Compact flow sensors

Advertisement

Quick Links

FS101...2UPN8 | ...2LI
Compact Flow Sensors
Instructions for Use

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FS101 2LI Series and is the answer not in the manual?

Questions and answers

Summary of Contents for turck FS101 2LI Series

  • Page 1 FS101…2UPN8 | …2LI Compact Flow Sensors Instructions for Use...
  • Page 2: Table Of Contents

    Protecting the sensor with a password.................  29 9.2.5 Parameters in the main menu .................... 29 9.2.6 Parameters in the OUT… (FS…2UPN8) submenu ............ 30 V02.00 | 2024/03 | 2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 3 12.1 Returning devices ...................... 36 13 Disposal..............................  36 14 Technical data...........................  37 15 Turck branches — contact data .................... 39 V02.00 | 2024/03 | 3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 4: About These Instructions

    If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V02.00 | 2024/03 | 4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 5: Notes On The Product

    Two seals (not on devices with NPT threads) Quick Start Guide Turck service Turck supports you in your projects – from the initial analysis right through to the commission- ing of your application. The Turck product database at www.turck.com offers you several soft- ware tools for programming, configuring or commissioning, as well as data sheets and CAD files in many export formats.
  • Page 6: For Your Safety

    The product is designed according to state of the art technology. Residual hazards, however, still exist. Observe the following safety instructions and warnings in order to prevent danger to persons and property. Turck accepts no liability for damage caused by failure to observe these safety instructions.
  • Page 7: Product Description

    [0.37] G 1/2 Ø 8.5 [0.33] Ø 7.3 [0.29] 14.5 [0.57] mm [Inch] Fig. 2: Dimensions — sensor with G1/2″ screw-in adapter V02.00 | 2024/03 | 7 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 8 NPT 3/4 Ø 8.5 [0.33] Ø 7.3 [0.29] 14.5 [0.57] mm [Inch] Fig. 5: Dimensions — sensor with NPT 3/4″ screw-in adapter V02.00 | 2024/03 | 8 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 9: Properties And Characteristics

    The greater the energy dissipation, the higher the flow speed or flow rate. V02.00 | 2024/03 | 9 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 10: Functions And Operating Modes

    V02.00 | 2024/03 | 10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 11: Output Functions - Switching Output

    SP2 switch-off point. If the process value decreases below the switch-off point SP2, the switching output becomes inactive. Switching state Process value Fig. 8: Two point mode V02.00 | 2024/03 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 12: Window Mode

    (SP2-Hyst). If the process value decreases below (SP2- Hyst), the switching output becomes inactive again. Switching state Hyst Hyst Window Process value Fig. 9: Window mode V02.00 | 2024/03 | 12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 13: Deltaflow Monitoring

    The auto detect function enables the device to automatically detect the pre-defined switching output behavior (PNP/NPN)when connected to an I/O module. The auto detect function is ac- tivated by default. V02.00 | 2024/03 | 13 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 14: Technical Accessories

    FS…, FP… product series; material: stainless steel 1.4571 (316Ti); process con- nection: G3/4" M18 x 1.5 11 37 14.5 G3/4“ V02.00 | 2024/03 | 14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 15 FS…, FP… product series; material: stainless steel 1.4571 (316Ti); process con- nection: N3/4" M18 x 1.5 11 37 N3/4“ 14.5 V02.00 | 2024/03 | 15 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 16: Installing

    If the medium flows in a horizontal direction and the flow channel is not completely filled with the medium: Mount the sensor e.g. below the flow. Fig. 12: Mounting below the flow V02.00 | 2024/03 | 16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 17 Prevent the tip of the probe rod coming into contact with the opposite side of the flow channel inner wall. V02.00 | 2024/03 | 17 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 18: Special Installation Instructions

    Teach in the teach-in values again if the sensor has been removed and reinstalled or the process connection has been disconnected. V02.00 | 2024/03 | 18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 19: Connecting

    PNP/NPN 2 out 2 3 L– out 1: Flow, IO-Link out 2: Temperature Fig. 17: Pin assignment Fig. 18: FS…-2UPN8-H1141 wiring diagram V02.00 | 2024/03 | 19 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 20: Commissioning

