User Manual Hybrid Inverter Applicable models H1PL-1J3K-EU H1PL-1J3.6K-EU H1PL-1J4.6K-EU H1PL-1J5K-EU H1PL-1J6K-EU Applicable System Single phase system Version 1.2, Release Date: 12,2024...
1 . Introduction User Manual 1 .1 Product Description The Haier H1PL Series is designed for residential hybrid systems, which can work with batteries to optimize self-consumption. The unit can operate in both off-grid and on-grid modes. This manual covers the Haier H1PL Series model listed below: H1PL-1J3K-EU, H1PL-1J3.6K-EU, H1PL-1J4.6K-EU, H1PL-1J5K-EU, H1PL-1J6K-EU...
1 . Introduction User Manual 1 .2 Packaging Please ensure that the following items are included in the packaging with your machine: Back plate x1 Fastening screw x2 Inverter x1 AC grid terminal x1 Battery Cable x2 (optional) RJ45 connector x8 AC backup terminal x1 DC connector x2 RS485 Meter cable x1...
2 . Safety & Warning User Manual 2 .1 Safety The following types of safety instructions and general information appear in this document as described below: DANGER: “ Danger” indicates a hazardous situation which if not avoided, will result in death or serious injury.
Page 6
Operations below must be accomplished by licensed technician or Haier authorized person. WARNING: Operator must put on the technicians’ gloves during the whole process in case of any electrical hazards. WARNING: AC BACKUP Port of Haier H1PL Series is not allowed to connect to the grid.
2 . Safety & Warning User Manual WARNING: The Haier H1PL Series does not support parallel in three phase operation on the AC-BACKUP port. The inverter support parallel in single phase and support generator. (Only for 5/6kW) × × ×...
User Manual 3 .1 Intelligent LED Indicators There are five indicators on the The Haier Inverter (Battery, Power, WiFi, Ethernet and Bluetooth) which indicate the working status of the inverter. The Bluetooth Antenna or WiFi datalogger shall be installed at the Antenna/COM port of the hybrid inverter before local debugging.
4 . Installation User Manual 4 .1 Select a Location for the Inverter To select a location for the inverter, the following criteria should be considered: Exposure to direct sunlight may cause output power derating. It is recommended to avoid installing the inverter in direct sunlight. It is recommended that the inverter is installed in a cooler ambient which doesn't exceed 104℉/40℃.
Page 10
Nothing should be stored on or placed against the inverter. NOTE: When installing the inverter inside the Haier HQBK -00-1P distribution module, the above minimum distance requirement does not apply as long as the clearance for the distribution module is respected. Please refer to the HA1L manual for further details.
4 . Installation User Manual 4 .2 Mounting the Inverter Dimensions of mounting bracket: 4 07.5 unit:mm Φ6.8 3 58 3 22 3 -OB11*6.8 Figure 4.3 Inverter wall mounting Once a suitable location has be found accordingly to 4.1 using figure 4.3 mount the wall bracket to the wall.
4 . Installation User Manual ≤ 15° Vertical Backward Install vertically (+/- 5°) or tilted backward (≤15°). Don't mount inverter on the tilted forward wall. Don't mount inverter on the horizontal. 4 .3 PE Cable Installation An external ground connection is provided at the right side of inverter. Prepare OT terminals: M4.
4 . Installation User Manual 4 .4 PV Input Cable Installation Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter. Before connection, please make sure the polarity of the output voltage of PV array matches the“DC+”and“DC-”symbols.
Page 14
4 . Installation User Manual 3 . Pass the stripped DC cable through the nut and waterproof rubber ring. Positive terminal Negative terminal Figure 4.8 . Connect the wire part of the DC cable to the metal DC terminal and crimp it with a special DC terminal crimping tool.
Page 15
4 . Installation User Manual 6 . Measure PV voltage of DC input with multimeter, verify DC input cable polarity. Figure 4.11 7 . Connect the wired DC terminal to the inverter as shown in the figure, and a slight "...
