  • Page 1 CMC-EIP01 EtherNet/IP Communication Card for VFD-C2000 Operation Manual CMC-0206120-01...
  • Page 3 AC motor drive is a delicate electrical and electronic product. For the safety of operator and the mechanical equipment, please allow professional electrical mechanics to do the trial run and adjust parameters for you. Should there be any questions, please consult your local Delta distributors. Our professional staff will be happy to help you.
  • Page 4 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 EtherNet/IP Communication Protocol ....................14 6.1 EtherNet/IP Specifications Supported ..................14 6.2 EtherNet/IP Communication Parameter ..................15 6.3 Services and Objects Supported ....................15 6.4 CIP Comman Status Code ......................15 6.5 Error Code for Monitor Request ....................15 Software Setting ...........................
  • Page 5: Specification

    SCADA (Supervisory Control And Data Acquisition) software or human machine interface. Sending e-mail, IP filter, on-line monitoring and webpage functions are also provided by CMC-EIP01. In addition, by auto MDI/MDI-X function, no jumper cable is required when using the network cable.
  • Page 6 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Product Profile and Outline Dimension Unit: mm [inch] Parts Screw fixing hole RJ-45 connection port Positioning hole POWER indicator AC motor drive connection port Fool-proof groove LINK indicator CMC-EIP01 Operation Manual...
  • Page 7 Incorrect default setting ECiF Serious internal error ECEF Ethernet connection error ECto Communication timeout between CMC-EIP01 and VFD-C2000 Checksum error in the communication between CMC-EIP01 and ECCS VFD-C2000 ECrF Reset CMC-EIP01 to default setting ECo1 Exceeds max. number of communications in EtherNet/IP...
  • Page 8 Conduct the setup by the keypad on AC motor different networks and drive. blocked by firewall Able to open Check if the network setting for CMC-EIP01 is CMC-EIP01 correct. For the Intranet setting in your company, setup page but Incorrect network setting in please consult your IT staff.
  • Page 9: Installation And Wiring

    EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Installation and Wiring In this section, we illustrate how to connect CMC-EIP01 to VFD-C2000 and the network. How to Install How to connect CMC-EIP01 to VFD-C2000 series AC motor drive: Switch off the power supply of VFD-C2000.
  • Page 10 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 How to Connect to Network Connect CMC-EIP01 to the Ethernet hub by CAT-5e pair twisted wire. Since CMC-EIP01 has auto MDI/MDIX function, so CAT-5e does not require jumper cable. Network structure of PC and CMC-EIP01:...
  • Page 11 Model code of CMC-EIP01 = H’0204 BR#1: Firmware Version Explanations: Displaying the firmware version of CMC-EIP01 in hex form, e.g. H’0100 indicates version V1.00. BR#2: Release Date of the Version Explanations: Displaying the release date of the version in hex form, e.g. H’0101 indicates January 1.
  • Page 12 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 4.3 Alarm Register (AL) ( AL MODBUS Address Base = 0x0200) bit in each AL Attribute Function Explanation bit 15 = 1 Function enabled bit 15 Function enabling flag bit 15 = 0 Function disabled...
  • Page 13 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 4.7 Explanations on MW MW#0: Monitor Function Explanations: Default: H’8010 MW#1~MW#32: Station No. and Device Address to be Monitored Explanations: The low byte in odd MW records the station No. of device to be monitored, and high byte records the number of data to be monitored.
  • Page 14 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 4.8 Definitions of Parameter Address for VFD-C2000 Communication Protocol Parameter content Address Definition Parameter set in GG is the parameter group; nn is the parameter number. GGnnH VFD-C2000 Ex: Parameter 04-01 is indicated by 0401H.
  • Page 15 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Parameter content Address Definition Commands to 2002H bit2 1: External interruption (B.B) = ON VFD-C2000 bit3~5 Reserved Monitor VFD-C2000 2100H Error code: Refer to parameter 06-17 ~ 06-22 status 2119H bit0 1: Forward running command...
  • Page 16 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Address No. on keypad Definition IP Configuration 2520H 09-75 0 – Static 1 – DHCP 2521H 09-76 IP Address 1 2522H 09-77 IP Address 2 2523H 09-78 IP Address 3 2524H 09-79 IP Address 4...
  • Page 17 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 EtherNet/IP Communication Parameter Input buffer register: In Assembly Instance = 101, Width = 16 bits, Size = 16 Output buffer register: Out Assembly Instance = 100, Width = 16 bits, Size = 3 Configuration: Instance = 102, Width = 8 bits, Size = 0 Services and Objects Supported See Appendix A.
  • Page 18: Software Setting

