2. Specification Wind-Free 4Way Cassette Indoor Unit Model Name AC018DN4DCG/AA AC024DN4DCG/AA AC030DN4DCG/AA Outdooru Unit AC018DXADCG/AA AC024DXADCG/AA AC030DXADCG/AA Indoor Unit US Code CNG184DD CNG244DD CNG304DD Outdooru Unit CXG18ADD CXG24ADD CXG30ADD Mode System Heat Pump Heat Pump Heat Pump Performance Capacity Cooling 1.4 / 5.2 / 6.4 2.0 / 7.0 / 8.7 2.9 / 8.7 / 10.8...
Page 10
2. Specification Wind-Free 4Way Cassette Indoor Unit Model Name AC018DN4DCG/AA AC024DN4DCG/AA AC030DN4DCG/AA Outdooru Unit AC018DXADCG/AA AC024DXADCG/AA AC030DXADCG/AA Indoor Unit US Code CNG184DD CNG244DD CNG304DD Outdooru Unit CXG18ADD CXG24ADD CXG30ADD PC4NUFMUNW PC4NUFMUNW PC4NUFMUNW Indoor Panel (1) Model Name Wind-Free Type Wind-Free Type Wind-Free Type Type Unit...
Page 11
2. Specification Wind-Free 4Way Cassette Indoor Unit Model Name AC036DN4DCG/AA AC048DN4DCG/AA Outdooru Unit AC036DXADCG/AA AC048DXADCG/AA Indoor Unit US Code CNG364DD CNG484DD Outdooru Unit CXG36ADD CXG48ADD Mode System Heat Pump Heat Pump Performance Capacity Cooling 3.2 / 10.5 / 12.6 3.9 / 14.0 / 15.8 (Min/Std/Max) Btu/h 11,000 / 36,000 / 43,000...
Page 12
2. Specification Wind-Free 4Way Cassette Indoor Unit Model Name AC036DN4DCG/AA AC048DN4DCG/AA Outdooru Unit AC036DXADCG/AA AC048DXADCG/AA Indoor Unit US Code CNG364DD CNG484DD Outdooru Unit CXG36ADD CXG48ADD PC4NUFMUNW PC4NUFMUNW Indoor Panel (1) Model Name Wind-Free Type Wind-Free Type Type Unit Material HIPS HIPS DA White DA White...
5. Dimensional Drawing Wind-Free 4Way Cassette CNG184DD (AC018DN4DCG/AA), CNG244DD (AC024DN4DCG/AA) Units : mm [inches] Description Name Liquid pipe connection Φ6.35(1/4) Gas pipe connection Φ15.88(5/8) Drain pipe connection OD26.67 Power supply & Communication wiring conduit Fresh air intake Φ10[4] , Use M4 Screw NOTE •...
Page 20
5. Dimensional Drawing Wind-Free 4Way Cassette CNG304DD (AC030DN4DCG/AA), CNG364DD (AC036DN4DCG/AA), CNG484DD (AC048DN4DCG/AA) Units : mm [inches] Description Name Liquid pipe connection Φ9.52(3/8) Gas pipe connection Φ15.88(5/8) Drain pipe connection OD26.67 Power supply & Communication wiring conduit Air Outlet Louver Air Inlet Grille Sub - duct * The sub duct is not applicabel to the Wind-free panel Fresh air intake...
7. Electrical Wiring Diagram Wind-Free 4Way Cassette SUB PBA for wired remote control SUB PBA ROOM(10K) Thermistor - Indoor Room Electronic Expansion Valve communication Contact output port for COMP CHECK EVA IN(10K) Thermistor - IDU heat exchanger In F100 Fuse compressor operation check M-BLDC Motor for Indoor Fan...
8. Sound Data Wind-Free 4Way Cassette Sound Power level Unit: dB(A) NOTE Model Cooling • Specifications may be subject to change without prior notice CNG184DD (AC018DN4DCG/AA) - Sound power level is an absolute value that a sound source generates. CNG244DD (AC024DN4DCG/AA) - dBA = A-weighted sound power level.
