Mitsubishi Electric BACS-AP50 Instruction Book
Mitsubishi Electric BACS-AP50 Instruction Book

Mitsubishi Electric BACS-AP50 Instruction Book

Air conditioning control system, bm adapter
Hide thumbs Also See for BACS-AP50:

Advertisement

Quick Links

Air Conditioning Control System
BM ADAPTER
BACS-AP50
Before using the controller,
please read this Instruction
Book carefully to ensure proper
operation.
Retain this manual for future
reference.
Instruction Book (Detailed Operation)
Contents
Safety precautions ........................................................................ 2
1. Introduction ............................................................................. 4
1-1. Screen images used in this manual ............................................4
1-2. BACnet Setting Tool version .......................................................4
1-3. Connection method .....................................................................4
1-4. PC environment ..........................................................................5
2. Setting the operating environment ......................................... 6
2-1. Setting the IP address of the PC.................................................6
2-2. Disabling a proxy server .............................................................9
2-3. Installing .NET Framework ..........................................................9
3-1. Installation .................................................................................10
3-2. Uninstallation ............................................................................12
4. Initial settings for the controller ............................................. 13
4-1. Quick IP address (LAN1) setting ...............................................13
4-2. Software updates ......................................................................15
5-1. Connecting the BACnet Setting Tool.........................................20
5-2. Starting up the BACnet Setting Tool .........................................21
5-3. Exiting the BACnet Setting Tool ................................................22
6-1. Screen configuration .................................................................23
6-2. Menu bar configuration .............................................................24
6-3. Setting tab configuration ...........................................................25
6-4. Initial setting procedure .............................................................26
7. Saving settings data ............................................................. 28
7-1. Settings data flow .....................................................................28
7-2. Backing up settings data ...........................................................28
8. Menu bar .............................................................................. 29
8-1. File ............................................................................................29
8-2. BACS-AP50 ..............................................................................30
8-3. Help ..........................................................................................32
9. Setting screens ..................................................................... 33
9-1. Explanation of screen buttons ..................................................33
9-2. System settings ........................................................................35
9-3. Group settings ..........................................................................38
9-4. BACnet settings ........................................................................43
10. Maintenance functions ......................................................... 65
10-1. Common matters ....................................................................65
10-2. User management ..................................................................66
10-3. Backing up/importing settings data .........................................67
Trademarks and registered trademarks ..................................... 76
<ORIGINAL>

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BACS-AP50 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mitsubishi Electric BACS-AP50

  • Page 1: Table Of Contents

    7-1. Settings data flow ..............28 7-2. Backing up settings data ............28 8. Menu bar ................29 8-1. File ....................29 8-2. BACS-AP50 ................30 8-3. Help ..................32 9. Setting screens ..............33 9-1. Explanation of screen buttons ..........33 9-2. System settings ................35 9-3.
  • Page 2: Safety Precautions

    Safety precautions ►Observe these precautions carefully to ensure safety. ►After reading this manual, pass the manual on to the end user to retain for future reference. ►The user should keep this manual for future reference and refer to it as necessary. This manual should be made available to those who repair or relocate the units.
  • Page 3: Precautions For Relocating Or Repairing The Unit

    To reduce the risk of injury, electric shock, or malfunction, avoid contact with the sharp edges of certain parts. Consult your dealer for the proper disposal of the controller. Improper disposal will pose a risk of environmental pollution. Precautions for relocating or repairing the unit The controller must be repaired or moved only by qualified personnel.
  • Page 4: Introduction

    The BACnet Setting Tool connects with the BACS-AP50 using a LAN. Connect the PC with the BACnet Setting Tool installed to the LAN1 connector of the BACS-AP50 via a HUB (refer to the figure below). For the LAN cable, use a cable that is compatible with category 5 or higher.
  • Page 5: Pc Environment