    “Ethernet” as the communication type. Next, you can search by “Search” or “IP search” function. CMC-EIP01 is set up by UDP port 20006; therefore, be aware of relevant settings of the firewall. The PC is connected to VFD-C2000 with CMC-EIP01 through cable or hub:...
  • Page 19 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Setting up Communication and Searching for Modules in DCISoft Communication Setting 1. Open DCISoft on the PC and select “Tools” => “Communication Setting”. 2. Select “Ethernet” for the communication setting. CMC-EIP01 Operation Manual...
  • Page 20 Search 1. Click the “Search” icon in DCISoft to search for all Delta’s Ethernet products on the network by search function. The modules found are displayed in the left-hand side column, and the device list of all modules is displayed on the right-hand side column.
  • Page 21 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 3. The setup page for CMC-EIP01. Search for Designated Module 1. Click “Communication Card” in the left-hand side column. Right click the mouse and select “Configure” to search for the designated module. CMC-EIP01 Operation Manual...
  • Page 22 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 2. Select CMC-EIP01 to be searched. Click “OK” and DCISoft will start to search for the existing CMC-EIP01 cards on the network. 3. Device list of the existing CMC-EIP01. CMC-EIP01 Operation Manual...
  • Page 23 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Search for Designated IP 1. Set the communication type to “Ethernet” and enter the designated IP address in the address column. Click “OK”. 2. Click “IP Search” icon to start searching for the designated IP.
  • Page 24: Device Name

    The basics 1. Device Name: There can be many CMC-EIP01 cards on the network. Therefore, you can set up a device name for the module to be controlled to identify it when you need to search for it. 2. Network Setup: (1) IP Configuration: There are 2 types of IP configuration: Static IP and DHCP.
  • Page 25: Timer Setting

    3. Timer Setting For setting up the network keep alive time (Unit: second; Range: 10 ~ 65,535; Default: 30s). If the idling time of the connection is longer than the keep alive time, CMC-EIP01 will disconnect the idling connection. CMC-EIP01 Operation Manual...
  • Page 26 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Network Settings The first step for all the equipment to connect to the network is to have its own IP (Internet Protocol) address. The IP address is like a number for every device on the network to be identified Setting up static IP of the PC 1.
  • Page 27 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 3. Click “Internet Protocol (TCP/IP)”. 4. Enter “192.168.0.1” into IP address. Click “OK” to complete the IP address setting of the CMC-EIP01 Operation Manual...
  • Page 28: Smtp Server

    EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Alarm Setting E-Mail is the abbreviation of electronic mail which transmits mails in a network. CMC-EIP01 has e-mail functions, and the user is able to self-define triggering conditions. When the condition to trigger e-mail is true, CMC-EIP01 will send an e-mail to the e-mail address set by the user.
  • Page 29 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 CMC-EIP01 executes “Free Run”, “Quick Stop” and “Stop” to VFD-C2000. (5) Mail address The recipient address of the e-mail to be sent (max. 63 English characters) Note: To correctly send out e-mails, there has to be an SMTP server on the network. When we sendout an e-mail, the mail will be sent to the SMTP server first, and the server will further send the mail to the designated address.
  • Page 30 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Parameter List The VFD-C2000 parameter numbers, Modbus addresses, register names, units, present values, default values, minimum values, maximum values, and attributes are listed for group 0~gourp 11 in the parameter list. Check a parameter on the parameter page to display it on the monitoring page and monitor it.
  • Page 31 The values of the VFD-C2000 parameters in the monitoring table can be constantly read, and saved in CMC-EIP01. If the values are read through the network, the flash memory will respond directly, enhancing the reading efficiency. In addition, this page can also be used to monitor the present values set in the parameters of VFD-C2000 on-line.
  • Page 32: Password Setup

    EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Security After you set up all the functions and network environment for CMC-EIP01, to prevent the set values from being modified, you can set up passwords to lock the settings in CMC-EIP01. Setting up password 1.
  • Page 33 Note: If you reset CMC-EIP01 to default setting by VFD-C2000 keypad, you can do it whether CMC-EIP01 is locked by a password or not, and please do not shut down the power supply during the process. CMC-EIP01 Operation Manual...
  • Page 34: Application Examples