Page 26
9. Temperature and air flow distribution Wind-Free 4Way Cassette CNG184DD (AC018DN4DCG/AA) + CXG18ADD (AC018DXADCG/AA) • Cooling Air Velocity distribution • Cooling temperature distribution (Discharge angle : 45 degree) (Discharge angle : 45 degree) • Heating Air Velocity distribution • Heating temperature distribution (Discharge angle : 52 degree) (Discharge angle : 52 degree) CNG244DD (AC024DN4DCG/AA) + CXG24ADD (AC024DXADCG/AA)
Page 27
9. Temperature and air flow distribution Wind-Free 4Way Cassette CNG304DD (AC030DN4DCG/AA) + CXG30ADD (AC030DXADCG/AA) • Cooling Air Velocity distribution • Cooling temperature distribution (Discharge angle : 45 degree) (Discharge angle : 45 degree) • Heating Air Velocity distribution • Heating temperature distribution (Discharge angle : 52 degree) (Discharge angle : 52 degree) CNG364DD (AC036DN4DCG/AA) + CXG36ADD (AC036DXADCG/AA)
Page 28
9. Temperature and air flow distribution Wind-Free 4Way Cassette CNG484DD (AC048DN4DCG/AA) + CXG48ADD (AC048DXADCG/AA) • Cooling Air Velocity distribution • Cooling temperature distribution (Discharge angle : 45 degree) (Discharge angle : 45 degree) • Heating Air Velocity distribution • Heating temperature distribution (Discharge angle : 52 degree) (Discharge angle : 52 degree)
Outdoor Units 1. Summary Table 2. Dimensional Drawing 3. Center of Gravity 4. Electrical Wiring Diagram 5. Sound Data 6. Capacity Correction 7. Operation Range 8. Piping Diagram...
Page 30
1 1 . . S S ummary ummary T Tabl able e Outdoor Units Performance Characteristics Sound Pressure Level (dBA) Sound Power Capacity Net Size Net Weight Airflow Model Code (Btu/h) (WxHxD inch) (lbs) (CFM) Level (dBA) Cooling Heating 18,000 CXG18ADD (AC018DXADCG/AA) 34.65 x 25.12 x 12.20 1,766...
Page 31
2 2 . . Dimensional Dr Dimensional Dra a wing wing Outdoor Units CXG18ADD (AC018DXADCG/AA) Units : mm [inches] Name Description Gas pipe connection Φ 12.7 (1/2) Liquid pipe connection Φ 6.35 (1/4) Drain pipe connection...
Page 32
2 2 . . Dimensional Dr Dimensional Dra a wing wing Outdoor Units CXG24ADD (AC024DXADCG/AA) Units : mm [inches] Name Description Gas pipe connection Φ 15.88 (5/8) Liquid pipe connection Φ 6.35 (1/4) Drain pipe connection...
Page 33
2 2 . . Dimensional Dr Dimensional Dra a wing wing Outdoor Units CXG30ADD (AC030DXADCG/AA), CXG36ADD (AC036DXADCG/AA) Units : mm [inches] [22-7/8] Name Description Liquid pipe connection Φ 9.52 (3/8) Gas pipe connection Φ 15.88 (5/8) Front / Side / Rear / Bottom Piping intake knockout hole Power wiring conduit Front / Side / Rear , Φ...
Page 34
2 2 . . Dimensional Dr Dimensional Dra a wing wing Outdoor Units CXG48ADD (AC048DXADCG/AA) Units : mm [inches] Name Description Liquid pipe connection Φ 9.52 (3/8) Gas pipe connection Φ 15.88 (5/8) Front / Side / Rear / Bottom Piping intake knockout hole Power wiring conduit Front / Side / Rear , Φ...
