of flue and connecting duct If the cross-section of the flue or casing, albeit adequate, differs 4.5.1 Insulated metal flue from the cross-section of the connecting duct, reduction or increase of the cross-section can only be carried out employing a The junction must be carried out on an insulated metal flue using the part shaped to avoid any sudden variation of cross-section.
5.1.1 General points Installation and insulation of the wooden beam and construction of the hood The hood is constructed in the set-up area. The obligatorily decompressed 5.1 Wooden beam hood must be constructed of incombustible or A2-s1, d0 insulating materials. The presence of combustible materials inside the hood is prohibited.
6.4 Instructions for use 6.1 General points 6.4.1 First lightnings Cheminées de Chazelles inserts are designed to operate using Although your fireplace may appear to have dried out fully, it is essential to firewood logs only. Maximum log length for the range of...
6.4.2 Lightnings - place screwed up paper and slivers of very dry wood on the grille or hearth, then pieces of split wood of wider diameter (3 to 5 cm). - Check if the primary air handle is on position: open. - Check if the secondary air handle is on position: open.
Page 21
Primary air register in position 1 and draught shutter closed. Use this Primary air in position 2 and draught shutter closed. brightness only temporarily, at night for example. To maintain ambient temperature, for example. Use this mode only for a short period, at night for example For less intense heating, use a smaller load –...
For long-period heating, with low brightness use one or two unsplit logs with diameters greater than 15 cm (position 1) on a bed of almost dead embers. - Make changes in brightness (from low to normal, for example) before reloading, while embers are burning, to allow the appliance and the flue to modify operation progressively.
6.6 Controls - Spray the window with a cleaning product designed for the purpose (ask your retailer for advise), complying with the instructions on the label. Accessories are at your disposal – use them to avoid getting - Wipe with a damp sponge. burnt! 6.7.3 End of season cleaning The “cool hand”...
7.3 After sales servive Never operate the appliance without the ash box in position. We recommend that you only use replacement parts supplied by Cheminées de Chazelles Notice d’installation et d’utilisation. Tout droit de reproduction interdit. Septembre 2012 version 2.0 TAM...
The guarantee does not apply in the following cases, (this is not an exhaustive list): but not in these alone: installation and assembly of 8.3 Validity appliances for which Cheminées de Chazelles is not responsible. The purchaser designated overleaf acknowledges having Consequently, Cheminées de Chazelles cannot be held responsible for...
Page 26
Guarantee Certificate The purchaser designated hereunder acknowledges his/her awareness of the various informational documents on use and maintenance to ensure proper operation of the appliance PURCHASER VENDOR: document to be returned within the month following Date:……………………………………………………………………… purchase at the sales outlet for the appliance ……...
Need help?
Do you have a question about the VE1000 and is the answer not in the manual?
Questions and answers