    The sensor operates in MAX/MIN mode by default. „ Perform MAX/MIN-Teach or Quick-Teach to adapt the sensor to application-specific con- ditions. V02.00 | 2024/03 | 20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 21: Operation

    NC: Switching point exceeded/within window (inactive output) Green Flow in % °C Green Temperature in °C °F Green Temperature in °F V02.00 | 2024/03 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 22: Displays

    Value < 0 % of the set flow range in MAX/MIN-Teach, value < 50 % of the set switching point in Quick-Teach, media temperature < -25 °C V02.00 | 2024/03 | 22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 23: Setting And Parameterization

    The auto detect function enables the device to automatically detect the pre-defined switching output behavior (PNP/NPN)when connected to an I/O module. The auto detect function is ac- tivated by default. V02.00 | 2024/03 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 24: Setting Via Touchpads

    The device returns to the standard display. Standard menu guidance — main menu Process value OUT1 OUT2 DISP Fig. 19: Main menu V02.00 | 2024/03 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 25 >3 s Current value AUTO Save value >3 s Current value OFF On Save value DOFF Fig. 20: OUT… submenu (FS…2UPN8) V02.00 | 2024/03 | 25 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 26 Current value DISU Save value >3 s Current value GrEN G1oU r1oU G2oU r2oU COLr Save value Fig. 22: Display submenu V02.00 | 2024/03 | 26 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 27 Save value PASS Process value Software version >3 s Current value FACT rEBO APPL UnDO Fig. 23: Extended functions submenu (EF) V02.00 | 2024/03 | 27 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 28: Setting Parameter Values Via The Touchpads

    LOC LED is yellow. The sensor is automatically locked if the touchpads of the device are not actuated for 1 min. V02.00 | 2024/03 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 29: Protecting The Sensor With A Password

    DISP for additional setting options Extended Functions submenu For additional setting options see the “Parameters in the EF submenu” table V02.00 | 2024/03 | 29 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 30: Parameters In The Out

    Default: 0.0 s DOFF Switch-off delay 0…60 s in increments of 0.1 s (0 = delay time not activated) Default: 0.0 s V02.00 | 2024/03 | 30 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 31: Parameters In The Disp Submenu (Display)

    Device restart (warm start) APPL Reset the application-specific data UnDO Reset the parameters to previous settings (last device start) V02.00 | 2024/03 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 32: 9.2.10 Quick-Teach

    Set SP Flow -1 % related to +1 % related to reference flow reference flow (max. 9 %) (max. 9 %) Process value Fig. 26: FS101 Quick-Teach V02.00 | 2024/03 | 32 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 33: 9.2.11 Max/Min Teach-In

    The switching points for single point mode, window mode and two point mode can be set for the MAX/MIN-Teach. By default, the switching point in single point mode is at a flow speed of 70 %. V02.00 | 2024/03 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 34: Setting Via Io-Link

    In SIO mode, the device operates in accordance with the most recent set- ting configured in IO-Link mode. V02.00 | 2024/03 | 34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 35: Troubleshooting

    If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type. V02.00 | 2024/03 | 35 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 36: Maintenance

    Disposal The devices must be disposed of properly and do not belong in the domestic waste. V02.00 | 2024/03 | 36 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 37: Technical Data

    ≤ 2 VDC Continuous current carrying capacity 250 mA of the DC switching output Overload protection Protection class Start-up delay 30 s V02.00 | 2024/03 | 37 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 38 LED display function for status of supply voltage, switching states, units and teach processes. Process display via 12-segment display MTTF 120 years acc. to SN 29500 (Ed. 99) 40 °C V02.00 | 2024/03 | 38 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 39: Turck Branches - Contact Data

    Via San Domenico 5, IT-20008 Bareggio (MI) www.turckbanner.it Japan TURCK Japan Corporation ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo www.turck.jp V02.00 | 2024/03 | 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 40 United Kingdom TURCK BANNER LIMITED Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex www.turckbanner.co.uk Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us V02.00 | 2024/03 | 40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
  • Page 41 Over 30 subsidiaries and 60 representations worldwide! 100030515 | 2024/03 100030515 www.turck.com...