ProtEX-MAX PD8-6000 Explosion-Proof Process Meter
Instruction Manual
Fully Approved Explosion-Proof Meter
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Field Selectable Inputs with ±0.03% Accuracy
Dual-Line 6-Digit Display, 0.60" (15.2 mm) & 0.46" (12.0 mm)
CapTouch Through-Glass Button Programming
Display Mountable at 0°, 90°, 180°, & 270°
Isolated 24 VDC @ 25 mA Transmitter Power Supply
Easy Field Scaling in Engineering Units without Applying an Input
4 Relays with Interlocking Capability + Isolated 4-20 mA Output Option
Free PC-Based, On-Board, MeterView Pro USB Programming Software
SunBright Display Standard Feature; Great for Outdoor Applications
Operating Temperature Range: -55 to 65°C (-67 to 149°F)
CSA Certified as Explosion-Proof / Dust-Ignition-Proof / Flame-Proof
ATEX and IECEx Certified as Flame-Proof
Input Power Options: 85-265 VAC / 90-265 VDC or 12-24 VDC / 12-24 VAC
Display Input in Two Different Scales Simultaneously - Great for Level Applications
Multi-Pump Alternation Control
Round Horizontal Tank Function; Just Enter Diameter & Length
32-Point Linearization, Square Root Extraction and Programmable Exponent Function
Password Protection
Programmable Display, Function Keys & Digital Inputs
Flanges for Wall or Pipe Mounting
Explosion-Proof Aluminum or Stainless Steel NEMA 4X / IP68 Enclosures
On-Board RS-485 Serial Communications
®
Modbus
RTU Communication Protocol Standard
Four 3/4" NPT Threaded Conduit Openings
Stainless Steel Pipe Mounting Kit
Stainless Steel Tag Available
3-Year Warranty
PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA
Tel (800) 343-1001 • (508) 655-7300
www.predig.com
MeterView Pro
USB Install

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProtEX-MAX PD8-6000-6H0-SS and is the answer not in the manual?

Questions and answers

Summary of Contents for Precision Digital Corporation ProtEX-MAX PD8-6000-6H0-SS

  • Page 1 RTU Communication Protocol Standard • Four 3/4" NPT Threaded Conduit Openings • Stainless Steel Pipe Mounting Kit • Stainless Steel Tag Available • 3-Year Warranty PRECISION DIGITAL CORPORATION 233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • (508) 655-7300 www.predig.com...
  • Page 3 Cancer and Reproductive Harm - www.P65Warnings.ca.gov they like without even looking in the manual. Limited Warranty Precision Digital Corporation warrants this product Watch MeterView Pro Software Video at against defects in material or workmanship for the www.predig.com/meterviewpro specified period under “Specifications” from the date of shipment from the factory.
  • Page 4: Table Of Contents

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Table of Contents Introduction ......................7 Ordering Information ..................7 Key Features ....................... 9 Specifications ....................17 General......................17 Process Inputs ....................18 Relays ......................18 USB Connection .................... 18 Isolated 4-20 mA Transmitter Output Option ..........19 RS-485 Serial Communications ..............
  • Page 5 ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Relay and Alarm Operation Diagrams ............42 High Alarm Operation (Set > Reset) ............. 42 Low Alarm Operation (Set < Reset) ............43 High Alarm with Fail-Safe Operation (Set > Reset) ........43 Low Alarm with Fail-Safe Operation (Set <...
  • Page 6 ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Table of Figures Figure 1. Enclosure Dimensions – Front View ..........23 Figure 2. Enclosure Dimensions – Side Cross Section View ....... 23 Figure 3. Transmitter Supply Voltage Selection ..........26 Figure 4. Integrated P Required Connections ........
  • Page 7: Introduction

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Introduction Ordering Information The ProtEX-MAX PD8-6000 is an explosion-proof, Aluminum Enclosure multi-purpose, easy to use, digital process meter ideal 85-265 VAC Models for level, flow, temperature, pressure, or any other process application. The meter features a dual-line Options Model Standard Features...
  • Page 8 ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Helpful Videos Connect to PC for Programming Learn how to connect a ProVu (ProtEX-MAX) process There are several videos that will help you get a meter to your PC and install free MeterView Pro better understating of the features and functionality of programming software.
  • Page 9: Key Features