Page 35
3 3 . . C C ent enter er of Gr of Gra a vity vity Outdoor Units CXG18ADD (AC018DXADCG/AA) Units : mm [inches] 150.0 220.0 [8-5/8] [5-7/8] 661.0 [26] 338.0 [13-5/16] CXG24ADD (AC024DXADCG/AA) Units : mm [inches]...
Page 36
3 3 . . C C ent enter er of Gr of Gra a vity vity Outdoor Units CXG30ADD (AC030DXADCG/AA), CXG36ADD (AC036DXADCG/AA) Units : mm [inches] CXG48ADD (AC048DXADCG/AA) Units : mm [inches]...
Page 37
4. Electrical Wiring Diagram Outdoor Units CXG18ADD (AC018DXADCG/AA), CXG24ADD (AC024DXADCG/AA) ERROR CHECK Contact output port for error check OUT-TH(10K) OUTDOOR TEMPERATURE SENSOR Electronic Expansion Valve Contact output port for EXTERNAL Input port for external COMP CHECK DIS-TH(200K) DISCHARGE TEMPERATURE SENSOR compressor operation check contact control CRTL...
Page 38
4. Electrical Wiring Diagram Outdoor Units CXG30ADD (AC030DXADCG/AA), CXG36ADD (AC036DXADCG/AA), CXG48ADD (AC048DXADCG/AA) BELT 4WAY BASE ※ Thermistor(TH) Value 10㏀ at 25℃(77℉) 200㏀ at HEATER VALVE HEATER 25℃(77℉) High CN406 CN844 CN01 CN100 CN847 CN845 Pressure (RED) (YEL) (WHT) (WHT) (RED) (BLU) Sensor FH151...
Page 39
5 5 . . S S ound D ound Data Outdoor Units Sound Pressure level Unit: dB(A) Model Cooling Heating Microphone CXG18ADD (AC018DXADCG/AA) CXG24ADD (AC024DXADCG/AA) 1.5m CXG30ADD (AC030DXADCG/AA) Front CXG36ADD (AC036DXADCG/AA) • NC Curve 1) CXG18ADD (AC018DXADCG/AA) 2) CXG24ADD (AC024DXADCG/AA) NC 70 NC 70 Heating...
Page 40
5 5 . . S S ound D ound Data Outdoor Units Sound Pressure level Unit: dB(A) Model Cooling Heating Microphone CXG48ADD (AC048DXADCG/AA) 1.5m Front • NC Curve 1) CXG48ADD (AC048DXADCG/AA) Heating NC 70 Cooling NC 60 NC 55 NC 50 NC 45 NC 40 NC 35...
Page 41
5 5 . . S S ound D ound Data Outdoor Units Sound Power level Unit: dB(A) NOTE Model Cooling • Specifications may be subject to change without prior notice CXG18ADD (AC018DXADCG/AA) - Sound power level is an absolute value that a sound source generates.
Page 42
5 5 . . S S ound D ound Data Outdoor Units Sound Power level Unit: dB(A) NOTE Model Cooling • Specifications may be subject to change without prior notice CXG48ADD (AC048DXADCG/AA) - Sound power level is an absolute value that a sound source generates.
Page 45
7 7 . . Oper Operation Range ation Range Outdoor Units Cooling Heating NOTE • The assumed installation conditions are follows - The pipe length(including elbow) is 7.5m(24.6ft). - The level difference is 0 m.
• Do not use means to accelerate the defrost operation or to clean, other than those recommended by Samsung. • Do not pierce or burn. • Be aware that refrigerants may not contain an odor.
Page 51
• Any auxiliary device installed must be approved by Samsung and must be suitable for operating with the • The actual total refrigerant charge is in accordance with refrigerant marked on the label. the room size in accordance with Table 1.
Installation Indoor Units WindFree 4Way Cassette Spacing requirements 59.1 inch (1500 mm) or more 98.43 inch (2500 mm) or more 0.79 inch (20 mm) Obstruction • As a rule, the unit cannot be installed at a height of less that 2.5m. Unit: inch(mm) Model AC018DN4DCG...
