AIR CONDITIONER
2-unit multi-split type
DESIGN & TECHNICAL MANUAL
INDOOR
ASHG07–14KMTB
ASHH07–14KMCG-B
ASHG07–14KMCC
ASHH07–14KMCH-B
ASHG07–14KMCE
ASHG07–14KMCF
ASHH07–14KMCG
ASHH07–14KMCH
OUTDOOR
AGHG09–14KVCA
AUXG07–14KVLA
ARXG07–14KSLAP ARXG07–14KLLAP ARXH12–14KMTAP
ASHG07–14KETA
ASHG07–14KETA-B
ASHG07–14KETE-B
ASHG07–14KETF-B
ASHG07–14KGTB
ASHG07–14KETE
ASHG07–14KGTE
ASHG07–14KETF
ASHG07–14KGTF
ASHH07–14KGTG
ASHH07–14KGTH
AOHG14KBTA2
AOHG18KBTA2
ASHH05-12KNCA
ASHH05–12KNCH
DR_MU021EG_15
2024.12.16

Advertisement

loading
Need help?

Need help?

Do you have a question about the GENERAL ARXG07-14KSLAP and is the answer not in the manual?

Questions and answers

Summary of Contents for Fujitsu GENERAL ARXG07-14KSLAP

  • Page 1 AIR CONDITIONER 2-unit multi-split type DESIGN & TECHNICAL MANUAL INDOOR AUXG07–14KVLA ARXG07–14KSLAP ARXG07–14KLLAP ARXH12–14KMTAP ASHG07–14KMTB ASHH07–14KMCG-B ASHG07–14KETA ASHG07–14KGTB ASHH05-12KNCA ASHG07–14KMCC ASHH07–14KMCH-B ASHG07–14KETE ASHG07–14KGTE ASHH05–12KNCH ASHG07–14KMCE ASHG07–14KETF ASHG07–14KGTF ASHG07–14KMCF ASHG07–14KETA-B ASHH07–14KGTG ASHH07–14KMCG ASHG07–14KETE-B ASHH07–14KGTH ASHH07–14KMCH ASHG07–14KETF-B OUTDOOR AGHG09–14KVCA AOHG14KBTA2 AOHG18KBTA2 DR_MU021EG_15 2024.12.16...
  • Page 2 • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of FUJITSU GENERAL LIMITED in the United States, other countries or both. “AIRSTAGE Mobile” is a trademark of FUJITSU GENERAL LIMITED. Android and Google Play are trademarks of Google LLC.
  • Page 3 CONTENTS Part 1. INDOOR UNIT................1 1. Model lineup ....................2 1-1. Connectable indoor units to each outdoor unit..............5 1-2. Indoor unit connection patterns..................6 2. Specifications....................7 2-1. Compact cassette type ....................7 2-2. Mini duct type........................8 2-3. Slim duct type ........................9 2-4. Medium static pressure duct type ..................10 2-5.
  • Page 4 CONTENTS (continued) 8-4. Medium static pressure duct type ................123 8-5. Wall mounted type .......................124 8-6. Floor type........................135 9. Noise level curve..................136 9-1. Compact cassette type ....................136 9-2. Mini duct type.......................138 9-3. Slim duct type ......................140 9-4. Medium static pressure duct type ................142 9-5.
  • Page 5 CONTENTS (continued) 15-5.Indoor unit (setting by simple remote controller) ............312 15-6.Function details......................319 15-7.Wired remote controller (UTY-RNNGM) ..............329 15-8.Wired remote controller (UTY-RVNGM)..............331 15-9.Wired remote controller (UTY-RLRG) .................332 15-10.Wired remote controller (UTY-RNRGZ*) ..............332 15-11.Simple remote controller (UTY-RSNGM) ..............333 16. Accessories ....................334 16-1.Compact cassette type ....................334 16-2.Mini duct type......................335 16-3.Slim duct type ......................336 16-4.Medium static pressure duct type ................337...
  • Page 6 CONTENTS (continued) Part 2. OUTDOOR UNIT (2 UNITS TYPE) ........365 1. Specifications....................366 2. Dimensions....................368 2-1. Model: AOHG14KBTA2 ....................368 2-2. Model: AOHG18KBTA2 ....................369 3. Installation space ..................370 3-1. Models: AOHG14KBTA2 and AOHG18KBTA2............370 4. Refrigerant circuit ..................373 4-1. Model: AOHG14KBTA2 ....................373 4-2. Model: AOHG18KBTA2 ....................374 5.
