Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment
can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
Page 1
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. WSHP-SVX021B-EN February 2025...
(HCFCs). Not all refrigerants containing these compounds bump cap, fall protection, electrical PPE and arc have the same potential impact to the environment. Trane flash clothing). ALWAYS refer to appropriate advocates the responsible handling of all refrigerants.
Follow EHS Policies! This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in Failure to follow instructions below could result in part without written permission. Trane reserves the right to death or serious injury.
Digit 17 — Coil Protection C = 9kW Electric Heat E = 12kW Electric Heat 0 = None G = 18kW Electric Heat K = 27kW Electric Heat N = 36kW Electric Heat P = 54kW Electric Heat R = 72kW Electric Heat WSHP-SVX021B-EN...
Page 7
7 = Insulated Copper-Water Coil 8 = Insulated Cupro-Nickel Water Coil Digit 42 — Freeze Protection A = 20°F Freezestat (For Glycol Loop) B = 35°F Freezestat (For Water Loop) Digit 43 — Special 0 = Standard Unit S = Special Unit WSHP-SVX021B-EN...
The nameplate for the compressors are located on the side provided in the building. Isolate all side panel service of the compressor. entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and water inlet/outlet) from the ambient air until the unit is ready for start-up. WSHP-SVX021B-EN...
2 minutes. diagnostic generated, if applicable, and a manual reset The system will continue to operate regardless of the status required to restart the compressor. of the filter switch. For further details, see Clogged Filter Switch - Installation Instructions (ACC-SVN238*-EN). WSHP-SVX021B-EN...
(BAYSENS073*) has been lowered approximately 25ºF below the cutout setpoint. This sensor features remote zone sensing and timed override with override cancellation. It is used with a Trane Digital Display Zone Sensor Integrated Comfort™ building management system. (BAYSENS135*) Integrated Comfort System LCD display provides heat, cool, auto, on, and off status.
The power supply circuit is not balanced with the proper phase sequence of L1, L2, L3 for the 3 conductors of a 3 phase circuit. – The line to line voltage is not between 180 volts and 633 volts. WSHP-SVX021B-EN...
Water limits Min. entering water temperature 45°F (7°C) 25°F (-4°C) Max. entering water temperature 120°F (49°C) 86°F (30°C) Max. water pressure 400 PSIG (2758 kPa) Water flow range 2.0 to 3.75 GPM/ton See performance tables for each model’s rated values. WSHP-SVX021B-EN...
3. If an element has detached from its ceramic insulator, carefully put it back into place. Precautionary Measures 4. Replace the heater elements if they present symptoms noted in the above Step 2.a and 2.c. • Avoid breathing fiberglass dust. WSHP-SVX021B-EN...
Page 14
Installation, repair, removal, or disposal should be performed by trained service personnel. A2L Work Procedures At all times, Trane’s maintenance and service guidelines shall be followed. If in doubt, contact Trane technical WARNING support for assistance. Risk of Fire — Flammable Refrigerant!
(Detection equipment shall be calibrated in a accelerate defrosting of components. Use only defrost and refrigerant-free area.) Ensure that the detector is not a cleaning procedures recommended by Trane. Do not potential source of ignition and is suitable for the refrigerant pierce or burn.
Part 2-40: Particular Requirements for Electrical Heat Verify the equipment refrigerant charge is in accordance Pumps, Air-Conditioners and Dehumidifiers, which defines with the room area limitation as described in Minimum safe design and use strategies for equipment using A2L Room Area Limits section. WSHP-SVX021B-EN...
Page 18
(TA) of all rooms connected by ducts, may • Units without airflow proving will disable electric heat be used instead of A. sources. Rooms connected by drop ceilings only are not considered Building fire and smoke systems may override this function. a single room. WSHP-SVX021B-EN...
Page 19
If the refrigerant sensor has a fault, is at the end of its life, The refrigerant sensors do not need service. Use only or is disconnected, the unit will initiate the mitigation manufacturer-approved sensors when replacement is actions. Mitigation actions may be verified by disconnecting required. the sensor. WSHP-SVX021B-EN...
