www.acornfiresecurity.com Warranty Statement The GLT EXPORTS Optical Flame Detector described in this document is the property of GLT EXPORTS Inc. No part of the hardware, software or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of GLT EXPORTS Inc.
Certification Instructions This section refers only for intrinsically safe installation on model ZT-500EX.. The following instructions apply to equipment covered by certificate number: DNV 11 ATEX 02569X The equipment may be used in a hazardous area with flammable gasses and vapors with apparatus groups IIC and with temperature class T6.
Page 4
www.acornfiresecurity.com Definition of ATEX Marking 0575 II 2 G Ex d II C T6 DNV 11 ATEX 02569X (4)(5)(6) (7) (10) (11) (12) (1) CE Marking (2) Notified Body Number (0575: DNV) (3) European Commission mark for Ex-equipment (4) Equipment Group (II: Group for Offshore and surface Industries) (5) Equipment Category (Zone 1,2 / Zone 20, 21, 22) (6) G ( Gas ) (7) Type of protection (Ex d: Flameproof )
www.acornfiresecurity.com ABLE ONTENTS …………………………………………..……………………………1 Warranty Statement ………………………………………………………………………….... 1 Warnings ……..…………..………..…………..………. ……..………… 2 Certification Instruction Scope…………………………………………………………………………..7 1.1 P ................7 RODUCT VERVIEW 1.2 D OCUMENT VERVIEW…………………………………………………………………… Technical Description…………………………………………………………….. 8 2.1 P RINCIPLES PERATION………………………………………………… ………….. 2.2 M RS-485..................8 ODBUS 2.3 T ...................8 YPES AND ODELS...
Page 6
www.acornfiresecurity.com 7.4 F ................28 UNCTIONAL TESTING 7.4.1 Manual BIT Test................28 7.4.2 Testing with Fire Simulator............29 7.5 S ................29 AFETY RECAUTIONS Maintenance Instructions................30 8.1 S .......................30 COPE 8.2 M ........30 AINTENANCE NSTRUMENTATION AND ERSONNEL 8.3 P ..........30...
Page 7
IGURES Figure 1: ZT-500EX IR3 Flame Detector ............... 10 Figure 2: ZT-500EX IR3 Flame Detector Assembly - Outline Drawing - Cable output option..10 Figure 3: Horizontal and Vertical Fields of View............12 Figure 4: ZT-500EX LED ....................14 Figure 5: Detector and Tilt Mount Assembly ..............24 Figure 6: Tilt Mount TM-ST10 Assembly - Outline Drawing..........
1. Scope 1.1 Product Overview The GLT EXPORTS Model ZT-500EX Triple IR(IR3) Flame Detectors is designed to sense the occurrence of fire and flames and subsequently activate an alarm or an extinguishing system, directly or through a control circuit for maximum fire protection. They use the innovative technology of advanced digital signal processing to analyze the dynamic characteristics of fire.
2.2 Modbus RS-485 (to be specified later) 2.3 Types and Models ZT-500EX has a enclosure of aluminium or optionally stainless steel(ST 316L), The output is via either a connector (socket) or a cable tail (up to 1m long). www.acornfiresecurity.com...
Page 10
www.acornfiresecurity.com Model Definitions ZT-500 : IR3 EX : Ex/Metallic Enclosure P : non-Ex/Plastic Enclosure Cable Entries 1 x M20 Others Housing Aluminium ST, SUS316L Plastic(Polycarbonate)- Approvals ATEX Korean Type Approval - Non-certified www.acornfiresecurity.com...
Sensitivity Ranges: The detector has the four(4) modes of user selectable sensitivity range. Alarm response times for a “standard fire” at a specified range are shown hereunder. <ZT-500EX > Detection Range (m): nom. 50 meters Other fuels The detector will react to other types of fires as follows: Pan Fire Size: 1ft-sq(30cm x 30cm) Maximum Wind Speed: 6.5 ft/sec (2 m/sec)
www.acornfiresecurity.com 3.3 False Alarms Prevention The detector will not provide an alarm signal as a reaction to the radiation sources specified below. False alarm immunity is listed in Table 1. Notes: IAD = Immune at Any Distance. All sources are chopped from 0 to 20Hz. Table 2.
DIP SW setting Internal Power Fault or system Blinking 0 mA power out of range / Fault Normal Operation Solid 4 mA Fire Detection(Warning) Solid 16 mA Fire confirmed All LEDs blinking simultaneously 20 mA Figure 4: ZT-500EX LED www.acornfiresecurity.com...
www.acornfiresecurity.com 4.2 Output Signals The detector provides the following outputs: Alarm relay Fault relay 4-20mA current output RS-485 communication (optional) The detector can be in one of the following states. The detector is functioning normally. Normal: The detector performs a Built In Test. BIT<Option>: Fire detected –...
Page 18
www.acornfiresecurity.com or performing a manual BIT). Latching affects the ALARM RELAY, 4-20mA output, the ALARM LED. www.acornfiresecurity.com...