  • Page 7 Part 1. INDOOR UNIT COMPACT CASSETTE TYPE: AUXG07–14KVLA MINI DUCT TYPE: SLIM DUCT TYPE: ARXG07–14KSLAP ARXG07–14KLLAP MEDIUM STATIC PRESSURE DUCT TYPE: ARXH12–14KMTAP WALL MOUNTED TYPE: ASHG07–14KMTB ASHG07–14KETA ASHG07–14KGTB ASHH05-12KNCA ASHG07–14KMCC ASHG07–14KETE ASHG07–14KGTE ASHH05–12KNCH ASHG07–14KMCE ASHG07–14KETF ASHG07–14KGTF ASHG07–14KMCF ASHG07–14KETA-B ASHH07–14KGTG ASHH07–14KMCG ASHG07–14KETE-B ASHH07–14KGTH ASHH07–14KMCG-B...
  • Page 8 1. Model lineup Indoor unit (other than wall-mounted type) AUXG07KVLA ARXG07KSLAP ARXG07KLLAP AUXG09KVLA ARXG09KSLAP ARXG09KLLAP AUXG12KVLA ARXG12KSLAP ARXG12KLLAP AUXG14KVLA ARXG14KSLAP ARXG14KLLAP ARXH12KMTAP AGHG09KVCA ARXH14KMTAP AGHG12KVCA AGHG14KVCA - 2 - 1. Model lineup...
  • Page 9 Indoor unit (wall-mounted type) ASHG07KMTB ASHH07KMCG-B ASHG07KETA ASHG07KETA-B ASHG09KMTB ASHH09KMCG-B ASHG09KETA ASHG09KETA-B ASHG12KMTB ASHH12KMCG-B ASHG12KETA ASHG12KETA-B ASHG14KMTB ASHH14KMCG-B ASHG14KETA ASHG14KETA-B ASHG07KMCC ASHH07KMCH-B ASHG07KETE ASHG07KETE-B ASHG09KMCC ASHH09KMCH-B ASHG09KETE ASHG09KETE-B ASHG12KMCC ASHH12KMCH-B ASHG12KETE ASHG12KETE-B ASHG14KMCC ASHH14KMCH-B ASHG14KETE ASHG14KETE-B ASHG07KMCE ASHG07KETF ASHG07KETF-B ASHG09KMCE ASHG09KETF ASHG09KETF-B ASHG12KMCE...
  • Page 10 Outdoor unit AOHG14KBTA2 AOHG18KBTA2 - 4 - 1. Model lineup...
  • Page 11 1-1. Connectable indoor units to each outdoor unit ●: Connectable / -: Not connectable Compact cassette Mini duct Outdoor unit AUXG07–14KVLA ARXG07–14KSLAP Btu class kW class AOHG14KBTA2 ● ● ● — ● ● ● — AOHG18KBTA2 ● ● ● ● ●...
  • Page 12 1-2. Indoor unit connection patterns ¢ 2 units AOHG14KBTA2 Combination no. Unit 1 Unit 2 Total AOHG18KBTA2 Combination no. Unit 1 Unit 2 Total Numbers in column Unit 1, 2, and Total indicate the indoor unit capacities as follows: 5: 5,000 Btu/h, 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..- 6 - 1-2.
  • Page 13 2. Specifications 2-1. Compact cassette type Model name AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.19 0.22 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 14 2-2. Mini duct type Model name ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.29 0.33 0.38 0.58 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET...
  • Page 15 2-3. Slim duct type Model name ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.33 0.30 0.35 0.51 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 16 2-4. Medium static pressure duct type Model name ARXH12KMTAP ARXH14KMTAP Power supply 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.34 0.49 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Sirocco fan ×...