    1-4. PC environment The PC operating environment for using the installed tools is as follows. Ensure that the PC is connected to the same network as the BACS-AP50. PC operating environment (2) BACnet Setting Tool Item Requirements Remarks (1) Browser 1.0 GHz or more...
  • Page 6: Setting The Operating Environment

    Set the IP address of the PC to be used for the BACnet Setting Tool. Set an IP address for the PC that does not duplicate the IP address of LAN1 of each BACS-AP50 (initial value: 192.168.1.1) but is an IP address of the same network.
  • Page 7 (4) In the [Network Connections] window, double-click the [Ethernet] icon. (5) In the [Ethernet status] window, click [Properties]. (6) In the [Ethernet Properties] window, click [Internet Protocol Version 4 (TCP/IPv4)] to select it, and click [Properties]. WT10955X01...
  • Page 8 (7) In the [Internet Protocol Version 4 (TCP/IPv4) Properties] window, check the radio button next to [Use the following IP address]. Enter the IP address (e.g., [192.168.1.101]) in the [IP address] field, and enter the subnet mask (e.g., [255.255.255.0]) in the [Subnet mask] field. (8) Keep clicking [OK] or [Close] to close all windows.
  • Page 9: Disabling A Proxy Server

    2-2. Disabling a proxy server Configure the settings for the IP connection environment of the PC (disable a proxy server). (1) Open the Network and Sharing center as follows. ® Windows 10 or 11 Search for the control panel using the search box, and click [Network and Sharing]. (2) Click [Internet options].
  • Page 10: Installation And Uninstallation Of The Bacnet Setting Tool

    3. Installation and uninstallation of the BACnet Setting Tool This chapter explains how to install the BACnet Setting Tool (SetBACnet) to a PC and how to uninstall it. If you click [Cancel] in any of the steps during the installation or uninstallation, the installation or uninstallation will be canceled.
  • Page 11 Click [Browse...] to select a different installation destination folder. When done selecting the folder, click [Next] to proceed. The default installation destination folder location is [C:\Program Files (x86)\MITSUBISHI ELECTRIC CORPORATION\BACS-AP50 BACnet Setting Tool]. Clicking [Disk Cost...] will display the disk capacity of each drive of the PC.
  • Page 12: Uninstallation

    Quit the program if it is. (2) Click [Control Panel] in the Start menu, and click [Uninstall a program]. (3) In the [Programs and Features] window, click [BACS-AP50_SetBACnet] to uninstall it. Or, click [BACS-AP50 BACnet Setting Tool], right-click, and select [Uninstall].
  • Page 13: Initial Settings For The Controller

    4. Initial settings for the controller 4-1. Quick IP address (LAN1) setting The IP address (LAN1) and the network settings of the BACS-AP50 can be set using the rotary switch (SW1). (Set SW1 to 1 to F.) IP address (LAN1)
  • Page 14 2. Point the arrow of the SW1 at the alphanumeric character you want to select. 3. Turn on the BACS-AP50. The BACS-AP50 will start with the address (192.168.1.1 to 14) corresponding to the alphanumeric character you selected with the SW1.
  • Page 15: Software Updates

    2) If using a PC for initial settings, update the BACnet Setting Tool as well. (4) Precautions during updates 1) Do not turn off the BACS-AP50 during the BACS-AP50 update. 2) If using a USB flash drive: • Do not remove the USB flash drive until the update is complete.
  • Page 16 Check that the update PC satisfies the requirements given in “PC environment.” Set the IP address of the update PC so that it can connect to the BACS-AP50 via LAN. For update using a Web browser on a PC that is connected to an internal LAN, request your network administrator to provide the IP address, subnet mask, etc.
  • Page 17 (2) Update operation Step 1. Connect the update PC and the LAN1 port on the BACS-AP50 using a LAN cable. 2. Use a Web browser to access the following Web page address. The factory default IP address of the BACS-AP50 is 192.168.1.1.
  • Page 18 Note The update proceeds as follows. It takes approximately 10 minutes to complete the update. STATUS LED Step Remarks Color Status Update start Blue Blinking BACS-AP50 will restart automatically, then the update complete. WT10955X01...
  • Page 19 Hold down the button until the STATUS LED lights up in blue (approx. 1 minute). Start the update. 4. Remove the USB flash drive once the update is complete. 5. Reset the power of the BACS-AP50. Note The update proceeds as follows.
  • Page 20: Connecting And Starting Up The Bacnet Setting Tool