4 . Installation User Manual 4 .5 Battery Power Cable Installation NOTE: 1 . The positive wiring (the angle of the limit tip is 90°) is connected to the positive socket, and the negative wiring (the angle of the limit tip is 180°) is connected to the negative socket;...
4 . Installation User Manual 4 .6 AC Cable Installation There are two AC terminals and the assembly steps for both are the same. Take out the AC connector parts from the packaging. Describe Numerical value Cable diameter 10~14mm Traverse cross sectional area 8~10mm²...
Page 18
4 . Installation User Manual 4 . Push Housing into Body. Click Figure 4.17 5 . Insert Seal and Clamp Finger into socket ,then tighten the nut , torque 4+/-0.5N·m. Figure 4.18 . The same installation for both cable end plug and socket connectors. .
4 . Installation User Manual 4 .7 Communication Cable Installation 4 .7.1 Protective Cover for Communication Ports Figure 4.20 Inverter in the package is with a protective cover assembled to protect the communication ports. Step 1. Use Phillips screwdriver to take out the 4 screws on the cover. Step 2.
Page 20
4 . Installation User Manual 4 .7.2 Communication Port Definition Meter RS485 DRM DO/DI BMS Reserved Figure 4.21 Port Function Used for CAN communication between inverter and Lithium battery BMS. Used for RS485 communication between inverter and the smart Meter meter.
Page 21
4 . Installation User Manual 4 .7.3 BMS Port Connection Take out the pre-made CAN cable from the package and connect one end to battery CAN port and then connect another end to the inverter BMS port. Cable Length: 3 meters. Figure 4.22 NOTE: Before connecting CAN cable with the battery, please check whether the...
Page 22
.7.5 DRM Port Connection (Optional) .7.5.1 For Remote Shutdown Function Haier inverters support remote shutdown function to remotely control the inverter to power on and off through logic signals. The DRM port is provided with an RJ45 terminal and its Pin5 and Pin6 can be used for remote shutdown function.
Page 23
If a 3rd party external device or controller needs to communicate with the inverter, the RS485 port can be used. Modbus RTU protocol is supported by Haier inverters. To acquire latest protocol document, please contact Haier local service team or Haier sales.
2 . One Smart Meter can be used with only one hybrid inverter. The Haier H1PL Series inverter is able to connected Acrel meters or Eastron meters to fuilfill the control logic of the self-consumption mode, export power control, monitoring, etc.
Page 25
4 . Installation User Manual 4 .8.1 Single phase meter installation...
4 . Installation User Manual 4 .9 Inverter Remote Monitoring Connection The inverter can be remotely monitored via WiFi, LAN or 4G. The USB type COM port at the bottom of the inverter can connect to different kinds of data loggers to realize the remote monitoring on cloud platform. To install data loggers, please refer to corresponding user manuals of data loggers.
4 . Installation User Manual 4 .10 Parallel System Wiring NOTE: Only 4.6/5/6kW can be parallel, 3/3.6kW cannot. L Wire Inverter 1 (Master) N Wire PE Wire CAN Wire/Parallel Wire DC Wire Inverter 2 (Slave) Inverter 3 (Slave) Grid Battery Backup Grid Figure 4.29...
Page 28
4 . Installation User Manual NOTE: Only 4.6/5/6kW can be parallel, 3/3.6kW cannot. L Wire N Wire PE Wire CAN Wire/Parallel Wire DC Wire Phase A (Master) Phase B (Slave) Phase C (Slave) Grid Battery Backup Grid Load Load Figure 4.30 When multiple inverters are connecting in parallel, ONLY same model (same power rating) can be used.
5 . Commissioning User Manual 5 .1 Preparation Ensure all the devices are accessible for operation, maintenance and service. Check and confirm that the inverter is firmly installed. Space for ventilation is sufficient for one inverter or multiple inverters. Nothing is left on the top of the inverter or battery module. Inverter and accessories are correctly connected.