  • Page 17 2-5. Wall mounted type Model name ASHG07KMTB ASHG09KMTB ASHG12KMTB ASHG14KMTB Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 18 Model name ASHG07KMCC ASHG09KMCC ASHG12KMCC ASHG14KMCC Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 19 Model name ASHG07KMCE ASHG09KMCE ASHG12KMCE ASHG14KMCE Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 20 Model name ASHG07KMCF ASHG09KMCF ASHG12KMCF ASHG14KMCF Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 21 ASHH07KMCG ASHH09KMCG ASHH12KMCG ASHH14KMCG Model name ASHH07KMCG-B ASHH09KMCG-B ASHH12KMCG-B ASHH14KMCG-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 22 ASHH07KMCH ASHH09KMCH ASHH12KMCH ASHH14KMCH Model name ASHH07KMCH-B ASHH09KMCH-B ASHH12KMCH-B ASHH14KMCH-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 23 ASHG07KETA ASHG09KETA ASHG12KETA ASHG14KETA Model name ASHG07KETA-B ASHG09KETA-B ASHG12KETA-B ASHG14KETA-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 24 ASHG07KETE ASHG09KETE ASHG12KETE ASHG14KETE Model name ASHG07KETE-B ASHG09KETE-B ASHG12KETE-B ASHG14KETE-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 25 ASHG07KETF ASHG09KETF ASHG12KETF ASHG14KETF Model name ASHG07KETF-B ASHG09KETF-B ASHG12KETF-B ASHG14KETF-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 26 Model name ASHG07KGTB ASHG09KGTB ASHG12KGTB ASHG14KGTB Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 27 Model name ASHG07KGTE ASHG09KGTE ASHG12KGTE ASHG14KGTE Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 28 Model name ASHG07KGTF ASHG09KGTF ASHG12KGTF ASHG14KGTF Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 29 Model name ASHH07KGTG ASHH09KGTG ASHH12KGTG ASHH14KGTG Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 30 Model name ASHH07KGTH ASHH09KGTH ASHH12KGTH ASHH14KGTH Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 31 Model name ASHH05KNCA ASHH07KNCA ASHH09KNCA ASHH12KNCA Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.11 0.12 0.19 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 32 Model name ASHH05KNCH ASHH07KNCH ASHH09KNCH ASHH12KNCH Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.11 0.12 0.19 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 33 2-6. Floor type Model name AGHG09KVCA AGHG12KVCA AGHG14KVCA Power supply 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.18 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 34 After installation of mobile app, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the wireless LAN control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 28 - 3-1. System requirement 3.
  • Page 35 4. Dimensions 4-1. Compact cassette type ¢ Models: AUXG07–14KVLA Unit: mm Grid type grille Hanging bolt position IR receiver Drain hose View A Ceiling Control Box View B View C - 29 - 4-1. Compact cassette type 4. Dimensions...
  • Page 36  Installation space requirement Provide enough clearance for product safety. Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) 07 and 09 models 12 or larger models Standard 2,700...
  • Page 37 4-2. Mini duct type ¢ Models: ARXG07–14KSLAP Unit: mm Rear view Drain port P 100 × 6 = 600 Side view (L) Top view Side view (R) Front view Bottom view - 31 - 4-2. Mini duct type 4. Dimensions...
  • Page 38  Installation space requirement Provide sufficient installation space for product safety. Unit: mm Strong and durable ceiling Indoor unit Left Right side side or more* or more *: 400 or more when drain from drain pipe • When intaking air from back: •...
  • Page 39 4-3. Slim duct type ¢ Models: ARXG07–14KLLAP Unit: mm Rear view (Drain hose) Drain port 100 x 6 = 600 Side view (R) Side view (L) Top view Front view Bottom view - 33 - 4-3. Slim duct type 4. Dimensions...
  • Page 40  Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: mm 300 or more Strong and durable ceiling 20 or more Indoor unit Left Right side side 20 or more Service access Ceiling or more or more Floor ...
  • Page 41 4-4. Medium static pressure duct type ¢ Models: ARXH12–14KMTAP Unit: mm Rear view P100 × 5 = 500 Hole: × Φ4 PCD*160 Φ125 Φ4.5 P100 × 5 = 500 *: PCD (Pitch Circle Diameter) Side view (L) Top view Side view (R) Front view - 35 - 4-4.
  • Page 42  Installation space requirement Provide enough clearance for product safety. NOTE: The detailed component shape depends on the model. Unit: mm 20 or more 300 or more 20 or more* Ceiling 2,500 or more (When no ceiling) Floor *: According to the distance between the ceiling and the unit, the construction plan of the mainte- nance access differs.
  • Page 43 Unit: mm • Distance between the ceiling and the unit is from 20 to 300: Choose one of these methods to set up the maintenance access. Pattern A Maintenance access Control box 100 to 200 Pattern B 1,300 or more Control box Bottom view - 37 -...
  • Page 44 4-5. Wall mounted type ¢ Models: ASHG07–14KMTB and ASHG07–14KMCC Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 38 - 4-5. Wall mounted type 4. Dimensions...
  • Page 45  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more A: Install so that the flare connection part is outdoors. - 39 - 4-5.
  • Page 46 ¢ Models: ASHG07–14KMCE, ASHG07–14KMCF, ASHH07– 14KMCG, ASHH07–14KMCG-B, and ASHH07–14KMCH-B Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 40 - 4-5. Wall mounted type 4. Dimensions...
  • Page 47  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 41 - 4-5.
  • Page 48 ¢ Models: ASHH07–14KMCH Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 42 - 4-5. Wall mounted type 4. Dimensions...
  • Page 49  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 43 - 4-5.