    (check that a cable is not connected to LAN2). Then, connect LAN1 and the PC with the BACnet Setting Tool installed using a LAN cable. The BACnet Setting Tool can only be connected to a single BACS-AP50 at a time. Accordingly, when using a configuration that connects multiple BACS-AP50 units, configure BACnet settings for each BACS-AP50.
  • Page 21: Starting Up The Bacnet Setting Tool

    • Is the cable between the PC and BACS-AP50 (LAN1) connected correctly? • Is the IP address of the PC set to an IP address of the same network as LAN1 of the BACS-AP50? (Refer to 2-1 “Setting the IP address of the PC” for details.) •...
  • Page 22: Exiting The Bacnet Setting Tool

    5-3. Exiting the BACnet Setting Tool To exit the BACnet Setting Tool, click at the top right of the BACnet Setting Tool screen or select [Exit] from [File] in the menu bar. WT10955X01...
  • Page 23: Bacnet Setting Tool Screens And Setting Items

    6. BACnet Setting Tool screens and setting items 6-1. Screen configuration The screen configuration of the BACnet Setting Tool is shown below. To switch the settings screens, select menus on the menu bar, main tabs, or sub tabs. Menu bar Main tab Sub tab WT10955X01...
  • Page 24: Menu Bar Configuration

    Saves BACnet Setting Tool settings data to a specific folder with a Save Settings As... specific file name. Exits the BACnet Setting Tool. Exit Sets the LAN1 IP address for the BACS-AP50 to communicate BACS-AP50 Property with. Acquires the settings data from the BACS-AP50.
  • Page 25: Setting Tab Configuration

    (Event_Enable, Notify_Type). Other Set the notification destination at reset. Used when using the Settings Tool to cancel a BACS-AP50 emergency ForcedOff Reset stop originating from the central monitoring device (BACnet). Settings not required.
  • Page 26: Initial Setting Procedure

    6-4. Initial setting procedure 6-4-1. BACnet function initial settings flow Perform the following BACS-AP50 BACnet function settings. Refer to this manual for detailed procedures and settings details for BACS-AP50 BACnet settings. Ensure that the LAN2 (for BACnet) of BACS-AP50 is not connected.
  • Page 27 [BACS-AP50] — [Mode Setting] (Confirm) (Refer to 8-2-4.) *1 After performing [Send settings] to the BACS-AP50, check the followings. ① Perform [Acquire settings] and check that the data has been properly set. ② Check that the BACS-AP50 BACnet connection mode is “Online”.
  • Page 28: Saving Settings Data

    (refer to 9-2-1-4 “Use Time Synchronaization by Central Monitoring Device”). • In the BACS-AP50, LAN1 is used for the setting tool and LAN2 is used for BACnet connection, which is the opposite of the BAC-HD150. The settings for LAN1 and LAN2 will be reversed when importing the configuration data, so please ensure that the settings are correct.
  • Page 29: Menu Bar

    8-1-1. New Settings Used to create new settings information. Displays the initial status settings screen (displays default values for screen). The initial status is the same as the factory default settings for the BACS-AP50. 8-1-2. Open Settings Used when opening a settings data file in BACnet Setting Tool. Select the saved file name, click [Open Settings] to open the file and display settings details on the settings screen.
  • Page 30: Bacs-Ap50