Page 53
Installation Indoor Units WindFree 4Way Cassette CAUTION • T heindoorunitmustbeinstalledaccordingtothespecifieddistancesinordertopermitaccessibilityfromeach side, to guarantee correct operation, maintenance, and repair of the unit. The components of the indoor unit must be reachable and removable under safe conditions for people and the unit. •...
Installation Indoor Units WindFree 4Way Cassette NOTE • A: Reference for the outer circumference of the unit (Wheninsulatingthebodyoftheindoorunit,useAasthereferenceforitsoutercircumference.) Unit:inch (mm) Indoor unit AC018DN4DCG 35.83X7.60 37.00X7.60 24.02X7.60 25.59X7.60 34.25X34.25 AC024DN4DCG (910X193) (940X193) (610X193) (650X193) (870X870) 4-Way AC030DN4DCG Cassette 35.83X9.25 37.00X9.25 24.02X9.25 25.59X9.25 34.25X34.25 AC036DN4DCG...
Page 55
Installation Indoor Units WindFree 4Way Cassette 3 Installthesuspensionbolts,dependingontheceilingtype. Ceiling support CAUTION • M akesurethattheceilingisstrongenoughtosupporttheweightoftheindoorunit.Beforehangingtheunit, test the strength of each attached suspension bolt. • Ifthelengthofthesuspensionboltismorethan1.5m,youarerequiredtopreventvibration. 4 Screweightpairsofnutsandwasherstothesuspensionbolts,makingspaceforhangingtheindoorunit. CAUTION • You must install all of the suspension rods. • I tisimportanttoleavesufficientspaceinthefalseceilingtoallowaccessformaintenanceorrepairstothe drainagepipeconnection,therefrigerantpipeconnection,ortoremovetheunitifnecessary.
Page 56
Installation Indoor Units WindFree 4Way Cassette When the installation template is made of paper Unit: inch(mm) 4 way Cassette 0.79 inch (20 mm) Indoor unit Ceiling 0.67 inch (17 mm) Gauge of dimensions Installation Procedure Installing the drain hose and drain pipe 1 Pushthesupplieddrainhoseasfaraspossibleoverthedrainsocket.
Page 57
Installation Indoor Units WindFree 4Way Cassette • Installairventilationtodraincondensationsmoothly. Air ventilation Ceiling • fPlace the drainpipe at a height of 11.81 to 21.65 inches (300 to 550 mm) within 11.81 inches (300 mm) from the drain hose, and install it with a drop-off of at least 0.79 inch (20 mm). •...
Page 58
Installation Indoor Units WindFree 4Way Cassette • Do not apply force to the piping on the unit side when connecting the drain hose. The hose should not be allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other support as close to the unit as possible.
Page 59
Installation Indoor Units WindFree 4Way Cassette NOTE • Ifaconcentrateddrainpipeisinstalled,refertothefigurebelow. Main air vent Full thread (must be installed) bolt hanger 3.28 ~ 4.92 ft (1~1.5 m) 32.8 ft (10 m) 32.8 ft (10 m) 7.87 in (200 mm) 21.65 in (550 mm) Common horizontal drainpipe Main Drainpipe (more than 1/100 slope)
Installation Indoor Units WindFree 4Way Cassette Connecting the power and communication cables Bushing bracket installation When connecting the power supply wire conduit, the supplied bracket must be installed as shown in the picture below. Indoor unit NOTE • Please follow national and local electrical codes. Additional electrical connection components <...
Page 61
Installation Indoor Units WindFree 4Way Cassette Indoor Unit Outdoor Unit 1(L) 2(N) L F1 F2 Cable Cable clamp clamp Communication Main power cable cable Outdoor to indoor power cable Indoor power supply Power supply Max/Min(V) Indoor power cable 208 to 230V, 60 Hz ±10% AWG18↑, 3 wires Communication cable...