  • Page 50 ¢ Models: ASHG07–14KETA, ASHG07–14KETA-B, ASHG07– 14KETE, ASHG07–14KETE-B, ASHG07–14KETF, and ASHG07– 14KETF-B Unit: mm (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 44 - 4-5. Wall mounted type 4. Dimensions...
  • Page 51  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 40 or more Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 52 ¢ Models: ASHG07–14KGTB Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 46 - 4-5. Wall mounted type 4. Dimensions...
  • Page 53  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more A: Install so that the flare connection part is outdoors. - 47 - 4-5.
  • Page 54 ¢ Models: ASHG07–14KGTE, ASHG07–14KGTF, ASHH07– 14KGTG , and ASHH07–14KGTH Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 48 - 4-5. Wall mounted type 4. Dimensions...
  • Page 55  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 49 - 4-5.
  • Page 56 ¢ Models: ASHH05-12KNCA and ASHH05–12KNCH Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 50 - 4-5. Wall mounted type 4. Dimensions...
  • Page 57  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 30 or more 40 or more Wall hook bracket 107 or more Outline of the indoor unit 163 or more 1,500 or more - 51 - 4-5. Wall mounted type 4.
  • Page 58 ¢ Pipe exit length from the rear (for KMCG, KMCG-B, KMCH, KMCH-B, KGTG, KGTH, KNCA, and KNCH) Design the system considering the length of the pipes or hose exiting from the rear of the indoor unit. NOTE: Detailed shapes of the indoor unit and the tip of each pipe or hose may vary depending on the model.
  • Page 59 4-6. Floor type ¢ Models: AGHG09–14KVCA Unit: mm Side view Front view - 53 - 4-6. Floor type 4. Dimensions...
  • Page 60  Installation space Unit: mm 100 or more 80 or more 80 or more 50 or more 150 or below from the floor PROHIBITED Grating WARNING • The appliance shall be installed, operated and stored in a room with a floor area larger than X Minimum room area Amount of refrigerant charge M (kg)
  • Page 61 5. Wiring diagrams 5-1. Compact cassette type ¢ Models: AUXG07–14KVLA - 55 - 5-1. Compact cassette type 5. Wiring diagrams...
  • Page 62 5-2. Mini duct type and Slim duct type ¢ Models: ARXG07–14KSLAP and ARXG07–14KLLAP WLAN adapter, Converter etc. (Option) - 56 - 5-2. Mini duct type and Slim duct type 5. Wiring diagrams...
  • Page 63 5-3. Medium static pressure duct type ¢ Models: ARXH12–14KMTAP - 57 - 5-3. Medium static pressure duct type 5. Wiring diagrams...
  • Page 64 5-4. Wall mounted type ¢ Models: ASHG07–14KMTB - 58 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 65 ¢ Models: ASHG07–14KMCC - 59 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 66 ¢ Models: ASHG07–14KMCE, ASHH07–14KMCH, and ASHH07– 14KMCH-B - 60 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 67 ¢ Models: ASHG07–14KMCF, ASHH07–14KMCG, and ASHH07– 14KMCG-B - 61 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 68 ¢ Models: ASHG07–14KETA and ASHG07–14KETA-B - 62 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 69 ¢ Models: ASHG07–14KETE and ASHG07–14KETE-B - 63 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 70 ¢ Models: ASHG07–14KETF and ASHG07–14KETF-B - 64 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 71 ¢ Models: ASHG07–14KGTB - 65 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 72 ¢ Models: ASHG07–14KGTE and ASHH07–14KGTH - 66 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 73 ¢ Models: ASHG07–14KGTF and ASHH07–14KGTG - 67 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 74 ¢ Models: ASHH05-12KNCA - 68 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 75 ¢ Models: ASHH05–12KNCH - 69 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 76 5-5. Floor type ¢ Models: AGHG09–14KVCA - 70 - 5-5. Floor type 5. Wiring diagrams...
  • Page 77 6. Air velocity and temperature distributions 6-1. Compact cassette type ¢ Models: AUXG07–09KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Horizontal louver: Up 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25...
  • Page 78 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data...
  • Page 79 ¢ Model: AUXG12KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Horizontal louver: Up 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25 0.25 4 (m) - 73 - 6-1.
  • Page 80 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data...
  • Page 81 ¢ Model: AUXG14KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 Top view Horizontal louver: Up 0.25 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25 0.25 4 (m) - 75 - 6-1.
  • Page 82 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH...
  • Page 83 6-2. Mini duct type ¢ Model: ARXG07KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up...
  • Page 84 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 78 - 6-2.