5 . Commissioning & Shutdown User Manual NOTE: This sequence is critical. Set the parameters of the inverter before the data logger distribution network. You cannot set the inverter parameters if the network distribution is performed first. In this situation, you need to clean the inverter data. (For details, refer to Figure 5.14).
Page 31
5 . Commissioning & Shutdown User Manual Step 2: Installer to log in to the APP. Entering the account and password, then check the “Privacy Policy" and "User Agreement," then click "Log In”. Figure 5.2 Step 3: Installer to create the Plant. Click the “Plant”...
Page 32
1 . Click the “Add device” to enter the device list webpage. Click the inverter icon below the “ Add Manually” to choose the “Haier (H1PL,H3PH)” and add it. . Choose the consistent SN code with inverter (displays the inverter icon) to enter the Control Validation passage.
Page 33
5 . Commissioning & Shutdown User Manual NOTE: 1 . Please ensure your phone has Bluetooth/GPS turned on and the app has been authorized to use Bluetooth. . Click the inverter icon on the Nearby Device Page to add an inverter to set parameters.
Page 34
5 . Commissioning & Shutdown User Manual Step 5.1: Set the inverter Date and Time. You can set it to follow the time on your mobile phone. Step 5.2: Set the battery model. It must be based on the battery model that is actually connected to the inverter. If there is no battery connected for the moment, please select “No Battery”...
Page 35
5 . Commissioning & Shutdown User Manual Step 5.4: Set the grid code setting. Please select the grid code based on the local grid network requirements. Figure 5.7 Step 5.5: Set the work mode setting. There are four work modes that can be set. Work mode1: Self-Use Mode (default ) Work mode2: Feed in Priority Mode Work mode3: Peak-shaving Mode...
Page 36
5 . Commissioning & Shutdown User Manual Work mode1: Self-Use Mode (default) The recommended setting is Self-Use Mode. This mode can maximize the use of PV power generation for household electricity or store it in batteries and use it for household electricity. If you need to manually control the battery charging and discharging with respect to time, please use the Time of Use switch and the following set points.
Page 37
5 . Commissioning & Shutdown User Manual Work mode2: Feed in Priority Mode This mode can preferentially send power to the grid when the load is met, used in areas with a subsidy for power to the grid. If you need to manually control the battery charging and discharging with respect to time, please use the Time of Use switch and the following set points.
Page 38
5 . Commissioning & Shutdown User Manual Work mode3: Peak-shaving Mode This mode is typically used when the local grid company charges the electricity price based on the peak power consumption of the system. Customers can use this peak shaving mode to avoid the peak consumption power at the grid connection point.
Page 39
5 . Commissioning & Shutdown User Manual Work mode4: Off-Grid Mode This mode is only used for pure off-grid and is not recommended for standard storage systems. Note that if this mode is enabled in the grid-connected state, the working logic of the machine will be confused, and the "Off-grid"...
5 . Commissioning & Shutdown User Manual Figure 5.13...
Page 41
5 . Commissioning & Shutdown User Manual If the network distribution of the datalogger is performed first, the inverter parameters cannot be set. In this situation, you need to clean the datalogger of the device list. Step1: Enter the added plant; Step2: Click the datalogger in the device list;...
Page 42
5 . Commissioning & Shutdown User Manual App Interface Structure The interface structure of APP is shown as follows. Check system data, equipment information, and alarms on Overview and Parameters interfacce. Set system equipment parameters on Setting interface. Current Alarm Alarm Today Yield of PV Historical Alarm...
Page 43
5 . Commissioning & Shutdown User Manual Energy flow diagram The home page can display the working state, Today Yield of PV, Today Imported/ Exported of Grid, Today Charged/Discharged of battery and Today Consumption of household electricity. Figure 5.16...
