KT- EMRG- 650- C FL2
FLUORESCENT EMERGENCY BALLAST
ASSEM BLY AND I NSTAL L AT I ON I NST RUCT I ONS
WARNING:
When using this lighting device, safety precautions should be followed at all times.
READ THE INSTRUCTIONS BELOW CAREFULLY AND FOLLOW THEM FOR YOUR OWN SAFETY.
1. Prior to installation, battery connector must be open to prevent high voltage from being present on output leads (red and yellow).
It must be connected only after installation is complete and AC Power is supplied to the unit.
2. This device is designed for use with one 9W-26W 2-Pin Twin-Tube (G23, GX23 base) or one quad (G24d base) compact fluorescent
lamp in the emergency mode.
3. Please ensure the electricity connections conform to the National Electrical Code and local regulations if applicable.
4. To avoid electric shock, please disconnect normal and emergency power supplies, and battery connector of the emergency ballast
before servicing.
5. This device is designed for factory or field installation in either the ballast channel or on top of indoor fixtures, except air handling,
heated air outlets, wet or hazardous locations. Do not install this device near gas or electric heaters or sealed and gasketed fixtures.
6. AC power source of 120 VAC or 277 VAC is required.
7. The battery is sealed, no-maintenance, and is not replaceable in the field. Please contact manufacturer for information on service.
Do not attempt to service the battery.
8. Do not use accessory equipment that is not recommended by manufacturer. Failure to do so may cause unsafe conditions.
Servicing should only be performed by qualified service personnel.
9. Do not use the product for other than its intended purpose.
LAMP COMPATIBILITY
• Compatible with most one-, two-, three-, and four-lamp electronic, standard and dimming AC ballasts.
• Operates the following lamps under emergency power:
2-Pin CFL (W)
No. of Lamps
1
13-26
Wattage
SAVE THESE INSTRUCTIONS