15-1/4 [381] 11-1/4 9-5/8 [279] [244] 23-1/2 [597] UNIT CONTROL SERVICE GAUGE WIRE Ø2"(51mm) PORT ACCESS Ø1 3/8"(35mm) SERVICE GAUGE PORT ACCESS 42-3/8 4-7/8 Ø1-3/8" (35 MM) [1072] [117] UNIT POWER 7-5/8 WIRE Ø2"(51mm) [194] 69-7/8 [1778] 44-1/4 [1124] WSHP-SVX021B-EN...
Page 22
65 3/16” 213 MM 1568 MM 1656 MM 14” 16 3/4” 356 MM 425 MM 1 3/4” 44 MM 17 7/8” 454MM 40 7/8” 65 13/16” 1038 MM 1670 MM 41 7/16” 2” 1053 MM 51 MM 2” 51 MM WSHP-SVX021B-EN...
Page 29
470 MM 1” 2045 MM 25 MM 1” 25 MM 14” 356 MM 1 3/4” 34 3/8” 873 MM 44 MM 59 7/8” 1521 MM 84 1/2” 2146 MM 60 3/8” 1534 MM 2” 51 MM 2” 51 MM WSHP-SVX021B-EN...
Page 30
Figure 20. C.0 cabinet – swing diameter for hinged door(s) option 11" [279] 17-3/8" [443] 21-3/4" [554] 35" [890] Figure 21. A.0, B.0 and C.0 cabinets – standard economizer, manual or motorized fresh air damper ECONOMIZER HOOD BAROMETRIC RELIEF HOOD WSHP-SVX021B-EN...
Page 31
Figure 22. A.0, B.0 and C.0 cabinet – power exhaust with standard economizer ECONOMIZER HOOD POWER EXHAUST Dimension Cabinet inch inch inch inch 6 1/4 16 3/4 12 1/2 6 1/4 B.0 and C.0 6 3/8 20 1/2 16 3/4 7 1/4 WSHP-SVX021B-EN...
Page 32
Figure 23. A.0, B.0 and C.0 cabinet – power exhaust with low leak economizer ECONOMIZER HOOD POWER EXHAUST Dimension Cabinet inch inch inch inch 2 1/2 19 3/4 B.0 and C.0 2 1/2 19 3/4 29 1/4 33 1/2 WSHP-SVX021B-EN...
Page 34
Figure 27. D.0 and D.1 cabinets – unit clearance and roof opening CLEARANCE 36” 914 MM UNIT OUTLINE CLEARANCE 68” 1727 MM CLEARANCE FORM TOP OF UNIT 72” (1829 MM) ROOF 76 1/2” OPENING 1943 MM CLEARANCE 48” 1219 MM 81” 2057 MM FRONT OF UNIT CLEARANCE 60” 1524 MM WSHP-SVX021B-EN...
Page 35
1765 MM 14 1/16” 357 MM 2” 51 MM 81” 7 1/2” 2057 MM 191 MM 117 3/16” 2977 MM Figure 29. D.0 and D.1 cabinets – swing diameter for hinged door(s) option 30" 32" [754] [809] 36" [907] WSHP-SVX021B-EN...
Page 36
Figure 30. D.0 and D.1 cabinets – power exhaust 7.0" 4.4" 21.4" 22.7" clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency. Clearances illustrates the minimum operating and service clearances for either a single or multiple unit installation. These WSHP-SVX021B-EN...
Page 37
Weights are approximate. Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights to be added to unit weight, reference the following table. Figure 31. Center of gravity Compressor Ref Corner Note: Corner weights and center of gravity do not include accessories. WSHP-SVX021B-EN...
Provide concrete footings at each support Supply and return air openings as viewed from the rear of location with a “full perimeter” support structure or a slab the unit are shown in the following drawings. foundation for support. Refer to the weights information in WSHP-SVX021B-EN...
Page 41
ALTERNATE CONDENSATE CONNECTION Ø3/4-14 NPD 27-5/8 [702 ] 47-7/8 [1216] UNIT CONTROL WIRE Ø2"(51mm) 9-5/8 SERVICE GAUGE [244] PORT ACCESS Ø1-3/8 (35mm) 4-7/8 88-5/8 11-1/4 [124] [2252] [286] 9-1/4 UNIT POWER [235] WIRE Ø2" (52mm) 15-1/4 [386] 53-1/4 [1353] WSHP-SVX021B-EN...