Page 44
5 . Commissioning & Shutdown User Manual Information The Inverter page can display basic information such as historical yield, today PV input power, Inverter SN, rated power, model number, DSP/HMI firmware version, grid code and communication connection. The advanced information is authorized by the installer. Figure 5.17...
Page 45
5 . Commissioning & Shutdown User Manual The Battery page can display charging&Discharging power, battery SOC, Charging& Discharging Energy, Other Parameters(From BMS), Other Parameters(From inverter). Figure 5.18...
Page 46
5 . Commissioning & Shutdown User Manual The grid page can display Energy Imported&Exported Grid Data and Meter data. Figure 5.19...
Page 47
5 . Commissioning & Shutdown User Manual The Load page can display the load power consumption in the grid side and the backup side. Figure 5.20...
Page 48
5 . Commissioning & Shutdown User Manual Settings Mode Setting The interface can display the current work mode, Self-Use/Feed in Priority/Backup/ Off-Grid. Please refer to page 33-36 for specific introduction. Figure 5.21 Grid Code Setting Please select the Grid code you need. Figure 5.22...
Page 49
5 . Commissioning & Shutdown User Manual Battery Setting Battery Model: select the battery model to be connected. Battery Over-voltage/Under-voltage Protection: fill in the appropriate data to protect the battery and extend its life. Over-discharge SOC: when the battery is discharged to the over-discharge SOC, the battery will not discharge actively.(Due to the internal current conduction, there is a small self- consumption power, if not charged for a long time, the SOC will slowly continue to decline.) Force-charge SOC: due to the battery power consumption, when the over-discharge SOC...
Page 50
5 . Commissioning & Shutdown User Manual Backup Setting Backup Port Enabling Setting: please turn on it if the Backup port is needed. Figure 5.25...
5 . Commissioning & Shutdown User Manual Alarm The Alarm page can display the Current Alarm(unsolved faults) and the Historical Alarm (resolved faults). Figure 5.26 5 .4 Shutdown procedure Step 1. Turn off the AC circuit breaker at the grid-connection point. Step 2.
6 . Maintenance User Manual Haier H1PL inverter does not require any regular maintenance. However, cleaning the heatsink will help the inverter dissipate heat and increase the lifetime of inverter. The dirt on the inverter can be cleaned with a soft brush.
7 . Troubleshooting User Manual Message Name Information Description Troubleshooting Suggestion 1. Turn on the device in the ON/OFF Setting. Control device to shutdown 1 . Confirm whether the inverter is connected to an external EPM/meter to prevent reverse current. .
Page 54
7 . Troubleshooting User Manual Message Name Information Description Troubleshooting Suggestion 1 . Grid side fault, restart the device. Surge Alarm On-site grid surge If it is still not eliminated, please contact the manufacturer's customer service. Grid voltage exceeds the OV-G-V01 upper voltage range Grid voltage exceeds the...
Page 55
7 . Troubleshooting User Manual Message Name Information Description Troubleshooting Suggestion . Confirm whether the battery model selection Wrong battery brand selection BatName-FAIL is consistent with the actual one. . Can failure is a failure of communication between inverter and battery. Check cable conditions.
Page 56
7 . Troubleshooting User Manual Message Name Information Description Troubleshooting Suggestion . Confirm that the grid is abnormal. . Confirm that the AC cable connection is not DCInj-FAULT The current DC component abnormal. (1037 DATA:0000) exceeds the limit . Restart the system, confirm that the fault continues.
Page 57
Please keep ready with you the following information before contacting us. . Serial number of Haier Singles Phase Inverter; . The distributor/dealer of Haier Singles Phase Inverter (if available); . Installation date. . The description of the problem together with necessary information, pictures, attachment.
8 . Specifications User Manual H1PL-1J3K-EU H1PL-1J3.6K-EU Technical Data Input DC (PV side) Recommended max. PV power 4800W 5700W Max. input voltage 600V Rated voltage 330V Start-up voltage MPPT voltage range 90-520V Full load MPPT voltage range 105-520V 125-520V Max. input current 16A/16A Max.
