Carrier 48TJF008 Installation And Service Instructions Manual
Carrier 48TJF008 Installation And Service Instructions Manual

Carrier 48TJF008 Installation And Service Instructions Manual

Single-package rooftop heating/cooling units 50 hz
Table of Contents

Advertisement

CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33

Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
• ROOF CURB
• SLAB MOUNT
Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 2
Step 3 — Install External Trap for
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
• POSITIONING
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . 8
Step 7 — Make Electrical Connection . . . . . . . . . . . . 8
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS
Step 8 — Adjust Factory-Installed Options . . . . . . 11
• APOLLO CONTROL
• MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL DURABLADE ECONOMIZER
• OPTIONAL ECONOMI$ER
Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . . 20
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-41
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . 42-46
Start-Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 004-816
Book 1
4
Tab
1a 6a
Single-Package Rooftop Heating/Cooling Units
Installation, Start-Up and
Service Instructions
Page
Printed in U.S.A.
Disconnect gas piping from unit when leak test-
ing at pressure greater than 3.4 kPa (
Pressures greater than 3.4 kPa (
cause gas valve damage resulting in hazardous
condition. If gas valve is ever subjected to pres-
sure greater than 3.4 kPa (
replaced before use. When pressure testing
field-supplied gas piping at pressures of 3.4 kPa
(
1
/
psig) or less, a unit connected to such piping
2
must be isolated by manually closing the gas
valve(s).
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
INSTALLATION
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insula-
tion side down. Seals around duct openings must be tight. See
Fig. 1.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb. If gas, electric
power or control power is to be routed through the curb, attach
the accessory thru-the-curb service connection plates to the
roof curb in accordance with the accessory installation instruc-
tions. Connection plates must be installed before unit is set in
roof curb.
IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 3. This is necessary for unit drain to function properly. Re-
fer to Accessory Roof Curb Installation Instructions for addi-
tional information as required.
Form 48TF-C1SI
Pg 1
48TFD008-014
48TFE008-014
48TFF008,012
50 Hz
1
/
psig).
2
1
/
psig) will
2
1
/
psig), it must be
2
1-01
Replaces: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 48TJF008 and is the answer not in the manual?

Questions and answers

Summarization of Contents

Installation
Provide Unit Support
Details on unit support, including roof curb and slab mount.
Field Fabricate Ductwork
Instructions for fabricating and securing ductwork.
Install External Trap for Condensate Drain
Guidance on installing the condensate drain trap.
Rig and Place Unit
Steps for rigging and placing the unit.
Positioning
Guidelines for unit positioning and clearances.
Install Flue Hood
Instructions for installing the flue hood.
Install Gas Piping
Guidance on installing gas piping.
Make Electrical Connections
Covers field power supply and control wiring.
Adjust Factory-Installed Options
Details on adjusting Apollo Control and Manual Outdoor-Air Damper.
Apollo Control
Information on the optional Apollo Control system.
Manual Outdoor-Air Damper
Steps for assembling and adjusting the manual outdoor-air damper.
Optional Durablade Economizer
Instructions for assembling and installing the Durablade Economizer.
Optional Economiser
Instructions for installing the optional EconoMi$er.
CO2 Control Set Up
Steps for setting up the CO2 sensor.
Mechanical Cooling Lockout
Setting temperature for disabling mechanical cooling.
Dry Bulb Changeover Set Up
Setting dry bulb changeover point for the economizer.
Adjust Evaporator-Fan Speed
Guide to adjusting evaporator fan speed settings.
Start-Up
Unit Preparation
Checks for proper unit installation and adherence to codes.
Return-Air Filters
Ensuring correct filters are installed.
Outdoor-Air Inlet Screens
Verifying outdoor-air inlet screens are in place.
Compressor Mounting
Instructions regarding compressor mounting and tiedown bands.
Internal Wiring
Checking electrical connections within the unit.
Refrigerant Service Ports
Location and identification of refrigerant service ports.
High Flow Valves
Identifying and understanding High Flow Valves.
Compressor Rotation
Procedure to check and correct compressor rotation direction.
Cooling
Steps to start the unit for cooling operation.
TO SHUT OFF UNIT
Procedure for safely shutting down the unit.
Main Burners
Checks related to main burners and heating controls.
ADJUST GAS INPUT
Procedure for adjusting gas input and manifold pressure.
Heating
Steps for initiating the heating sequence.
Safety Relief
Information about safety relief mechanisms.
Ventilation (Continuous Fan)
Setting fan for continuous operation.
Operating Sequence
Describes how the unit operates in cooling and heating modes.
Cooling, Units Without Economizer
Cooling operation sequence without an economizer.
Heating, Units Without Economizer
Heating operation sequence without an economizer.
Cooling, Units With Durablade Economizer
Cooling sequence with the Durablade Economizer.
Cooling Units With EconoMi$er
Cooling operation with the EconoMi$er.
Service
Cleaning
General cleaning instructions for the unit.
Evaporator Coil
Steps for cleaning the evaporator coil.
Condenser Coil
Procedures for cleaning the condenser coil.
Condensate Drain
Maintenance for the condensate drain.
Filters
Filter cleaning or replacement.
Belts
Adjusting belt tension and pulley alignment.
Lubrication
Lubrication requirements for components.
Condenser-Fan Adjustment
Steps for adjusting the condenser fan.
Refrigerant Charge
Procedures for charging the refrigerant.
Low Charge Cooling
Using cooling charging charts for low charge units.
To Use Cooling Charging Charts
Guide to using cooling charts for proper refrigerant levels.
Flue Gas Passageways
Combustion-Air Blower
Cleaning and inspection of the combustion air blower.
Burner Ignition
Information on unit's burner ignition system and IGC.
Main Burners
Removal and Replacement of Gas Train
Steps for removing and replacing gas train components.
Cleaning and Adjustment
Cleaning and adjusting burners.
Troubleshooting
LED Error Code Service Analysis
Analysis of LED error codes for unit diagnostics.
Cooling Service Troubleshooting
Troubleshooting common cooling system problems.
Heating Service Troubleshooting
Troubleshooting common heating system problems.
EconoMi$er Troubleshooting
Troubleshooting common economizer issues.
Durablade Economizer Troubleshooting
Troubleshooting specific Durablade economizer problems.
Start-Up Checklist
Preliminary Information
Basic information about the unit model and job.
Pre-Start-Up
Pre-start-up checks to ensure unit readiness.
Start-Up
Electrical, temperature, and pressure checks during start-up.

Table of Contents

Save PDF