• With the screw unfastened, push the control box cover in the arrow direction and then pull it down. • After removing the control box cover, you can start installation. 2 Push the switch-type handle inwards and pull out the grille. • There are handles on the left and right of the Samsung logo above the grille.
Page 63
Installation Indoor Units 4 Way Cassette WindFree WiFi Panel 3 Install the panel with two hooks on both sides of the indoor unit. Hook 4 Separate four panel edges. When separating the edges, put your index fingers into two grooves in each corner. Groove CAUTION •...
Page 64
Installation Indoor Units 4 Way Cassette WindFree WiFi Panel 6 Connect 5 cables between the indoor unit and the panel. • Make sure you check the number of pins on the three white terminal before connecting the cables. Blue Yellow White (10 PIN) (10 PIN)
Page 65
Installation Indoor Units 4 Way Cassette WindFree WiFi Panel 8 Attach and close the front grille. • Make sure the hooks on the rear side of grille fits properly into the grooves on panel (➊) and then push the panel to close (➋). Hook Grille 9 Check out that the panel is fixed to the indoor unit.
Installation Outdoor Units Installation location requirements • The outdoor unit shall be installed in an open space that is always ventilated. • The local gas regulations shall be observed. • For installation inside a building (this applies either to indoor or outdoor units installed inside) a minimum room floor area of space conditioned is mandatory according to EN378-1:2017 (see the reference table into the indoor unit installation manual).
Page 67
Outdoor Unit 7.87 inch(200mm) Air Guide Duct (This product is not provided by Samsung) • Install the unit at a height where its base can be firmly fixed in place. • Make sure that the water dripping from the drain hose runs away correctly and safely.
Page 68
• Check the condition of the product periodically. – Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG (Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the product condition.
Page 69
Installation Outdoor Units Unit : inch (mm) Outdoor unit dimensions A Type C Type AC018DXADCG / AC018DXSCCF AC024DXSCCG, AC030/036DXADCG, AC030/036DXSCCF 12.20(310) 25.98(660) 37.01 (940) 24.41 (620) 1.93(49) 34.65(880) B Type D Type AC018DXSCCG, AC024DXADCG, AC024DXSCCF AC048DXADCG 12.20 (310) 37.01 (940) 26.02 (661) 24.41 (620) 34.65 (880)
Page 70
Installation Outdoor Units When installing more than 1 outdoor unit Unit : inch (mm) 7.87(200) 78.7(2000) 118. 1 1(3000) 5. 9 1 (150) 39.37(1000) or more or more or more or more or more 5.91 (150) or more 5.91 (150) or more 5.91 (150) or more 5.91 (150) or more 11.81 (300) 7.87(200)
Page 71
Installation Outdoor Units CAUTION • Should adopt bar type louver. Don’t use a type of rain resistance louver. [Bar type louver] [Rain resistance louver] • Louver specifications. − Angle criteria : less than 20° − Opening ratio criteria : greater than 80% Fixing the outdoor unit in place Install the outdoor unit on a rigid and stable base to prevent disturbance from any noise caused by vibration.
Page 72
Installation Outdoor Units CAUTION • Install a drain outlet at the lowest end around the base for outdoor unit drainage • When installing the outdoor unit on the roof, waterproof the unit and check the ceiling strength. Optional: Fixing the outdoor unit to a wall with a rack Designed to cut off residual vibration from outdoor unit to rack.
Page 73
Installation Outdoor Units Air conditioning system examples When using an earth leakage circuit breaker (ELCB) for a single phase unit. Main power Communication cable cable Outdoor-to-indoor power cable MCCB Earthing ELCB Indoor Unit Outdoor Unit ※ The appearance of the unit may be different from the picture depending on the model. CAUTION •...
