Page 3
SPECIFIED GAS MUST BE SUPPLIED BY AUTHORIZED GAS ORGANIZATIONS BEFORE THE COMMISSIONING OF THE BOILER. COMMISSIONING OF THE BOILER MUST BE MADE BY GASSERO’S AUTHORIZED SERVICES. OTHERWISE BOILER WARRANTY WILL BE CANCELLED. THE MANUFACTURER IS NOT THE RESPONSIBLE OF THE DAMAGE DUE TO WRONG OR IMPROPER INSTALLATION OF THE BOILER.
Do not smoke Do not use your phone Close the gas valve immediately Ventilate the space by opening the doors and windows. Notify everyone in the building. WALLCON X-treme 115-125-150...
Page 5
(there may be a ground fault) Do not cut, pull, or bend the cables even if the switch is lowered and the power cut off. DON’T TOUCH THE BOILER WHEN YOUR HANDS ARE WET OR STEPPING ON A WET AREA. WALLCON X-treme 115-125-150...
Boiler Efficiency Directive GENERAL These installation and maintenance instructions are prepared for the wall hung condensing boilers specified below: Wallcon X-treme 115 Wallcon X-treme 125 Wallcon X-treme 150 CE LABEL: This boiler complies with the essential requirements of the relevant European directives. The CE marking...
One of the rights can be used. PURPOSE OF DESIGN Gassero Wallcon X-treme Wall Hung Condensing Boilers with Premix Burners are designed for heating purposes only. For hot water use, the boiler must also be connected to the DHW tank. Boiler can be used with in a cascade system or stand alone.
0°C against the risk of freezing. Read the FROST PROTECTION section. Wallcon X-treme condensing boilers must be installed in spaces that have the necessary ventilation openings according current standards and applicable regulations WALLCON X-treme 115-125-150...
Commissioning must be made by an authorized Gassero service. The boiler must be located in a location that is separate from the living quarters and only in accordance with the ventilation legislation. WALLCON X-treme 115-125-150...
If the carrying capacity of the wall is not sufficient, an external suspension device must be provided. For example; a footed device may be used. For ease of service oparation to the boiler, the necessary distances must be left around the boiler. WALLCON X-treme 115-125-150...
Faults that may arise if the water conditions are not in accordance with the values specified in the table, boiler will be considered out of warranty. WALLCON X-treme 115-125-150...
The methods of flushing / flushing are described in detail in the manual GASSERO DYNAMIC AND CHEMICAL WASHING / FLUSHING. Neutral-based, non-acidic, non-alkaline registered products can be used to clean the installation or keep the water conditions at desired levels.
A neutralization tank should be used for condensate water occurring in systems with a total power of 200 kW and above. It is mandatory to comply with the relevant local regulations for the discharge of condensate water. WALLCON X-treme 115-125-150...
Heating systems which are consist of partly of fully floor heating, Used, older systems, Systems that are dirty, corrosive, bacterial and calcareous water. Periodic inspection and maintenance of the plate heat exchanger is highly important for the efficiency of the system. WALLCON X-treme 115-125-150...
Loud ignition and combustion occurs. Overheating, leakage and deformation would be observed in the flue system. Manufacturer cannot be held liable for damages caused by dirty combustion air. Don’t block the air filter partially or totally. WALLCON X-treme 115-125-150...
Wallcon X-treme boilers equipped with modulated pumps according to the last ErP regulation. Wallcon X-treme 115 Wallcon X-treme 150 Wallcon X-treme 125 FLUE CONNECTIONS Flue and chimney connections must be carried out in accordance with applicable regulations and relevant standards. Materials which are used for the flue and...
CE certified flue pipes. C83 = It is a flue system which takes the combustion air from the outside with horizontal flue pipes and throws flue gas to the self contained (negative pressure) chimney. WALLCON X-treme 115-125-150...
4.3.2 FLUE CONNCETIONS LENGTHS C43,C53 Wallcon X-Treme 115 C63,C83 Air inlet 150 mm 150 mm 150 mm Flue 100 mm 100 mm 100 mm Max. length 17 m 17 m 17 m Δ 100 Pa 100 Pa 100 Pa Max. output (...
Electrical panel connections CABLE will be made by the installation services. Boiler connections from the electrical panel will be BLUE made by authorized Gassero service. YELLOW Room comfort setting and operation mode 2 X 0,75 Room Thermostat: can be adjusted.
Page 24
Supply 2 x 1,5 Pump control 2 x 1,5 ELECTRICAL Supply 2 x 1,5 PANEL Supply 3 x 1,5 Supply 3 x 1,5 Sensor 2 x 0,75 Communcation 2 x 0,75 Outdoor Sensor 2 x 0,75 Sensor 2 x 0,75 WALLCON X-treme 115-125-150...
Maximum length between the control panel and the outside temperature sensor is 50 meters. Sensor cable has to be used as a single cable as possible. Aware of multiple additions as far as possible. WALLCON X-treme 115-125-150...