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Key Features • Form C (SPDT) relays • Two isolated supplies available even on 12/24 VDC input power models • Removable terminal blocks • 4 relays + isolated 4-20 mA output option • Universal 85-265 VAC or 12/24 VDC input power •...
  • Page 10: Programming Assistance

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Easy Programming Methods Advanced Display Features The ProtEX-MAX can be programmed in a hazardous Dual-Line Makes All the Difference area with the through-glass CapTouch buttons without The main display can be programmed to indicate PV, removing the cover, in a safe area with the front panel maximum (peak), minimum (valley), alternating push buttons with the cover removed, or in a safe...
  • Page 11 ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Dual-Scale Display Feature The ProtEX-MAX PD8-6000 has a rather unique, and very flexible dual-scale capability. This is of particular value in level applications where a second scaled display can represent the measured input in a different form (i.e. gallons & height).
  • Page 12: Physical Features

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Physical Features Wide Viewing Angle Customers can’t always look at the display from The ProtEX-MAX is designed for ease-of-use in safe straight on, so the window and display module have and hazardous area applications, and is housed in a been optimized to provide a wide viewing angle of rugged NEMA 4X explosion-proof enclosure, approximately ±...
  • Page 13: Hazardous Area Approvals

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Rotatable Display Removable Screw Terminals The ProtEX-MAX rotatable display, along with four Industrial applications require screw terminal available conduit connections, provide for numerous connections for easy field wiring and the ProtEX-MAX installation options. The display can be rotated in 90° goes one step further in convenience by making them increments.
  • Page 14 ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Transmitter Power Supplies Input Signal Conditioning Non-linear input signals (i.e. weirs & flumes, Meter Powers Transmitter differential pressure, round horizontal tanks, etc.) can be linearized with the ProtEX-MAX’s simple to One of the most useful standard features of the use built-in signal input conditioning functions.
  • Page 15 ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Exp-Proof Dual-Pump Alternation The ProtEX-MAX can be used as an explosion-proof pump controller when combined with a continuous level transmitter. The most common pump control application is shown below: controlling and alternating two pumps and providing high and low-level alarms. In addition, the ProtEX-MAX provides the 24 V to power the transmitter.
  • Page 16: Useful Tools

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Useful Tools PD9501 Multi-Function Calibrator This PD9501 Multi-Function Calibrator has a variety of signal measurement and output functions, including voltage, current, thermocouple, and RTD. PD9502 Low-Cost Signal Generator PD9502 is a low-cost, compact, simple to use 4-20 mA or 0-10 VDC signal generator.
  • Page 17: Specifications

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Specifications Power 85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max; Options 12-24 VDC, 12-24 VAC, 15 W max. Powered over USB for configuration only. Except where noted all specifications apply to operation at +25°C. Fuse Required external fuse: UL Recognized, 5 A max, slow blow;...
  • Page 18: Process Inputs

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Process Inputs Relays Inputs Field selectable: 0-20 mA, 4-20 mA Rating Rating: 4 SPDT (Form C) internal and rated ±10 V (0-5 V, 1-5 V, 0-10 V) 3 A @ 30 VDC and 125/250 VAC resistive Modbus PV (Slave) load, Total current: 4 A max (total of all relays), 1/14 HP (≈...
  • Page 19: Isolated 4-20 Ma Transmitter Output Option

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Isolated 4-20 mA Transmitter Digital Input (F4) Output Option Function Remote operation of front-panel buttons, acknowledge/reset relays, reset max/min Output Process variable (PV), max, min, set points values. See Function Keys & Digital I/O Source 1-4, Modbus input, or manual control mode Available Settings on page 55 for a...
  • Page 20: Enclosure

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual General Compliance Enclosure Information Material AL Models: ASTM A413 LM6 die-cast aluminum, copper-free, enamel coated SS Models: Electromagnetic Compatibility ASTM A743 CF8M investment-cast 316 stainless steel Emissions EN 55022 Class A ITE emissions requirements Gasket Fluoroelastomer Radiated...
  • Page 21: Product Ratings And Approvals