If a Curb Accessory Kit is not used: Refer to unit nameplate and installation instructions • The ductwork can be attached directly to the factory- for proper clearances. provided flanges around the unit’s supply and return air WSHP-SVX021B-EN...
5. Test-lift the unit to ensure it is properly rigged and General Unit Requirements balanced, make any necessary rigging adjustments. The checklist listed below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing personnel WSHP-SVX021B-EN...
4. Slide the top bracket down the aluminium sensing tube. • For 12.5 to 25 ton units with standard or low leak economizers, also secure the tube to the top right side of the horizontal opening flange (right side WSHP-SVX021B-EN...
For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes. WSHP-SVX021B-EN...
Controls using 24 VAC Before installing any connecting wiring, refer to the Dimensions and Weights chapter for the electrical access WSHP-SVX021B-EN...
Controls using DC Analog Input/Outputs (Standard Low Voltage Multi conductor Wire) Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to the Dimensions and Weights chapter for the electrical access locations provided on the unit. WSHP-SVX021B-EN...
50° 10.0 19.96 averaging. 55° 12.8 17.47 • Example #3 illustrates the circuit required for this sensor. lists the temperature versus resistance 60° 15.6 15.33 coefficient for all sensors. 65° 18.3 13.4 70° 21.1 11.89 WSHP-SVX021B-EN...
Page 53
Table 9. Temperature vs. resistance (continued) Table 9. Temperature vs. resistance (continued) Temperature Temperature Nominal Resistance Nominal Resistance (kOhms) (kOhms) Degrees °F Degrees °C Degrees °F Degrees °C 75° 23.9 10.50 90° 32.2 7.330 80° 26.7 9.297 95° 35.0 6.528 85° 29.4 8.247 WSHP-SVX021B-EN...
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2 percent. WSHP-SVX021B-EN...
5. Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect The modes shown below can be initiated. Depending on switch or circuit protection switch and remove the the equipment configuration, the controller will energize the phase sequence indicator. WSHP-SVX021B-EN...
Page 56
Water Source Heat Pump Axiom™ Rooftop Application state once initiated. For detailed information on how each Guide (ACC-APG003*-EN). Service Test State is interpreted based on the equipment’s Figure 53. Symbio 700 service test mode WSHP-SVX021B-EN...
Close the main disconnect switch or circuit protector disconnect switch to the Off position or proceed to the switch that provides the supply power to the units next component start-up procedure. Remove terminal block or the unit mounted disconnect switch. electromechanical test mode connections (if applicable). WSHP-SVX021B-EN...
Make any necessary repairs. section(s) of the smoke detector Installation and • Verify that the electric heat system operates properly. Maintenance Instructions provided with the literature package for this unit. WSHP-SVX021B-EN...
Sulfates Less than 25 ppm personal illness or injury or severe equipment damage. Chlorides Less than 125 ppm 5. Pour the cleaning solution into the sprayer. If a high pressure sprayer is used: Carbon Dioxide Less than 75 ppm WSHP-SVX021B-EN...
- ok - low - low - ok - ok - low - low - ok - ok - low - low Note: Check and record the data requested above each month during the cooling season with the unit running. WSHP-SVX021B-EN...
LINE THERMOSTAT COMPRESSOR HIGH PRESSURE CONTROL DISCHARGE LINE HIGH THERMOSTAT PRESSURE CONTROL SERVICE COMPRESSOR VALVE 4 WAY VALVE SERVICE VALVE RTPF INDOOR COIL FILTER DRIER LIQUID LINE CHECK VALVE Note: 3 to 10 tons unit have only one compressor. WSHP-SVX021B-EN...
Page 66
COMPRESSOR HIGH PRESSURE CONTROL DISCHARGE LINE HIGH THERMOSTAT PRESSURE CONTROL SERVICE VALVE COMPRESSOR 4 WAY VALVE SERVICE MTW-9S VALVE VALVE RTPF INDOOR COIL FILTER DRIER LIQUID LINE CHECK VALVE Note: 3 to 10 tons unit have only one compressor. WSHP-SVX021B-EN...