No: IS-0521 – rev. 3 9/23
LVOS-0-10-PWM-DIN • Les Numéros de Catalogue • Los Números de Catálogo:
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
STATION
1
2
3
4
BUS
IR
SENS
COMMERCIAL DIMMERS
CLASS 2
50mA
2K21
CONTACT INPUTS
MAX
1
2
3
4
RED = 0-10
GREEN = PWM
LOW VOLTAGE OUTPUT STATION-0-10-PWM-DIN
1
2
3
4
5
INPUT
13.8-36
VDC
•
8, independent 0-10V low-voltage outputs
•
Outputs 1-4 can be configured as PWM or 0-10V
•
Manual control and LED status for all 8 LV outputs on front
•
High resolution performance when dimming
•
Communicates via Station Bus
•
Assembled in a 9 unit DIN case
•
Override switch for ON and OFF states of all loads
•
CE Certification / UL
Dimensions, HWD
Weight
LED Indicators
Ambient Operating Temperature
Relative Humidity
Cooling
Firmware
Manual Control
FreeRTOS
Compliance
No: IS-0521 – Rev. 3
STATION
SERIAL NUMBER
BUS
CLASS 2
OVERRIDE
5
6
7
8
STATUS
6
7
8
LVOS-0-10-PWM-DIN
0-10: 10VDC@100mA MAX
PWM: 12VDC@100mA MAX
FEATURES AND OPERATIONS OVERVIEW
RadioLink Keypad Station
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
The DIN Rail mounted Low Voltage Output Station (LVOS) is used for the
control and automation of LED and Fluorescent lighting loads requiring either
0-10V or pulse width modulation (PWM) for dimming control. The DIN LVOS
can control up to eight 0-10V loads. Unlike other LVOS products the DIN
LVOS does not have relays on-board for switching. It relies on an external
relay station (RS8-L-DIN) or module (MDR8CW301) to do high-voltage
switching. The dry contact inputs on the station can be used with motion
sensors, light sensors, optical switches, magnetic switches, and more. As part
of the Legrand Architectural Dimming lighting solution, it provides control of
lighting loads as well as inputs from dry contacts for lighting and automation.
SPECIFICATIONS
General
85.7mm x 157.2mm x 61.9mm (3.38" x 6.19" x 2.44")
237g (8.36oz)
Microprocessor status, configuration, loads
LED on loads 1-4: Red = 0-10 / GREEN = PWM
32-104°F (0-40° C)
Maximum 90%, non-condensing
Convection
Upgradeable via Station Bus
Overlay with control/status for each output
Real-time scheduling provided by FreeRTOS (www.freertos.org)
UKCA, UL, cUL, RoHS, CE, FCC, EN 55032, EN 55035, EN 61000-3-2,