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Product Ratings and Approvals Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1, T5 Class III, Division 1, T6 (Ta max = 60°C) Ex db IIC T5 Ex db IIC T6 (Ta max = 60°C) Ex tb IIIC T90°C...
  • Page 22: Eu Declaration Of Conformity

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual EU Declaration of Unpacking Conformity Remove the meter from box. Inspect the packaging and contents for damage. Report For shipments to the EU and UK, a Declaration of damages, if any, to the carrier. Conformity was printed and included with the product.
  • Page 23: Mounting

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Wall Mounting Instructions Mounting The meter can be mounted to any wall or flat surface The ProtEX-MAX has two slotted mounting flanges using the four provided mounting holes located in the that may be used for pipe mounting or wall mounting. built-in flanges.
  • Page 24: Pipe Mounting Instructions

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Pipe Mounting Instructions Vertical Pipe Mounting Horizontal Pipe Mounting The meter can also be mounted to a pipe using an optional U-Bolt kit. This kit includes two U-bolts, the necessary hardware, and is available in 316 stainless steel (PDA6848-SS) To mount the meter using a U-Bolt kit, follow these instructions:...
  • Page 25: Installation Overview

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Once the driver is installed, an AutoPlay Installation Overview dialog should appear for the drive We recommend the following sequence for getting the “MAINSTAL.” Click “Open folder to view meter into service: files.” DO NOT apply AC or DC power to the meter.
  • Page 26: Transmitter Supply Voltage Selection (P+, P-)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual To access the connectors, remove the enclosure Transmitter Supply Voltage cover. The electronics module is snapped into the Selection (P+, P-) back of the enclosure and is removed by pulling it straight out. Signal connections are made to de- All meters, including models equipped with the 12-24 pluggable connectors on the back of the electronics VDC power option, are shipped from the factory...
  • Page 27: Pro Vu U Electronics Module Layout

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Electronics Module Layout for PD8-6000-6H7 and PD8-6000-7H7* * For models PD8-6000-6H0 and PD8-6000-7H0 the upper set of connectors (RELAYs & MA OUT) are not present Figure 5. P Electronics Module Layout USB Connection Figure 6.
  • Page 28: Power Connections

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual The current input is protected against current Power Connections overload by an internal resettable fuse. The display Power connections are made to a two-terminal may or may not show a fault condition depending on connector labeled POWER.
  • Page 29: Switching Inductive Loads

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Switching Inductive Loads RS-485 Connections The use of snubbers to suppress electrical noise is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The snubbers also prolong the life of the relay contacts.
  • Page 30: Digital I/O Connections

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Digital I/O Connections 4-20 mA Output Connections Connections for the 4-20 mA transmitter output are made to the connector terminals labeled mA OUT. The 4-20 mA output may be powered internally or from an external power supply. The ProtEX-MAX has a 10-position terminal block for connecting digital inputs and outputs.
  • Page 31: Remote Programming

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Remote Programming The meter can be operated via the programming buttons or a remote control station with required approvals to be located in a hazardous area using the digital inputs. Interlock Relay Feature As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s).
  • Page 32: Setup And Programming

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Setup and Programming There is no need to recalibrate the meter when first received from the factory. The meter is factory calibrated prior to shipment for milliamps and volts with calibration equipment that is certified to NIST standards. Overview There are no jumpers to set for the meter input selection.
  • Page 33: Programming Buttons

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Programming Buttons Button Symbol Description Press to enter or exit Programming Mode, view settings, or exit max/min readings Press to reset max/min readings or other parameter/function assigned through the User menu Press to display max/min readings or other parameter/function assigned through the User menu Press to acknowledge relays or other parameters/function assigned through the User menu...
  • Page 34: Display Functions & Messages

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Display Functions & Messages Display Functions & Messages Display Parameter Action/Setting The meter displays various functions and messages Description during setup, programming, and operation. The following table shows the main menu functions and Act 1 Action 1 Set relay 1 action...
  • Page 35: Main Menu