Page 74
Installation Outdoor Units When using ELB for AC024/030/036/048DXSCCG, AC030/036/048DXADCG, AC030/036DXSCCF (1-phase) Power Electrical supply component box MCCB F1 F2 1(L) 2(N) L Cable tie Main power Outdoor to Communication cable indoor power cable cable The appearance of the unit may be different from the picture depending on the model.
Page 75
Installation Outdoor Units Main power terminal block specifications [Unit : inch(mm)] AC power: Communication: M4 screw M4 screw 1(L) 2(N) 0.40(10.1) 0.54(13.8) 0.41(10.3) 0.45(11.4) Main power cable specifications The power cable is not supplied with the air conditioner. • Select the power supply cable following relevant local and national regulations. •...
Page 76
Installation Outdoor Units Model Outdoor Indoor Rated input Power current of the Source power conversion Outdoor Indoor equipment FAN1(A) FAN2(A) FAN(A) AC030DN4DCG 0.79 AC030DXSCCF AC030DNHDCG 17. 9 0.97 3.50 27.0 30.0 AC030DNTDCG 0.51 AC030DNHDCG 3.50 AC030DNTDCG 0.51 AC030DXSCCG AC030DN4DCG 22.6 1.20 1.20 0.79...
Page 77
Installation Outdoor Units NOTE • RLA is based on AHRI 210/240 cooling standard condition [Indoor temp. : 26.7 °C / 80 °F(DB) / 19.46 ° C / 67 °F(WB), Outdoor temp. : 35 °C / 95 °F(DB)] • Voltage tolerance is ± 10 %. •...
Page 78
Installation Outdoor Units Connecting the outdoor-to-indoor power cable and the communication cable • AC018DXSCCG, AC024DXADCG, AC024DXSCCF • AC024/030/036/048DXSCCG, AC018DXADCG, AC018DXSCCF AC030/036/048DXADCG, AC030/036DXSCCF Indoor Unit Indoor Unit Outdoor Unit Outdoor Unit 1(L) 2(N) L F1 F2 1(L) 2(N) L F1 F 2 Cable clamp Cable clamp Cable clamp...
Page 79
Installation Outdoor Units Outdoor-to-indoor power terminal specifications • Connect the cables to the terminal board using the compressed ring terminal. • Cover a solderless ring terminal and a connector part of the power cable and then connect it. Silver solder Nominal Nominal dimensions...
Page 80
Installation Outdoor Units CAUTION • When connecting cables, you can connect the cables to the electrical part or connect them through the holes below depending on the spot. • Connect the communication cable between the indoor and outdoor units through a conduit to protect against external forces, and feed the conduit through the wall together with refrigerant piping.
Installation Installation Outdoor Units Outdoor Units Connecting the refrigerant pipe Items Maximum allowable length [ft (m)] Applicable outdoor Main pipe Max. height difference between outdoor and indoor units (h1) unit models (L1) AC018DXSCCF 98.4(30) 65.6(20) AC018DXADCG AC018DXSCCG AC024DXSCCG AC024DXADCG 164.0(50) 98.4(30) AC030DXADCG AC036DXADCG...
Page 82
Installation Installation Outdoor Units Outdoor Units CAUTION Pipe outlet • Cut the pipe outlet to the exact pipe size. In addition, remove foreign substances and burrs around the outlet. • Perform cutting with only a cutter (ex. nipper) and never tap with a hammer near the pipe outlet. Otherwise, it may cause product damage such as warping of the cabinet.
Page 83
Installation Installation Outdoor Units Outdoor Units 3. After about 30 minutes, charge the refrigerant through the service port of the gas stop valve. Indoor Unit Balance Vacuum Pump Gas side stop valve (service port) Liquid side stop valve (Non-service port) •...
Page 84
Installation Installation Outdoor door Units Units Calculating the quantity of refrigerant to add The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialist. When installing the outdoor unit only Inter-connection pipe length [ft(m)] Model...
Page 85
2024.09 Ver.1.0 Samsung Electronics Co., LTD. Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677 Website : www.samsung.com, https://partnerhub.samsung.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.