B. Water and dust tight IP 67 per EN 60529 C. Electrical connection (two options) 1. 1 X M20 (ISO) 2. Others D. Dimensions ZT-500EX : 83(Dia)mm × 126(L)mm (w/o optional Tilt Mount) E. Weight Detector (aluminium) :appr. 1.1kg(1.4kg with Ex cable gland/2-meter cable) Detector (staineless steel) :appr.
www.acornfiresecurity.com 5.3 Environmental Specifications -40ºC to +75ºC (-40ºF to +167ºF) Operating temperature range: -40ºC to +75ºC (-40ºF to +167ºF) Storage temperature range: 0 to 95% RH non-condensing Humidity range: Electromagnetic Compatibility (EMC): This product is in conformance with EMC directive 89/336/EC. Radiated Emission EN61000-6-3 Conducted Emission EN61000-6-3 Radiated Immunity EN61000-4-3...
www.acornfiresecurity.com 6. Installation Instructions 6.1 Scope The detectors are a self-contained Optical Flame Detectors designed to operate as a stand- alone units, directly connected to alarm systems or automatic fire extinguishing systems. The detectors can be part of a more complex system where many detectors and other devices are integrated through a common control unit.
www.acornfiresecurity.com 6.3 Preparation for Installation Installation should comply with local codes or something as applicable to flame detectors. The detectors can be installed with the use of general-purpose common tools and equipment. 6.3.1 Checking Detector Verify the appropriate Purchase Order. Record the Part No. and the Serial No of the detectors and the installation date in the appropriate Log-book.
www.acornfiresecurity.com 6.4 Installation The detector can be mounted on the wall preferably with the optional Tilt Mount. The Tilt Mount enables the detector to be rotated in all direction as the installer intends to do.. 6.4.1 Tilt Mount Kit -The detector can be mounted with one of two Tilt Mount Kits ;TM-ST10(Stainless) and TM-AL10(Aluminium) to be optionally selected by customers when ordering the detectors.
www.acornfiresecurity.com 6.5 Detector Mounting A. Choose the wiring configuration according to Appendix A. B. Connect the wire to the required PIN on the connector or choose the required color on the cable, according to your wiring diagram. C. Connect the grounding wire to general screw outside the detector, (Figs.2 and 3).
www.acornfiresecurity.com 7. Operating Instructions 7.1 Scope The following instructions are designed to obtain optimal performance from the detector over its life cycle. 7.2 Power-Up Apply power and wait approximately 20 seconds for the automatic self-test of the detector. Note: Applying power initiates the following sequence: - All LEDs blink respectively.
www.acornfiresecurity.com 7.4.2 Testing with Fire Simulator (to be released later) To be additionally instructed later. 7.5 Safety Precautions After Powering-up, the detector requires hardly any attention in order to function properly, but the following should be noted: Follow the instructions in the manual and refer to the drawings and specifications issued by the manufacturer.
www.acornfiresecurity.com 8. Maintenance Instructions 8.1 Scope This Section deals with preventive maintenance, describes possible faults in detector operation and indicates corrective measures. Ignoring these instructions may cause problems with the detector and may invalidate the warranty. Whenever a unit requires service, please contact the manufacturer or its authorized distributor for assistance.
www.acornfiresecurity.com 8.6 Troubleshooting 8.6.1 Fault Indication Check power supply for correct voltage, polarity and wiring. Check detector window and reflector for cleanliness. If necessary clean the window as indicated in paragraph 8.3 and repeat the test. Disconnect the power supply to the system and check the detector's internal wiring.
www.acornfiresecurity.com RS-485 Communication Network For more details, consult the factory. Detector Last Detector Control Panel Power + ○ Black Supply - ○ Gray RS485 ○ COMPUTER Pink PORT ○ Figure 10: RS-485 Networking www.acornfiresecurity.com...
www.acornfiresecurity.com DETECTOR CONTROL PANEL Power 24V(+) Black GND(Return) Max. 800Ω AT 30VDC Blue 4-20mA Figure 11: 4-20mA Wiring (Non-isolated “ SOURCE” Version) Notes: The 4-20mA will be measured between CN1 PIN 7 or blue wire and CN2 PIN 2 or black wire. www.acornfiresecurity.com...
www.acornfiresecurity.com Control Panel Detector Detector Last Detector Power + ○ Black Supply - ○ White Alarm ○ Green Loop ○ Alarm ○ Loop ○ Figure 14: Typical Wiring For 4-Wire Control Panel Notes: For EOL resistor value see Controller Manual (ex: 10k ohms) The color wire refers to the color of the cable output option.
Appendix B: Ordering Information Please define the requested model according to 1.1.5 by filling in the appropriate squares below. Model Definitions ZT-500EX EX : Ex/Metallic Enclosure P : non-Ex/Plastic Enclosure Cable Entries 1 x M20 Housing Aluminium ST, SUS316L...
Page 39
www.acornfiresecurity.com Orders may be sent to: GLT Exports Ltd. 72/78, Morfa Road, Swansea, SA1 2EN, United Kingdom. Tel) +44 (0) 1792 455175 Fax)+44 (0) 1792 455176 For additional details or assistance, please contact GLT Exports Ltd. 72/78, Morfa Road, Swansea, SA1 2EN, United Kingdom. Web-Site: www.zetaalarmsystems.com Tel) +44 (0) 1792 455175 Fax)+44 (0) 1792 455176...
Need help?
Do you have a question about the ZT-500EX and is the answer not in the manual?
Questions and answers