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Main Menu Display Functions & Messages Display Parameter Action/Setting The main menu consists of the most commonly used Description functions: Setup, Reset, Control, and Password. Out 1 Output 1 Program output 1 value •...
  • Page 36: Setting Numeric Values

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Setting the Input Signal (Input) Setting Numeric Values Enter the Input menu to set up the meter to display The numeric values are set using the Right and Up current (nmA) or voltage (Volt) inputs. arrow buttons.
  • Page 37: Setting The Display Units Or Custom Tags (Units)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Setting the Decimal Point (dEc pt) Setting the Display Units or Custom Tags (units) The decimal point may be set with up to five decimal places or with no decimal point at all. Enter the display unit or custom tag that will be displayed if d unit is selected as the line 2 The decimal point selection should be made prior to...
  • Page 38: Programming The Meter (Prog)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Programming the Meter (prog) Scaling the Meter (SCALE) The meter may either be scaled (SCALE) without The process input (4-20 mA, 10 VDC) can be scaled applying an input or calibrated (Cal) by applying an to display the process variable in engineering units.
  • Page 39: Error Message (Error)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Error Message (Error) Calibrating the Meter with External Source (Cal) An error message indicates that the calibration or scaling process was not successful. Note: To scale the meter without a signal source After the error message is displayed, the meter refer to Scaling the Meter (SCALE) on page 38.
  • Page 40: Setting The Display Parameter & Intensity (Dsplay)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Setting the Display Parameter & Display Parameter Menu Intensity (dsplay) The main display (Line 1) can be programmed to display: Process value 1 (PV1) Process value 2 (PV2)* Percent of PV1 (PCT)* Relay set points Max &...
  • Page 41: Setting The Relay Operation (Relay)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Setting the Relay Action Setting the Relay Operation Operation of the relays is programmed in the Action (relay) menu. The relays may be set up for any of the following modes of operation: This menu is used to set up the operation of the relays.
  • Page 42: Programming Set And Reset Points

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual The following graph shows the loop break relay Programming Set and Reset operation for a high alarm relay. Points High alarm indication: program set point above reset point. Low alarm indication: program set point below reset point.
  • Page 43: Low Alarm Operation (Set < Reset)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Low Alarm Operation (Set < Reset) Low Alarm with Fail-Safe Operation (Set < Reset) Note: For Manual reset mode, ACK can be pressed anytime to turn "off" relay. For relay to turn back “on”, signal must go above set point and then go below it.
  • Page 44: Pump Alternation Control Operation

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Pump Alternation Control Operation Relay Sampling Operation When the signal crosses the set point, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high alarms and going down for low alarms.
  • Page 45: Relay Operation Details

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Front Panel LEDs Relay Operation Details The alarm status LEDs on the front panel are Overview available on all meters, even those without relays installed, and provide status indication for the The four-relays option for the meter expands its following: usefulness beyond simple indication to provide users with alarm and control functions.
  • Page 46: Non-Latching Relay (Auto)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Non-Latching Relay (Auto) Latching Relay with Clear (Lt-Clr) In this application, the meter is set up for automatic In this application, the meter is set up for manual reset (non-latching relay). Acknowledging the alarm reset only after the signal passes the reset point while it is still present has no effect on either the LED (alarm condition has cleared).
  • Page 47: Acknowledging Relays

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Acknowledging Relays Application #1: Pump Alternation Using Relays 1 & 2 There are three ways to acknowledge relays programmed for manual reset: Relays 1 and 2 are set up for pump alternation. Via the programmable front panel function keys Relays 3 and 4 are set up for low and high alarm F1-F3 (Example: F3 assigned to ACK).
  • Page 48: Setting Up The Interlock Relay (Force On) Feature

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Pump Alternation Visual Setting Up the Interlock Relay (Force Representation On) Feature Relays 1-4 can be set up as interlock relays. To set The following graphics provide a visual representation up the relays for the interlock feature: of a typical pump alternation application with high and 1.
  • Page 49: Scaling The 4-20 Ma Analog Output (Aout)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Scaling the 4-20 mA Analog Reset Menu (reset) Output (Aout) The Reset menu is used to reset the maximum or minimum reading (peak or valley) reached by the The 4-20 mA analog output can be scaled to provide process;...
  • Page 50: Setting Up The Password (Pass)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Disabling Password Protection Setting Up the Password (pass) To disable the password protection, access the The Password menu is used for programming three Password menu and enter the correct password levels of security to prevent unauthorized changes to twice, as shown below.
  • Page 51: Advanced Features Menu

