Download Print this page

Keystone KT-EMRG-650-CFL2 Assembly And Installation Instructions

Fluorescent emergency ballast

Advertisement

Quick Links

KT- EMRG- 650- C FL2
FLUORESCENT EMERGENCY BALLAST
ASSEM BLY AND I NSTAL L AT I ON I NST RUCT I ONS
WARNING:
When using this lighting device, safety precautions should be followed at all times.
READ THE INSTRUCTIONS BELOW CAREFULLY AND FOLLOW THEM FOR YOUR OWN SAFETY.
1. Prior to installation, battery connector must be open to prevent high voltage from being present on output leads (red and yellow).
It must be connected only after installation is complete and AC Power is supplied to the unit.
2. This device is designed for use with one 9W-26W 2-Pin Twin-Tube (G23, GX23 base) or one quad (G24d base) compact fluorescent
lamp in the emergency mode.
3. Please ensure the electricity connections conform to the National Electrical Code and local regulations if applicable.
4. To avoid electric shock, please disconnect normal and emergency power supplies, and battery connector of the emergency ballast
before servicing.
5. This device is designed for factory or field installation in either the ballast channel or on top of indoor fixtures, except air handling,
heated air outlets, wet or hazardous locations. Do not install this device near gas or electric heaters or sealed and gasketed fixtures.
6. AC power source of 120 VAC or 277 VAC is required.
7. The battery is sealed, no-maintenance, and is not replaceable in the field. Please contact manufacturer for information on service.
Do not attempt to service the battery.
8. Do not use accessory equipment that is not recommended by manufacturer. Failure to do so may cause unsafe conditions.
Servicing should only be performed by qualified service personnel.
9. Do not use the product for other than its intended purpose.
LAMP COMPATIBILITY
• Compatible with most one-, two-, three-, and four-lamp electronic, standard and dimming AC ballasts.
• Operates the following lamps under emergency power:
2-Pin CFL (W)
No. of Lamps
1
13-26
Wattage
SAVE THESE INSTRUCTIONS

Advertisement

loading
Need help?

Need help?

Do you have a question about the KT-EMRG-650-CFL2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Keystone KT-EMRG-650-CFL2

  • Page 1 KT- EMRG- 650- C FL2 FLUORESCENT EMERGENCY BALLAST ASSEM BLY AND I NSTAL L AT I ON I NST RUCT I ONS WARNING: When using this lighting device, safety precautions should be followed at all times. READ THE INSTRUCTIONS BELOW CAREFULLY AND FOLLOW THEM FOR YOUR OWN SAFETY. 1.
  • Page 2 KT-EM RG-650-CF L 2 NOTE: All the branch circuit wiring has to be ready as well as an unswitched source of power before the fixture is installed. Confirm that the same branch circuit would be used for both the AC and emergency ballasts. CAUTION: Inverter connector has to be left open for preventing high voltage on output leads (red and yellow).
  • Page 3 KT-EM RG-650-CF L 2 M A I NT E NA NC E NOTE: Services should only be performed by qualified personnel. The emergency ballast should be checked periodically to confirm proper functionality and the following schedule is recommended by the manufacturer. 1.
  • Page 4 Lamp 1 Operates in Emergency Mode 1. B) FLEX Conduit Wiring Diagram 2. A) FLEX Conduit Wiring Diagram Keystone Technologies, LLC • P.O. Box 246, Ambler PA 19002 • Phone (800) 464-2680 • Fax (215) 628-4412 • www.keystoneballast.com Specifications subject to change. Revised 10-22-12...