4. Check-Valve 5. Strainer 6. Thermometer 7. Manometer 8. Air seperator 9. Deposit and dirt seperator 10.Hydraulic seperator or plated heat exchanger 11.Expansion tank 12.Pumps (seconder system) 13.DHW sensor Condensation drain Water filling unit Water softener unit WALLCON X-treme 115-125-150...
Page 28
4. Check-Valve 5. Strainer 6. Thermometer 7. Manometer 8. Air seperator 9. Deposit and dirt seperator 10.Hydraulic seperator or plated heat exchanger 11.Expansion tank 12.Pumps (seconder system) 13.DHW sensor Condensation drain Water filling unit Water softener unit WALLCON X-treme 115-125-150...
/ decrease temperatures, choose and select sub menus, Change the settings. OK BUTTON (C) Used for to apply selected value or setting. In the parameters section this button is used for the further menu options. WALLCON X-treme 115-125-150...
Page 32
Then this function will be turned off automatically. INFO BUTTON (F) Used for the display boiler information such as temperatures, operating modes, error codes etc. RESET BUTTON (J) Used for to reset any fault and error which caused to stop the boiler. WALLCON X-treme 115-125-150...
OK button to set the temperature. REDUCED TEMPERATURE : It is a defined lower temperature limit so that the room temperature does not fall below a certain degree. Adjusting this value too high can cause unnecessary operation of the boiler. WALLCON X-treme 115-125-150...
Turn the adjusment knob one click and set mounth and day with pushing OK button. Push OK button to adjust the year as a final step. Push ESC button to return the home secreen. WALLCON X-treme 115-125-150...
Boiler manually blocked, no release RESET Press button again > 3 sec. Boiler released, Alarm symbol disappears PARAMETERS Parameters of Wallcon X-treme boilers are divided into 4 groups according to their level: END USER PARAMETERS COMMISSIONING ENGINEER WALLCON X-treme 115-125-150...
Bakınız : 1610 Swimming pool 2055 Pool setpoint solar heating °C 2056 Pool sepoint boiler heating °C Boiler 2214 Setpoint manual control °C Fault 6705 SW Diagnose Code Indication only 6706 Burner ctrl phase lockout pos Indication only WALLCON X-treme 115-125-150...
BX / extension module same sensors Sensor primary heat exchanger Loss of flame during operation BX / mixing group same sensors Functional earth not connected Fan error or LP error Extension module same function Temperature primary heat exchanger to high WALLCON X-treme 115-125-150...
The communication between the MASTER boiler and the other boilers is carried out with the cascade module which is standard in all boilers. For detailed information about the installation of the cascade system please contact nearest authorized service center or GASSERO. SLAVE WALLCON X-treme 115-125-150...
Wallcon X-treme boilers are offer to sale after all required combusiton, efficiecny and safety controls. Emission settings mustn’t be changed which are made by GASSERO. However, if there is a deviation in the values which are given below, emission settings should be changed by GASSERO authorized service.
CO2 value will decrease. LPG CONVERSION Gas conversioned process which is mentioned below must be issued by authorized GASSERO services only on Wallcon X-treme 125 and Wallcon X-treme 150 boilers. Wallcon X-treme boilers are manufactured to work with natural gas.
Page 42
LPG. Before the commissioning of the boiler, all parameters must be regenerated according to the LPG. This process must 1) Remove 8 screws and seperate the made authorized Gassero gas valve from the flange. services. WALLCON X-treme 115-125-150...
1) Seperate the gas valve and gas 3) Remove the group of fan, venturi supply pipe. and gas valve 4) Remove the 3 screws on the gas valve 2) Seperate the air inlet pipe and the venturi WALLCON X-treme 115-125-150...
Page 44
Replace the disassembled companents after the nozzles installed with the care of tightness. Use the flue gas analyzer to provide the values which are given in the table of values for LPG. WALLCON X-treme 115-125-150...
This information should be added to the information provided by the consumer and the service history of the boiler should be established. Authorized Gassero service responsible should inform the consumer about the defects in the installation or location and advise on the solution of these defects.
Ignition and ionization electrodes of the boiler will be removed and cleaned if necessary, replaced. Distances between the electrodes and the burner are very important in terms of ignition and flame detection. WALLCON X-treme 115-125-150...
Page 47
Time / holiday settings which are made according to the requests of the consumer will be checked. Emission values ( CO2 and O2) will be written to the service document by operating the boiler at nominal, minimum and partial load. WALLCON X-treme 115-125-150...
WATER QUALITY: Water treatment will keep the water conditions under constant control and saves energy. REGULAR MAINTENANCE: Maintenance of the boiler once a year and reviewing the system periodically is also important for energy saving. WALLCON X-treme 115-125-150...
Such wastes must be treated in accordance with the applicable regulations. Ignoring this warining may harm, people, animals and may cause property damage. Manufacturer is not liable for damages that may arise in such cases. WALLCON X-treme 115-125-150...
Page 53
MANUFACTURER : Gassero Isı Teknolojileri Sanayi Limited Şirketi İstanbul Endüstri ve Ticaret Serbest Bölgesi 4.Sokak,No:8, 34957 Tuzla / Istanbul / TÜRKİYE Telefon : +90 216 394 09 85 -86 -87 Faks : +90 216 394 24 91 www.gassero.com...