    Use [BACS-AP50] menu for the following operations and settings. 8-2-1. Property Input the LAN1 IP address or the host name of the BACS-AP50 that is the BACnet Setting Tool destination, and click [OK] to set. Set the port number to 443 (fixed).
  • Page 31: Send Settings

    (5) Use [Send settings] to reflect the data (a) to the BACS-AP50. Note: If an error message “Version Mismatch Error The version of this tool is not compatible with the version of BACS-AP50” pops up after [Send settings] is executed, refer to section 1-2 “BACnet Setting Tool version” for version compatibility.
  • Page 32: Date And Time

    Sets the date and time in the BACS-AP50. By selecting [Date and Time], the BACnet Setting Tool acquires from the BACS-AP50 the date and time stored in the BACS-AP50. Use [▲]/[▼] to set the current time, then click [Set] to update the date and time saved in the BACS-AP50. Additionally, click [Refresh] to display the current time of the BACS-AP50.
  • Page 33: Setting Screens

    Click to temporarily save the displayed settings data. Selecting [Save Settings] enables switching to other tab screens. However, settings details are not sent to the BACS-AP50 at the point [Save Settings] is clicked. Save Settings After configuring settings, select [Send settings] from the tool bar to send settings details to the ④...
  • Page 34: Pop-Up Screen

    9-1-2. Pop-up screen 9-1-2-1. [OK] Reflects the settings details in the pop-up window to the BACnet Setting Tool, and closes the pop-up window. 9-1-2-2. [Cancel] Closes the pop-up window, without reflecting the settings details in the pop-up window to the BACnet Setting Tool.
  • Page 35: System Settings

    [System Settings] tab contains the [Basic System] and [M-NET] and sub tabs. 9-2-1. Basic system Set the IP addresses of BACS-AP50 LAN1 (for Setting Tool) and LAN2 (for BACnet). 9-2-1-1. LAN1 (for Setting Tool) Set fields for the LAN1 (for Setting Tool) IP address. LAN1 can only use IPv4.
  • Page 36 9-2-1-4. Use Time Synchronaization by Central Monitoring Device If reflecting the time data sent from the central monitoring device to the BACS-AP50 or M-NET system (indoor units, remote controllers, or system controllers), select this check box. When selecting this check box, ensure that “Time Synchronization”...
  • Page 37 9-2-1-5. BACS-AP50 Data BACS-AP50-related data appears when [Acquire settings] is performed. (1) Serial No BACS-AP50 serial number appears. (2) BACS-AP50 Program Version BACS-AP50 program version appears. (3) BACnet Program Version BACS-AP50 BACnet program version appears. 9-2-2. M-NET Settings Click the [M-NET] tab on the [System Settings] tab to display the [M-NET Settings] window.
  • Page 38: Group Settings

    *2 The maximum number of remote controllers and system controllers that can be configured into a group is four, not including the BACS-AP50 unit. No more than two remote controllers can be included in each group. *3 The number of units connected to M-NET (one system) must satisfy the following restrictions.
  • Page 39 (1) Configuring the group setting for the units Double-click the Unit address field of the group to be set to display the [Select Unit Address] popup window. Select the units to be included in each group on this window. (a) Unit selection Click a unit address to select.
  • Page 40 Light gray: System controllers that do not belong to any group Lime green: System controllers that are currently selected Dark gray: BACS-AP50 address 9-3-2. OC settings To use objects related to outdoor units (COP (AI_51zz01), etc.), enter their addresses in the OC settings.
  • Page 41 (1) Configuring the outdoor unit settings Click [OC Settings] to display the Select OC Address popup window. (a) Outdoor unit selection Click an outdoor unit address to select. Click the selected address to deselect. The unit selection status is indicated in different colors. Light gray indicates the units that are available for selection, and lime green indicates the units that are currently selected.
  • Page 42 (1) Configuring the interlock settings for the LOSSNAY units Double-click the LOSSNAY address field to display the [Select LOSSNAY Address] popup window. (a) Interlocking LOSSNAY address selection Click the address of the LOSSNAY unit to select. Click the selected address to deselect. Light gray indicates the units that are available for selection, and lime green indicates the units that are currently selected.
  • Page 43: Bacnet Settings