  • Page 85 ¢ Model: ARXG09KSLAP NOTE: This data is measured after installing optional Auto Louver Grille Kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 86 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 80 - 6-2.
  • Page 87 ¢ Model: ARXG12KSLAP NOTE: This data is measured after installing optional Auto Louver Grille Kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 88 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 82 - 6-2.
  • Page 89 ¢ Model: ARXG14KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 90 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 84 - 6-2.
  • Page 91 6-3. Slim duct type ¢ Model: ARXG07KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up...
  • Page 92 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 86 - 6-3.
  • Page 93 ¢ Model: ARXG09KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 94 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 88 - 6-3.
  • Page 95 ¢ Model: ARXG12KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 96 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 90 - 6-3.
  • Page 97 ¢ Model: ARXG14KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 98 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 92 - 6-3.
  • Page 99 6-4. Wall mounted type ¢ Models: ASHG07–12KMTB, ASHG07–12KMCC, ASHG07– 12KMCE, ASHG07–12KMCF, ASHH07–12KMCG, ASHH07– 12KMCG-B, ASHH07–12KMCH, ASHH07–12KMCH-B, ASHG07– 12KETA, ASHG07–12KETA-B, ASHG07–12KETE, ASHG07– 12KETE-B, ASHG07–12KETF, ASHG07–12KETF-B, ASHG07– 09KGTB, ASHG07–09KGTE, ASHG07–09KGTF, ASHH07– 09KGTG, and ASHH07–09KGTH Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center...
  • Page 100 ¢ Models: ASHG14KMTB, ASHG14KMCC, ASHG14KMCE, ASHG14KMCF, ASHH14KMCG, ASHH14KMCG-B, ASHH14KMCH, ASHH14KMCH-B, ASHG14KETA, ASHG14KETA- B, ASHG14KETE, ASHG14KETE-B, ASHG14KETF, ASHG14KETF-B, ASHG12–14KGTB, ASHG12–14KGTE, ASHG12–14KGTF, ASHH12–14KGTG, and ASHH12–14KGTH Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up...
  • Page 101 ¢ Models: ASHH05KNCA and ASHH05KNCH Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
  • Page 102 ¢ Models: ASHH07KNCA and ASHH07KNCH Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
  • Page 103 ¢ Models: ASHH09KNCA and ASHH09KNCH Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
  • Page 104 ¢ Models: ASHH12KNCA and ASHH12KNCH Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
  • Page 105 6-5. Floor type ¢ Models: AGHG09–14KVCA Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower Unit: m/s Top view Horizontal louver: Up Vertical louver: Center UPPER LOWER Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up...
  • Page 106 7. Fan performance NOTE: Airflow and capacity/outlet temperature curve data are measured based on the same condi- tions mentioned in "Specifications". 7-1. Mini duct type ¢ Model: ARXG07KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Quiet (SP mode 03) Hi (SP mode 03) Normal SP upper limit...
  • Page 107  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 101 - 7-1. Mini duct type 7. Fan performance...
  • Page 108 ¢ Model: ARXG09KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Hi (SP mode 03) Quiet (SP mode 03) SP mode 00 upper limit SP mode 03 lower limit Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 109  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 103 - 7-1. Mini duct type 7. Fan performance...
  • Page 110 ¢ Model: ARXG12KSLAP SP mode 03 upper limit Quiet (SP mode 03) Hi (SP mode 03) Quiet Normal SP (Normal SP) upper limit Quiet SP mode 03 (SP mode 00) lower limit SP mode 00 (Normal SP) upper limit Hi (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 03)
  • Page 111  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 105 - 7-1. Mini duct type 7. Fan performance...
  • Page 112 ¢ Model: ARXG14KSLAP Hi (SP mode 05) SP mode 05 upper limit Quiet (SP mode 00) Nomal SP Quiet upper limit (Nomal SP) Quiet Hi (Normal SP) (SP mode 05) SP mode 05 lower limit SP mode 00 upper limit (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 113  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 107 - 7-1. Mini duct type 7. Fan performance...
  • Page 114 7-2. Slim duct type ¢ Model: ARXG07KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Normal SP upper limit lower limited Quiet (SP mode 00)
  • Page 115  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 109 - 7-2. Slim duct type 7. Fan performance...
  • Page 116 ¢ Model: ARXG09KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) Hi (SP mode00) SP mode 00 upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 09)
  • Page 117  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 111 - 7-2. Slim duct type 7. Fan performance...
  • Page 118 ¢ Model: ARXG12KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Hi (SP mode 00) upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 119  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 113 - 7-2. Slim duct type 7. Fan performance...
  • Page 120 ¢ Model: ARXG14KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) Nomal SP upper limit SP mode 09 lower limit Quiet (Nomal SP) Hi (Normal SP) SP mode 00 upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000...
