Setting parameter values via touchpads .............. 22 Unlocking the device .................... 22 Locking the device...................... 22 Protecting the sensor with a password .............. 23 V01.00 | 2025/03 | 2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V01.00 | 2025/03 | 4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The delivery consists of the following: Pressure sensor Quick Start Guide Turck service Turck supports you in your projects — from the initial analysis right through to the commis- sioning of your application. The Turck product database at www.turck.com offers you several software tools for programming, configuring or commissioning, as well as data sheets and CAD files in many export formats.
The product is designed according to state of the art technology. Residual hazards, however, still exist. Observe the following safety instructions and warnings in order to prevent danger to persons and property. Turck accepts no liability for damage caused by failure to observe these safety instructions.
Operating principle The pressure sensors in the PS310 and PS311 series work with ceramic measuring cells, while the pressure sensors in the PS510 series work with fully welded metal measuring cells. As a result of the pressure acting on the ceramic or metal substrate, a signal that is proportional to the pressure is generated and processed electronically.
VDMA menus. In Legacy Mode, devices with the SSP label (Smart Sensor Profile) can be operated using the old menu guidance. V01.00 | 2025/03 | 10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
SP2 switch-off point. If the process value de- creases below the switch-off point SP2, the switching output becomes inactive. Switching state Process value Fig. 5: Two point mode V01.00 | 2025/03 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Fig. 7: Behavior of the switching output – Window function V01.00 | 2025/03 | 12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
I [ mA ] 1 1 Fig. 9: Behavior of the current output Fig. 10: Behavior of the current output (4… 20 mA) (0…20 mA) V01.00 | 2025/03 | 13 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
When connected to an I/O module, the device detects the pre-defined switching output beha- vior (PNP/NPN) or the analog output characteristic. The auto detect function is activated by de- fault. V01.00 | 2025/03 | 14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
5 [0.20] [0.10] mm [Inch] In addition to the above connection cables, Turck also offers other cable types for specific ap- plications with the correct terminals for the device. More information on this is available from the Turck product database at www.turck.de/products...
This means that the measured value displayed in a depressurized state is not zero. If the zero point has drifted, an offset value can be set via the COF parameter (see chapter “ [} 21]”). V01.00 | 2025/03 | 16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Set Compatible Device Mode in the IO-Link master so that the device changes to Legacy Mode. Alternatively, set Legacy Mode in the Extended Functions menu. V01.00 | 2025/03 | 18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
> 5 % of full scale below the measuring range No measurement data available PArA Incorrect user parameterization TEMP Device temperature outside the permissible range Unspecified error V01.00 | 2025/03 | 20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Fully lock user interface (display and touchpads locked) Lock local parameters (user interface parameters — parameters are displayed but cannot be changed) V01.00 | 2025/03 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
LOC LED is yellow. The sensor is automatically locked if the touchpads of the device are not actuated for 1 min. V01.00 | 2025/03 | 22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
In the EF menu, you can select Legacy Mode with its own menu guidance. Standard menu guidance — main menu Process value OUT1 OUT2 DISP Fig. 21: Main menu V01.00 | 2025/03 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 24
>3 s Current value AUTO Save value >3 s Current value OFF on Save value DOFF Fig. 22: Outputs (OUT…) submenu V01.00 | 2025/03 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 25
… GrEn r-CW COLr Save value >3 s Current value OFF on Save value CSP1 CSP2 Fig. 23: Display (DISP) submenu V01.00 | 2025/03 | 25 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Refer to the "Parameters in the DISP submenu" table for additional setting options Extended Functions submenu For additional setting options see the “Parameters in the EF sub- menu” table V01.00 | 2025/03 | 26 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Switching output: The output is deactivated in the event of a fault. Analog output: Fault value of the set function at output 2 (OUT2) V01.00 | 2025/03 | 27 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 28
End point of the Measured value at which the analog output signal has its end analog signal point Default: depends on pressure range V01.00 | 2025/03 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Virtual lower switching point at which the display changes color point (if display color G-CW or r-CW is selected) Default: depends on pressure range V01.00 | 2025/03 | 29 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Reset the minimum value memory: The lowest measured value is deleted. UnDO Reset the parameters to the previous settings (last device start) V01.00 | 2025/03 | 30 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
>3 s Current value 4…20 … rtio AUTO OUT2 Save value SP2/FH2/ASP rP2/FL2/AEP Fig. 25: Legacy Mode — main menu V01.00 | 2025/03 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 32
>3 s APPL FACT rEbo >3 s Software version VDMA Save value Fig. 26: Legacy Mode — extended functions (EF) submenu V01.00 | 2025/03 | 32 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Lower switching point for win- Lower switching point at which output 1 dow function changes its switching state ou1: Fno/Fnc V01.00 | 2025/03 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
0. This drift can be corrected. Setting range: -5 %…+5 % of the measuring range. V01.00 | 2025/03 | 34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 35
Display rotated by 180° diSu Measured value display 50-ms update time 200-ms update time 600-ms update time Display update deactivated V01.00 | 2025/03 | 35 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
In SIO mode, the device operates in accordance with the most recent set- ting configured in IO-Link mode. V01.00 | 2025/03 | 36 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If the malfunction persists, the device is faulty. In this case, decommission the device and re- place it with a new device of the same type. V01.00 | 2025/03 | 37 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Disposal The devices must be disposed of properly and do not belong in the domestic waste. V01.00 | 2025/03 | 38 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
24 bits (16-bit process values + 8-bit scale) Switching point information 3-bit Minimum cycle time 3 ms Function pin 4 IO-Link Function pin 2 Maximum cable length 20 m V01.00 | 2025/03 | 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 40
± 0.15 % of full ± 0.1 % of full scale/10 scale/10 scale/10 MTTF 100 years acc. to SN 29500 (ed. 99) 40 °C V01.00 | 2025/03 | 40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 42
± 0.15 % of full ± 0.1 % of full scale/10 scale/10 scale/10 MTTF 100 years acc. to SN 29500 (ed. 99) 40 °C V01.00 | 2025/03 | 42 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Via San Domenico 5, IT-20008 Bareggio (MI) www.turckbanner.it Japan TURCK Japan Corporation ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo www.turck.jp V01.00 | 2025/03 | 43 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 44
United Kingdom TURCK BANNER LIMITED Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex www.turckbanner.co.uk Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us V01.00 | 2025/03 | 44 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 45
Over 30 subsidiaries and 60 representations worldwide! 100048281 | 2025/03 100048281 www.turck.com...
Need help?
Do you have a question about the PS310 and is the answer not in the manual?
Questions and answers