    I-Am segmentation support information, and vendor ID to destination devices. 9-4-1. BACnet Sets BACS-AP50 device number, BACnet functions, and other settings. From [BACnet Settings], click the [BACnet] tab to display the [BACnet Settings] screen. Initial settings are as follows. WT10955X01...
  • Page 44 9-4-1-1. BACS-AP50 BACnet Settings Sets items related to the BACS-AP50 device number and BACnet functions. (Items that cannot be changed are displayed in light gray.) Item Description Default value Select the Revision No. of the BACnet Standard applied to the BACS-AP50 according to the central monitoring device to be Revision No.
  • Page 45 (Heat or Cool). By enabling this setting, all indoor units that are connected Old Model Compatibility Mode to BACS-AP50 can be operated according to the setting for Unchecked the single set point temperature. The function is enabled when the checkbox is checked.
  • Page 46 Register the BACS-AP50 to the BBMD as an external device. Item Description Default Check the checkbox to register the BACS-AP50 to the BBMD as an Use Remote BBMD Unchecked external device. Set the time limit (in minute increments) for the BACS-AP50 to be registered to the BBMD as an external device.
  • Page 47 From [BACnet Settings], click the [Network and Device] tab to display the [Network and Device Settings] screen. Assign IP addresses and port numbers to network and device numbers. This chapter covers settings for the following devices that exchange information with the BACS-AP50. • Notification destination devices for COV notifications and Event notifications •...
  • Page 48 No. 1 above. IP Address (Blank) *1*2 (The IP address of the BACnet router on the network to which the BACS-AP50 is connected.) The number of the port that the BACnet router uses for BACnet Port No. communication appears here. 47808 Leave [47808] as it is unless otherwise specified.
  • Page 49 9-4-2-2. Device Address Registers other devices such as central monitoring devices that send and receive data with the BACS-AP50. A maximum of 11 devices can be registered as communications devices (including broadcast). (1) Registering communications device Sets communications device information. Click [Add] to display the [Device Address] pop-up window.
  • Page 50 (2) Changing communications device Changes device settings. Select the device to change and click [Modify], or double-click the [Address/Port No.] to change to display the [Device Address] pop-up window. When changing or deleting the device IP address, ensure that you check the notification destination IP address set in 9-4-3 “COV Notification”...
  • Page 51: Cov Notification

    9-4-3. COV Notification From [BACnet Settings], click the [COV Notification] tab to display the [COV Notification Settings] screen. This assigns device numbers registered on the [Network and Device] screen to the COV notification number. By using the COV notification number set here to set COV notifications for each control item in 9-4-5 “Object”, send COV notifications such as changes in status of control items and start-stop status in accordance with each COV notification number.
  • Page 52 9-4-3-2. Notification Address (1) Setting “Notification Address” Sets the COV number notification destination device. Select the [COV No.] (left) for the device to set, and under [Notification Address] (right), click [Add] to display the [Notification Address] pop-up window. A maximum of 5 devices can be set for each COV No. (including broadcast). Item Description Default...
  • Page 53 Click [Select] to display the [Network and Device Settings - Select BACnet Device] screen (figure below), from where you can select the COV notification destination device number. This screen shows the device list set in 9-4-2 “Network and Device”. In the screen above, select (reflect) the device number and click [Select] to reflect the device information selected in [Device No.] in the [Notification Address] pop-up window.
  • Page 54: Event Notification