  • Page 121  Characteristics of air volume and capacity • Cooling Capacity 1,000 Airflow (m • Heating Capacity 1,000 Airflow (m - 115 - 7-2. Slim duct type 7. Fan performance...
  • Page 122 7-3. Medium static pressure duct type ¢ Model: ARXH12KMTAP Fan performance curve 1 Hi (SP mode 15) SP mode 15 upper limit SP mode 15 lower limit Me (SP mode 15) Lo (SP mode 15) Standard SP upper limit SP mode 03 Qu (SP mode 15) upper limit Hi (Standard SP)
  • Page 123  Characteristics of air volume and capacity • Cooling 1,050 1,150 Airflow (m • Heating 1,050 1,150 Airflow (m - 117 - 7-3. Medium static pressure duct type 7. Fan performance...
  • Page 124 ¢ Model: ARXH14KMTAP Fan performance curve 1 Hi (SP mode 15) SP mode 15 upper limit SP mode 15 lower limit Me (SP mode 15) Lo (SP mode 15) Standard SP upper limit SP mode 03 upper limit Qu (SP mode 15) Hi (Standard SP) Me (Standard SP) Standard SP...
  • Page 125  Characteristics of air volume and capacity • Cooling 1,000 1,100 1,200 1,300 Airflow (m • Heating 1,000 1,100 1,200 1,300 Airflow (m - 119 - 7-3. Medium static pressure duct type 7. Fan performance...
  • Page 126 8. Airflow Conversion factor: • 1 m /h = 0.2778 l/s = 0.5886 CFM • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 8-1. Compact cassette type Airflow Model Operation mode Fan speed High Cooling AUXG07KVLA Quiet AUXG09KVLA...
  • Page 127 8-2. Mini duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KSLAP High Heating Quiet High Cooling Quiet ARXG09KSLAP High Heating Quiet High Cooling Quiet ARXG12KSLAP High Heating Quiet High Cooling Quiet ARXG14KSLAP High Heating Quiet - 121 - 8-2.
  • Page 128 8-3. Slim duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KLLAP High Heating Quiet High Cooling Quiet ARXG09KLLAP High Heating Quiet High Cooling Quiet ARXG12KLLAP High Heating Quiet High Cooling Quiet ARXG14KLLAP High Heating Quiet - 122 - 8-3.
  • Page 129 8-4. Medium static pressure duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXH12KMTAP High Heating Quiet High Cooling Quiet ARXH14KMTAP High Heating Quiet - 123 - 8-4. Medium static pressure duct type 8. Airflow...
  • Page 130 8-5. Wall mounted type Airflow Model Operation mode Fan speed High Cooling Quiet ASHG07KMTB High Heating Quiet High Cooling Quiet ASHG09KMTB High Heating Quiet High Cooling Quiet ASHG12KMTB High Heating Quiet High Cooling Quiet ASHG14KMTB High Heating Quiet High Cooling Quiet ASHG07KMCC High...
  • Page 131 Airflow Model Operation mode Fan speed High Cooling Quiet ASHG12KMCC High Heating Quiet High Cooling Quiet ASHG14KMCC High Heating Quiet High Cooling Quiet ASHG07KMCE High Heating Quiet High Cooling Quiet ASHG09KMCE High Heating Quiet High Cooling Quiet ASHG12KMCE High Heating Quiet High Cooling...
  • Page 132 Airflow Model Operation mode Fan speed High Cooling Quiet ASHG07KMCF High Heating Quiet High Cooling Quiet ASHG09KMCF High Heating Quiet High Cooling Quiet ASHG12KMCF High Heating Quiet High Cooling Quiet ASHG14KMCF High Heating Quiet High Cooling ASHH07KMCG Quiet High ASHH07KMCG-B Heating Quiet High...
  • Page 133 Airflow Model Operation mode Fan speed High Cooling ASHH12KMCG Quiet ASHH12KMCG-B High Heating Quiet High Cooling ASHH14KMCG Quiet High ASHH14KMCG-B Heating Quiet High Cooling ASHH07KMCH Quiet ASHH07KMCH-B High Heating Quiet High Cooling ASHH09KMCH Quiet High ASHH09KMCH-B Heating Quiet High Cooling ASHH12KMCH Quiet High...
  • Page 134 Airflow Model Operation mode Fan speed High Cooling ASHG07KETA Quiet ASHG07KETA-B High Heating Quiet High Cooling ASHG09KETA Quiet High ASHG09KETA-B Heating Quiet High Cooling ASHG12KETA Quiet ASHG12KETA-B High Heating Quiet High Cooling ASHG14KETA Quiet High ASHG14KETA-B Heating Quiet High Cooling ASHG07KETE Quiet High...