    Ethernet Steps (1) IP of Ethernet module DVPEN01-SL: 192.168.1.10 (2) IP of CMC-EIP01: 192.168.1.15. Station No.: 2 (3) Delta PLC DVP-SV sends out MODBUS command “06020620011770” to VFD-C2000 through DVPEN01-SL. 1. The connection: 2. PLC program: CMC-EIP01 Operation Manual...
  • Page 35 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Program explanations: 1. Write the IP of CMC-EIP01 into CR#117 (「1.15」= H’010F) and CR#118 (「192.168」= H’C0A8) of DVPEN01-SL. 2. Set CR#111 = 1 and use 8-bit mode. 3. Write the length of command into CR#119.
  • Page 36 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 2. Open DCISoft’s “Search” function (if in different LAN, search by designated IP) to search for CMC-EIP01. 3. Enter “Parameter List” page and check the VFD-C2000 parameters to be monitored. 4. Assume you want to monitor parameters 00-01, 01-01, 02-01, 03-01, 04-01, 05-01 and 06-01, check them on the parameter list.
  • Page 37 (3) Clear password in CMC-EIP01. 1. See 7.1 for the connection and communication settings. 2. Open the setup pages for CMC-EIP01 and switch to “Security” page. 3. Check “Modify” and enter password “1234” into the “Password” and “Confirm Password” columns. Click “Apply” to save the password.
  • Page 38 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 4. Reopen the setup page, and all the settings are now locked by password. Enter the password and click “OK”. 5. Enter the password to unlock the settings and modify parameters. If you close the setup page now, the settings will remain being locked.
  • Page 39 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 6. To clear the password, leave the password columns blank and click “Apply”. 7. After the password is cleared, you can then modify parameters. CMC-EIP01 Operation Manual...
  • Page 40 CMC-EIP01. 1. See 7.1 for the connection and communication settings. 2. Open the setup page for CMC-EIP01 and switch to “IP Filter” page. 3. Check “Enable IP Filter”. Enter “192.168.0.7” in No. 1 Begin IP Address and “192.168.0.7” in End IP Address.
  • Page 41 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 4. Enter “172.16.0.1” in No.2 Begin IP Address and “172.16.0.254” in End IP Address. Click “Apply”, then only equipment within the allowed IP range can be connected. CMC-EIP01 Operation Manual...
  • Page 42 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 E-Mail When the value in Address (Hex) = Value (Dec), CMC-EIP01 will make VFD-C2000 execute Application the command and send e-mail to notify the administrator. Steps (1) IP of SMTP Server: 172.16.144.122 (2) Administrator’s e-mail address: test@sample.com (3) When H’2103 = 60, execute “STOP”...
  • Page 43 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 3. Set up e-mail and trigger event. Enter “172.16.144.122” in SMTP Server. Enter “2103” in Address (Hex) in the first row, “=” in Condition, “60” in Value (Dec), “Stop” in Command and “test@sample.com” in Mail Address. Click “Apply” to complete the alarm setting.
  • Page 44 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Keypad Operation (1) Application Setting up network parameter by keypad Steps (1) Set Static IP to ”192.168.1.16”, Netmask ”255.255.255.0” and Gateway ”192.168.1.1”. (2) Set up IP to DHCP. Static 1. Enter the corresponding value in every address by keypad according to the table below.
  • Page 45 (2) Set Static IP to ”192.168.1.16”, Netmask ”255.255.255.0” and Gateway ”192.168.1.1”. 1. See 7.8 for how to set up password in CMC-EIP01. 2. Re-open the setup page, and it is locked by the password. No settings can be modified, nor returning to default settings.
  • Page 46 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 3. Enter the corresponding value in every address by keypad according to the table below. Press “Enter” on the keypad to complete the setup. Address Value Function 09-75 Set the IP to “Static” 09-76...
  • Page 47 (2) The password is lost. Return to default settings by keypad. 1. See 7.8 for how to set up password in CMC-EIP01. 2. Re-open the setup page, and it is locked by the password. No settings can be modified, nor returning to default settings.
  • Page 48 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 3. Enter “1” into address 09-90 by keypad. 4. Re-open the setup page in DCISoft. The password is now cleared and all settings returned to default ones. CMC-EIP01 Operation Manual...
  • Page 49 (3) Set VFD-C2000 to Stop: Move “1” to CMC_EIP01: O.Data[0] 11. Download the program and switch PLC 1769-L32E to be in on-line mode. 12. Set CMC-EIP01 to be the card controlling VFD-C2000. Refer to 3.3 for how to set. CMC-EIP01 Operation Manual...
  • Page 50: Appendix A: Ethernet/Ip Services And Objects

    EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 13. Switch on ”SW1” and set the frequency of VFD-C2000 to 60Hz. 14. Switch on ”SW2” for VFD-C2000 to Run. Swich on “SW3” for VFD-C2000 to Stop. Appendix A: EtherNet/IP Services and Objects A.1 Objects Supported...
  • Page 51 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 A.3.3. Common Services: Implemented for Service Service name Description of service code Class Instance 0x05 Reset Resets device settings Sends back attribute of designated 0x0E Get Attribute Single object A.4 Message Router Object (Class Code: 0x02) A.4.1.
  • Page 52 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 A.7 BR Object (Class Code: 0x64) A.7.1. Instance Code: Instance Description 0x01 Corresponds to BR0: Model name 0x02 Corresponds to BR1: Firmware version 0x03 Corresponds to BR2: Release date of the version 0x07 Corresponds to BR6: VFD-C2000 station No.
  • Page 53 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 A.9.2. Instance Attributes: Attribute Access Data Name Description of attribute rule ttype Refer to 4.6 for corresponding value. 0x03 Get / Set Data UINT Instance Code = 0x02~0x21 Get/Set Others Get Only A.9.3. Common Services:...
  • Page 54 EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01 Configuration Control Attribute Bits Name Description 0 = The device shall use the interface configuration values previously stored in non-volatile memory. Startup 1 = The device shall obtain its interface configuration values via BOOTP.