    9-4-4. Event Notification From [BACnet Settings], click the [Event Notification] tab to display the [Event Notification Settings] screen. As in 9-4-3 “COV Notification”, this assigns device numbers registered on the [Network and Device] screen to the notification destination class ID. By using the notification class set here to set event notifications for each control item in 9-4-5 “Object”, send event notifications such as changes in status of control items and abnormality alarms in accordance with each notification class ID.
  • Page 55 9-4-4-2. Notification Address (1) Setting “Notification Address” Sets the notification destination device to register in the notification class ID. Select the [Notification Class ID] for the device to set, and under [Notification Address], click [Add] to display the [Notification Address] pop-up window.
  • Page 56 Click [Select] to display the [Network and Device Settings - Select BACnet Device] screen (figure below), from where you can select the event notification destination device number. This screen shows the device list set in 9-4-2 “Network and Device”. In the screen above, select (reflect) the device number and click [Select] to reflect the device information selected in [Device No.] in the [Notification Address] pop-up window.
  • Page 57 Leave the checkbox unchecked unless the object corresponding to the checkbox is used. 9-4-5-1. Selecting objects to be used Select objects to use with the BACS-AP50 (control items) by selecting the check box in the [Use] field, (Use: )/Not use: ).
  • Page 58 AV_01xx28); and for groups not supporting dual-set-point mode, issue commands using indoor temperature set value objects (AV_01xx10). If the central monitoring device issues a command for groups that do not support dual-set-point mode using a dual-set-point mode object, then the BACS-AP50 will return an error to the central monitoring device. BACnet M-NET...
  • Page 59: Notification Setting

    9-4-5-2. Notification Setting Select the [Use] check box ( ), and set notifications (COV Notification and Event Notification) for enabled control items (objects). (1) Setting COV Notification and Event notification Double-click the control items (objects) to set, and the [Notification Setting] pop-up window as below will be displayed.
  • Page 60 *2 COV notification is sent when there is a change by the increase/decrease portion set by the COV Increment. However, because the indication on the BACS-AP50’s LCD and the Web display are rounded off using Swedish rounding, a difference from the notified value may occur.
  • Page 61 Whether or not COV notification and event notification settings are possible for objects is shown below. Support for COV notifications and event notifications (V: Settable/—: Not settable) Control item Object ID COV Notification COV Increment Event Notification OnOffSetup BO_01xx01 — OnOffState BI_01xx02 —...
  • Page 62 Control item Object ID COV Notification COV Increment Event Notification CH_SetTempCool AV_71tt07 — CH_SetTempHeat AV_71tt08 — CH_ReprInletWaterTemp AI_71tt09 — CH_ReprOutletWaterTemp AI_71tt10 — CH_ReprAlarmSignal BI_71tt11 — CH_CommunicationState BI_71tt12 — CH_ProhibitionOnOff BV_71tt15 — — CH_ProhibitionMode BV_71tt16 — — CH_ProhibitionSetTemp BV_71tt17 — — CH_UnitAlarmSignal BI_91uu11 —...
  • Page 63 From [BACnet Settings], click the [Object] tab to display the [Other Settings] screen. This screen displays “Restart Notification Recipients” settings. [1] Restart Notification Recipients Displays introduction sequence at BACS-AP50 start-up, and “I-Am” periodic transmission destination device settings. Default value settings are as follows. Additionally, settings values for these items cannot be changed.
  • Page 64 9-4-7. ForcedOff Reset From [BACnet Settings], click the [ForcedOff Reset] tab to display the [ForcedOff Reset] screen. During an BACS-AP50 emergency stop, clicking the [ForcedOff Reset] button from the central monitoring device (BACnet) will cancel the BACS-AP50 emergency stop. This function is used when canceling an BACS-AP50 emergency stop from the central monitoring device (BACnet) is not possible due to trouble with the central monitoring device (BACnet).
  • Page 65: Maintenance Functions

    10. Maintenance functions 10-1. Common matters Use a Web browser to access the following Web page address. The factory default IP address of the BACS-AP50 is 192.168.1.1 https://192.168.1.1/maintenance Screen transition Item Function and description The login screen to access the operation management screen (2) will Login be displayed.
  • Page 66: User Management