  • Page 135 Airflow Model Operation mode Fan speed High Cooling ASHG12KETE Quiet ASHG12KETE-B High Heating Quiet High Cooling ASHG14KETE Quiet High ASHG14KETE-B Heating Quiet High Cooling ASHG07KETF Quiet ASHG07KETF-B High Heating Quiet High Cooling ASHG09KETF Quiet High ASHG09KETF-B Heating Quiet High Cooling ASHG12KETF Quiet High...
  • Page 136 Airflow Model Operation mode Fan speed High Cooling Quiet ASHG07KGTB High Heating Quiet High Cooling Quiet ASHG09KGTB High Heating Quiet High Cooling Quiet ASHG12KGTB High Heating Quiet High Cooling Quiet ASHG14KGTB High Heating Quiet High Cooling Quiet ASHG07KGTE High Heating Quiet High Cooling...
  • Page 137 Airflow Model Operation mode Fan speed High Cooling Quiet ASHG12KGTE High Heating Quiet High Cooling Quiet ASHG14KGTE High Heating Quiet High Cooling Quiet ASHG07KGTF High Heating Quiet High Cooling Quiet ASHG09KGTF High Heating Quiet High Cooling Quiet ASHG12KGTF High Heating Quiet High Cooling...
  • Page 138 Airflow Model Operation mode Fan speed High Cooling Quiet ASHH07KGTG High Heating Quiet High Cooling Quiet ASHH09KGTG High Heating Quiet High Cooling Quiet ASHH12KGTG High Heating Quiet High Cooling Quiet ASHH14KGTG High Heating Quiet High Cooling Quiet ASHH07KGTH High Heating Quiet High Cooling...
  • Page 139 Airflow Model Operation mode Fan speed High Cooling Quiet ASHH12KGTH High Heating Quiet High Cooling Quiet ASHH14KGTH High Heating Quiet High Cooling Quiet ASHH05KNCA High Heating Quiet High Cooling Quiet ASHH07KNCA High Heating Quiet High Cooling Quiet ASHH09KNCA High Heating Quiet High Cooling...
  • Page 140 Airflow Model Operation mode Fan speed High Cooling Quiet ASHH05KNCH High Heating Quiet High Cooling Quiet ASHH07KNCH High Heating Quiet High Cooling Quiet ASHH09KNCH High Heating Quiet High Cooling Quiet ASHH12KNCH High Heating Quiet - 134 - 8-5. Wall mounted type 8.
  • Page 141 8-6. Floor type Airflow Model Operation mode Fan speed High Cooling Quiet AGHG09KVCA High Heating Quiet High Cooling Quiet AGHG12KVCA High Heating Quiet High Cooling Quiet AGHG14KVCA High Heating Quiet - 135 - 8-6. Floor type 8. Airflow...
  • Page 142 9. Noise level curve 9-1. Compact cassette type ¢ Model: AUXG07KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000...
  • Page 143 ¢ Model: AUXG12KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 144 9-2. Mini duct type ¢ Model: ARXG07KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH NC-35 NC-35 HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 145 ¢ Model: ARXG12KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 146 9-3. Slim duct type ¢ Model: ARXG07KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 147 ¢ Model: ARXG12KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 148 9-4. Medium static pressure duct type ¢ Model: ARXH12KMTAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH NC-30 NC-30 HIGH NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000...
  • Page 149 9-5. Wall mounted type ¢ Models: ASHG07KMTB, ASHG07KMCC, ASHG07KMCE, ASHG07KMCF, ASHH07KMCG, ASHH07KMCG-B, ASHH07KMCH, ASHH07KMCH-B, ASHG07KETA, ASHG07KETA- B, ASHG07KETE, ASHG07KETE-B, ASHG07KETF, and ASHG07KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30...
  • Page 150 ¢ Models: ASHG09KMTB, ASHG09KMCC, ASHG09KMCE, ASHG09KMCF, ASHH09KMCG, ASHH09KMCG-B, ASHH09KMCH, ASHH09KMCH-B, ASHG09KETA, ASHG09KETA- B, ASHG09KETE, ASHG09KETE-B, ASHG09KETF, and ASHG09KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20...
  • Page 151 ¢ Models: ASHG12KMTB, ASHG12KMCC, ASHG12KMCE, ASHG12KMCF, ASHH12KMCG, ASHH12KMCG-B, ASHH12KMCH, ASHH12KMCH-B, ASHG12KETA, ASHG12KETA- B, ASHG12KETE, ASHG12KETE-B, ASHG12KETF, and ASHG12KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20...