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Advanced Features Menu Advanced Features Menu & Display Messages Display Parameter Action/Setting To simplify the setup process, functions not needed for most applications are located in the Advanced No PtS Number of Set PV1 for 2 to 32-point Features menu.
  • Page 52: Noise Filter (Filter)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Rounding Feature (round) Advanced Features Menu & Display Messages The rounding feature is used to give the user a Display Parameter Action/Setting steadier display with fluctuating signals. Rounding is ICal Internal source Enter internal source used in addition to the filter function.
  • Page 53: Select Menu (Select)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Select Menu (SElect) Multi-Point Linearization (Linear) The Select menu is used to select the input signal Meters are set up at the factory for linear function with conditioner applied to the input (linear, square root, 2-point linearization.
  • Page 54: Round Horizontal Tank Linearization (Rht)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Round Horizontal Tank Changing the Volume from Gallons to Liters Linearization (rHt) In the above graphic, entering 48" for the diameter This function automatically calculates the volume in a and 120" for the length of the round horizontal tank, round horizontal tank with flat ends.
  • Page 55: Programmable Function Keys User Menu (User)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Analog Output Source Programmable Function Keys User Menu (user) The source for generating the 4-20 mA output may be assigned to the process variable, maximum or The User menu allows the user to assign the front minimum value reached by the process, one of the programming buttons function keys F1, F2, and F3, set points, or the Modbus PV input.
  • Page 56: Tare (Tare)

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Internal Source Calibration (ICAL) Function Keys & Digital I/O Available Settings Display Description The meter is factory calibrated prior to shipment Ln1 HL Display maximum & minimum display for milliamps and volts with calibration equipment values on line 1 that is certified to NIST standards.
  • Page 57: Meter Operation

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Meter Operation The following graphic shows the calibration of the current input. The voltage input is calibrated in a similar way. When installed, the primary way to operate the meter is with the CapTouch through-glass buttons that allow the user to perform various operations without removing the cover and exposing the electronics to the hazardous environment.
  • Page 58: Captouch Buttons

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual CapTouch Buttons Function Keys Operation The ProtEX-MAX is equipped with four capacitive During operation, the programmable function keys sensors that operate as through-glass buttons so that it operate according to the way they have been programmed in the Advanced Features –...
  • Page 59: Troubleshooting

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Troubleshooting Reset Meter to Factory Defaults The rugged design and the user-friendly interface of When the parameters have been changed in a way that is difficult to determine what’s happening, it might the meter should make it unusual for the installer or operator to refer to this section of the manual.
  • Page 60: Factory Defaults & User Settings

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Factory Defaults & User Settings Parameter Display Default Setting On 3 The following table shows the factory setting for most On delay relay 3 0.0 sec of the programmable parameters on the meter. Off 3 Off delay relay 3 0.0 sec...
  • Page 61: Troubleshooting Tips

    ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Troubleshooting Tips This meter is a highly sophisticated instrument with an extensive list of features and capabilities. If the programming buttons are used to program the meter, it may be a difficult task to keep everything straight. That is why we strongly recommend the use of the free MeterView Pro software for all programming activities.
  • Page 62 ProtEX-MAX PD8-6000 Explosion-Proof Process Meter Instruction Manual Troubleshooting Tips Symptom Check/Action CapTouch buttons do not respond Check if slide switch on connector board is in DISABLE position, switch to ENABLE. Be sure to hold the initial CapTouch button for 5 seconds to wake it up.
  • Page 64 Email: sales@predig.com Place Orders Email: orders@predig.com For the latest version of this manual please visit www.predig.com PRECISION DIGITAL CORPORATION 233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • (508) 655-7300 www.predig.com LIM8-6000_J SFT039 Ver 4.010 & up...