    10-2. User management 10-2-1. User management overview Only Commissioning user settings are possible in BACS-AP50. ■Commissioning user Can perform initial settings and manage all air conditioning units. Click [Settings] - [User Registration] on the operation management screen to display the user registration screen.
  • Page 67: Backing Up/Importing Settings Data

    Settings made with the Web browser or the BACnet Setting Tool can be backed up on a PC. The exported data can be imported back to the BACS-AP50 to restore the previous settings after BACS-AP50 replacement. The settings data can be backed up or imported using the Web browser.
  • Page 68 [1] Backing up settings data Step 1. Click [Backup settings data] (A). After creating settings data, a file download dialog will be displayed, and you can back up the BACS-AP50 settings data files all at once. Note • It takes a few minutes to create the settings data.
  • Page 69: Appendix 1: Bacnet Network Configuration And Settings Examples

    Appendix 1: BACnet network configuration and settings examples The BACS-AP50 only supports BACnet/IP. The following are types of BACnet network configuration. Network configuration Description Local network Local network configuration, without going through a router BACnet router connection Configuration in which each network connects through a BACnet router...
  • Page 70 BACnet Device Device Device Device ID: 22 Device ID: 31 Device ID: 32 BACS-AP50 IP address: 192.168.3.2 IP address: 192.168.2.2 IP address: 192.168.3.1 Device ID: 21 IP address: 192.168.2.1 *1 BMS: Building Management System 2. Configuring the Network and Device Settings The [Network and Device Settings] screen below shows the settings for the sample network configuration with the use of BACnet routers above.
  • Page 71 <Network No.500 settings> <Global Broadcast settings> 1. Configuring the Network and Device Settings – Auto IP address setting Note: You can obtain an IP address automatically without setting the BACnet router IP address and the device IP address. For possible combinations, refer to 9-4-2-2 “Device Address” table. WT10955X01...
  • Page 72 IP address: 192.168.2.1 *1 BMS: Building Management System *2 IP address of IP router for network to which BACS-AP50 is connected *3 The IP router forwards unicast messages across networks, but not broadcast messages. If using broadcast messages, ensure design in order that these do not leave IP routers.
  • Page 73 2. Configuring the Network and Device Settings The [Network and Device Settings] screen below shows the settings for the sample network configuration with the use of IP routers above. “Network No.” is “Local”. The use of IP routers will require the default gateway setting to be configured beforehand. (Refer to 9-2-1-2 “LAN2 (for BACnet)”...
  • Page 74 Ethernet IP address: 192.168.2.10 BACnet BBMD Device IP address: 192.168.2.40 Device ID: 22 BACS-AP50 IP address: 192.168.2.2 Device ID: 21 IP address: 192.168.2.1 *1 BMS: Building Management System ® *2 BBMD: BACnet /IP Broadcast Management Device 2. Configuring the Network and Device Settings The [Network and Device Settings] screen below shows the settings for the sample network configuration with the use of IP routers above.
  • Page 75 BACS-AP50 sends broadcast messages to the following devices: • All devices that belong to the same network as the BACS-AP50 • All devices connected to other networks via the BBMDs...
  • Page 76: Trademarks And Registered Trademarks

    Trademarks and registered trademarks MicroSDHC logo is a trademark of SD-3C, LLC. Android and Google Chrome are trademarks of Google LLC. BACnet is a registered trademark of ASHRAE. IOS is a trademark or registered trademark of Cisco in the U.S. and other countries and is used under license. iPad, iPad mini, iBooks, Safari, macOS, and Apple are trademarks of Apple Inc.
  • Page 77 WT10955X01...
  • Page 78 WT10955X01...
  • Page 79 WT10955X01...
  • Page 80 Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION Air-conditioning & Refrigeration Systems Works 5-66, Tebira 6 Chome, Wakayama-city, 640-8686, Japan WT10955X01...

Table of Contents