Page 59
8 . Specifications User Manual H1PL-1J3K-EU H1PL-1J3.6K-EU Technical Data Output AC(Grid side) Rated output power 3.6kW Max. apparent output power 3kVA 3.6kVA Operation phase 1/N/PE Rated grid voltage 220 V/230 V The grid voltage range 187-253 V Rated grid frequency...
Page 60
8 . Specifications User Manual H1PL-1J3K-EU H1PL-1J3.6K-EU Technical Data General data Dimensions(W/H/D) 405*480*205mm Weight 24.18kg Topology High frequency insolation (for battery) -25℃~+60℃ Operation temperature range Ingress protection IP66 Cooling concept Natural convection Max.operation altitude 4000m G98 or G99, VDE-AR-N 4105 / VDE V 0124,...
Page 61
8 . Specifications User Manual H1PL-1J4.6K-EU H1PL-1J5K-EU Technical Data Input DC (PV side) Recommended max. PV power 7000W 8000W Max. input voltage 600V Rated voltage 330V Start-up voltage MPPT voltage range 90-520V Full load MPPT voltage range 160-520V 175-520V Max. input current 16A/16A Max.
Page 62
8 . Specifications User Manual H1PL-1J4.6K-EU H1PL-1J5K-EU Technical Data Output AC(Grid side) Rated output power 4.6kW Max. apparent output power 4.6kVA 5kVA Operation phase 1/N/PE Rated grid voltage 220 V/230 V The grid voltage range 187-253 V Rated grid frequency 50 Hz/60 Hz AC grid frequency range 45-55 Hz/55-65 Hz...
Page 63
8 . Specifications User Manual H1PL-1J4.6K-EU H1PL-1J5K-EU Technical Data General data Dimensions(W/H/D) 405*480*205mm Weight 24.18kg Topology High frequency insolation (for battery) -25℃~+60℃ Operation temperature range Ingress protection IP66 Cooling concept Natural convection Max.operation altitude 4000m G98 or G99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1, VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 / UNE 206007-1, Grid connection standard...
Page 64
8 . Specifications User Manual Technical Data H1PL-1J6K-EU Input DC (PV side) Recommended max. PV power 9600W Max. input voltage 600V Rated voltage 330V Start-up voltage MPPT voltage range 90-520V Full load MPPT voltage range 210-520V Max. input current 16A/16A 24A/24A Max.
Page 65
8 . Specifications User Manual Technical Data H1PL-1J6K-EU Output AC(Grid side) Rated output power Max. apparent output power 6kVA Operation phase 1/N/PE Rated grid voltage 220 V/230 V The grid voltage range 187-253 V Rated grid frequency 50 Hz/60 Hz AC grid frequency range 45-55 Hz/55-65 Hz Rated grid output current...
Page 66
8 . Specifications Qingdao Nahui Energy Technology Co., LTD. User Manual Technical Data H1PL-1J6K-EU General data Dimensions(W/H/D) 405*480*205mm Weight 24.2kg Topology High frequency insolation (for battery) -25℃~+60℃ Operation temperature range Ingress protection IP66 Cooling concept Natural convection Max.operation altitude 4000m G98 or G99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1, VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 / UNE 206007-1,...
Warranty” before you start installing the product. You can download them from our website: https://eur.nahui- newenergy.com/ In addition to what is specified in this manual, to make sure your products are covered by the “Haier Energy Products Terms of Warranty”, please make sure the following instructions are always respected.
Page 68
Qingdao Nahui Energy Technology Co., LTD. Address: Room303,Entrance1,No.4Building, Lan Gu Entrepreneurship Center Phase 1,No.7,Keji Yilu Road, Aoshanwei Sub district Office,Jimo District Office,Jimo District,Qingdao,Shandong Copyright Declaration All rights to the content of this manual are owned by Qingdao Nahui EnergyTechnology Co., Ltd. (hereinafter called as 'Nahui Energy').