  • Page 1 EMC8432 Ethernet to RS232 converter module User's Manual (V1.4) 健昇科技股份有限公司 JS AUTOMATION CORP. 新北市汐止區中興路 100 號 6 樓 6F., No.100, Zhongxing Rd., Xizhi Dist., New Taipei City, Taiwan TEL:+886-2-2647-6936 FAX:+886-2-2647-6940 http://www.automation.com.tw E-mail:control.cards@automation.com.tw...
  • Page 2 Correction record Version Record firmware version 1.0 up Add System Reset 1. Modify dimension (chapt. 3) 2. Add dimension drawing (chapt. 4.2) 1. Modify Notes on hardware installation 2. Add Warranty 3. Add specifications to each input and output (chapt. 6) 4.
  • Page 3: Table Of Contents

    1. Forward ............................5 2. Features ............................. 6 3. Specifications ............................ 7 4. Layout and dimensions ........................8 4.1 EMC8432 board dimension ....................... 8 4.2 EMC8432 Dimension ........................ 8 5. Pin definitions ........................... 9 5.1 Overview of connectors and indicator ..................9 5.2 JM1 RS232 ..........................
  • Page 4 Notes on hardware installation For more detail of step by step installation guide, please refer the file “..\download\Supplemental_technical_data\Step_by_step_installation_of_EMC_module.pdf “ on the CD come with the product or download the document from http://www.automation.com.tw/common/Supplemental_technical_data.htm...
  • Page 5: Warranty

    The EMC8432 is warranted against defects in materials and workmanship for a period of two years from the date of shipment, as evidenced by receipts or serial no. on board. JS automation Corp. will, at its option, repair or replace product that proves to be defective during the warranty period. This warranty includes parts, labor and shipping costs of returning.
  • Page 6: Forward

    To utilize the Ethernet as data communication highway of industrial control devices is more attractive than ever. EMC8432 module is a Ethernet to serial converter and I/O control module. It is an RS232 to Ethernet device, which provide an easy to up grade your existing RS232 devices to Ethernet.
  • Page 7: Features

    2. Features - Over-voltage protection on digital input - Various IO combinations : 8 bit configurable I/O’s, any bit can be input or output - High drive capacity on digital output - Digital I/P as counter input - Baudrate up to 921.6K - Wide power range - Standalone mode:step sequence control - IP re-assignment...
  • Page 8: Specifications

    3. Specifications RS232 - Baud rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 921600 - Data bits: 5, 6, 7, 8 - Stop bits: 1, 1.5, - Parity: None, Even, Odd Digital input - Input points: max 8 (Configurable) - Logic high level: 3.15V(min) - Logic low level: 1.35V(max) - Over-voltage protection: 60Vdc(max)
  • Page 9: Layout And Dimensions

    4. Layout and dimensions 4.1 EMC8432 board dimension *dimension in bare board 4.2 EMC8432 Dimension...
  • Page 10: Pin Definitions

    5. Pin definitions 5.1 Overview of connectors and indicator (box inside) LED1: system active LED J2,J3: Ethernet RJ45 socket JM1: RS232 connector JM2: I/O connector JM4: external power 24V connector SW2: system reset switch...
  • Page 11: Jm1 Rs232

    5.2 JM1 RS232 Descriptions Descriptions 5.3 JM2 pin definitions +Ve* Plug Socket IO_0 IO_1 IO_2 IO_3 IO_4 IO_5 IO_6 IO_7 5.4 JM4 pin definitions Plug Socket PIN NO. * +Ve can floating or voltage input (voltage range +3.3V ~ +24V) * +Ve can apply different voltage as you need.
  • Page 12: I/O Interface Diagram

    6. I/O Interface diagram 6.1 I/O diagram For IO_0 ~ IO_7 I/P specification: +Ve (External voltage) +Ve (max) +Ve (min) (input voltage) ** (min) 3.15V ** (max) 1.35V (input current) (max) 50mA For IO_0 ~ IO_7 O/P specification: +Ve (External voltage) +Ve (max) +Ve (min) (output voltage)
  • Page 13: System Reset

    7. System Reset The system reset switch SW2 has provide normal system reset and reset to default functions. 7.1 Normal system reset Push the SW2 for more than 5 seconds, the power LED will flick at 3 HZ to signal the system has already reset.
  • Page 14: Applications

    8. Applications  RS232 to ethernet converter  Ethernet to RS232 converter  Remote signal input  Remote signal output  Standalone step sequence controller  Multi-channel low speed counter (100Hz)
  • Page 15: Ordering Information

    9. Ordering information PRODUCT DESCRIPTIONS EMC8432 Ethernet module to RS232 (8 IO) Module (include M23406) M23406 9 pin D type male cable 10cm JD52038 110/220Vac to 24Vdc @1.5A power supply JS52026 110/220Vac to 24Vdc @0.75A power adapter...