Delta AC Motor Drives VFD-XXXE Getting Started Manual page 3

Delta electronics ac motor drives quick start manual

Advertisement

Control System
Frequency Setting Resolution 0.01Hz
Output Frequency Resolution
Torque Characteristics
Overload Endurance
Skip Frequency
Accel/Decel Time
Stall Prevention Level
DC Brake
Regenerated Brake Torque
V/f Pattern
Keypad
Frequency
Setting
External Signal
Operation
Keypad
Setting
External Signal
Signal
Multi-function Input Signal
Multi-function Output
Indication
Analog Output Signal
Alarm Output Contact
Operation Functions
Protection Functions
Display Keypad (optional)
Built-in Brake Chopper
Built-in EMI Filter
Enclosure Rating
Pollution Degree
Installation Location
Ambient Temperature
General Specifications
SPWM(Sinusoidal Pulse Width Modulation) control (V/f or sensorless vector
control)
0.01Hz
Including the auto-torque/auto-slip compensation; starting torque can be 150%
at 3.0Hz
150% of rated current for 1 minute
Three zones, setting range 0.1-600Hz
0.1 to 600 seconds (2 Independent settings for Accel/Decel time)
Setting 20 to 250% of rated current
Operation frequency 0.1-600.0Hz, output 0-100% rated current
Start time 0-60 seconds, stop time 0-60 seconds
Approx. 20% (up to 125% possible with optional brake resistor or externally
mounted brake unit, 1-15hp (0.75-11kW) models have brake chopper built-in)
4-point adjustable V/f pattern
Setting by
Potentiometer-5kΩ/0.5W, 0 to +10VDC, 4 to 20mA, RS-485 interface; Multi-
function Inputs 3 to 9 (15 steps, Jog, up/down)
Set by RUNand STOP
2 wires/3 wires ((MI1, MI2, MI3)), JOG operation, RS-485 serial interface
(MODBUS), programmable logic controller
Multi-step selection 0 to 15, Jog, accel/decel inhibit, 2 accel/decel switches,
counter, , external Base Block, ACI/AVI selections, driver reset, UP/DOWN key
settings, NPN/PNP input selection
AC drive operating, frequency attained, zero speed, Base Block, fault indication,
overheat alarm, emergency stop and status selections of input terminals
Output frequency/current
Contact will be On when drive malfunctions (1 Form C/change-over contact and
1 open collector output) for standard type)
Built-in PLC(NOT for CANopen models), AVR, accel/decel S-Curve, over-
voltage/over-current stall prevention, 5 fault records, reverse inhibition,
momentary power loss restart, DC brake, auto torque/slip compensation, auto
tuning, adjustable carrier frequency, output frequency limits, parameter
lock/reset, vector control, PID control, external counter, MODBUS
communication, abnormal reset, abnormal re-start, power-saving, fan control,
sleep/wake frequency, 1st/2nd frequency source selections, 1st/2nd frequency
source combination, NPN/PNP selection, parameters for motor 0 to motor 3,
DEB and OOB (Out Of Balance Detection)(for washing machine)
Over voltage, over current, under voltage, external fault, overload, ground fault,
overheating, electronic thermal, IGBT short circuit, PTC
6-key, 7-segment LED with 4-digit, 5 status LEDs, master frequency, output
frequency, output current, custom units, parameter values for setup and lock,
faults, RUN, STOP, RESET, FWD/REV, PLC
VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T,
VFD007E21T/23T/43T, VFD015E23T/43T, VFD007E11A, VFD015E21A,
VFD022E21A/23A/43A, VFD037E23A/43A VFD007E11C, VFD015E21C,
VFD022E21C/23C/43C, VFD037E23C/43C, VFD055E23A/43A,
VFD075E23A/43A, VFD110E43A, VFD055E23C/43C, VFD075E23C/43C,
VFD110E43C
For 230V 1-phase and 460V 3-phase models.
IP20
2
Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust
o
o
o
-10
C to 50
C (40
C for side-by-side mounting) Non-Condensing and not frozen
English- 3