  • Page 152 ¢ Models: ASHG14KMTB, ASHG14KMCC, ASHG14KMCE, ASHG14KMCF, ASHH14KMCG, ASHH14KMCG-B, ASHH14KMCH, ASHH14KMCH-B, ASHG14KETA, ASHG14KETA- B, ASHG14KETE, ASHG14KETE-B, ASHG14KETF, and ASHG14KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20...
  • Page 153 ¢ Models: ASHG07KGTB, ASHG07KGTE, ASHG07KGTF, ASHH07KGTG, and ASHH07KGTH  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000...
  • Page 154 ¢ Models: ASHG12KGTB, ASHG12KGTE, ASHG12KGTF, ASHH12KGTG, and ASHH12KGTH  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000...
  • Page 155 ¢ Models: ASHH05KNCA and ASHH05KNCH  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 156 ¢ Models: ASHH09KNCA and ASHH09KNCH  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 157 9-6. Floor type ¢ Model: AGHG09KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 158 ¢ Model: AGHG14KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 HIGH NC-55 NC-55 HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 159 9-7. Sound level check point ¢ Compact cassette type Microphone 1.5 m Microphone - 153 - 9-7. Sound level check point 9. Noise level curve...
  • Page 160 ¢ Mini duct type , Slim duct type, and Medium static pressure duct type Product Measuring duct Measuring duct (Set the static pressure as rating in this area.) Microphone Microphone Front view Side view NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above.
  • Page 161 ¢ Floor type Microphone Microphone ● ● Airflow Airflow - 155 - 9-7. Sound level check point 9. Noise level curve...
  • Page 162 10. Electrical characteristics Power supply Wiring spec. of connection cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Input Cross- sectional Limited wiring power area length Type Model name AUXG07KVLA 0.19 0.15 AUXG09KVLA 0.19 0.15 Compact cassette AUXG12KVLA 0.24 0.19...
  • Page 163 Power supply Wiring spec. of connection cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Input Cross- sectional Limited wiring power area length Type Model name ASHG07KETA 0.25 0.20 ASHG07KETA-B ASHG09KETA 0.30 0.24 ASHG09KETA-B Wall mounted ASHG12KETA 0.30 0.24 ASHG12KETA-B...
  • Page 164 Power supply Wiring spec. of connection cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Input Cross- sectional Limited wiring power area length Type Model name ASHH05KNCH 0.14 0.11 ASHH07KNCH 0.15 0.12 Wall mounted ASHH09KNCH 0.24 0.19 ASHH12KNCH 0.25 0.20...
  • Page 165 11. Safety devices Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse AUXG07KVLA Activate: 100 ±15 °C Fan motor stop AUXG09KVLA Compact cassette Reset: 95 ±10 °C AUXG12KVLA AUXG14KVLA Fan motor restart ARXG07KSLAP ARXG09KSLAP Mini duct 250 V, 5 A...
  • Page 166 Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse ASHH07KMCH ASHH07KMCH-B Activate: 170 °C ASHH09KMCH Fan motor stop ASHH09KMCH-B Wall mounted 250 V, 3.15 A ― ― ASHH12KMCH Reset: 145 °C ASHH12KMCH-B Fan motor restart ASHH14KMCH ASHH14KMCH-B ASHG07KETA...
  • Page 167 Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse ASHG07KGTF Activate: 110 ±15 °C Fan motor speed down Reset: 110 ±15 °C ASHG09KGTF Fan motor speed recover Wall mounted 250 V, 3.15 A 102 °C Off ―...
  • Page 168 12. External input and output 12-1. Compact cassette type and Medium static pressure duct type • Compact cassette type CN71 Rotary switch CN14 CN65 CN47 CN46 (Ext. I/O PCB) (Ext. out) (Ext. in) Terminal (Ext. in) Fig. Indoor unit PCB Fig.
  • Page 169 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 170  Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External Input and Output PCB.
  • Page 171 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22 AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 172 ¢ Setting of external input and output • Indoor unit Input Connecting point Function setting number 46 Function Operation/Stop mode 1 (Setting prohibited) Terminal Forced stop mode Operation/Stop mode 2 Output Connecting point Function setting number 60 Function Operation/Stop 01 to 08 (Setting prohibited) CN47 Error status...
  • Page 173 ¢ Details of control input function  Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Off → On Operation — Input of indoor unit Terminal On →...
  • Page 174  Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Forced stop Off → On (R.C. disabled) — Input of indoor unit Terminal Normal On → Off (R.C.
  • Page 175  Operation/Stop mode 2 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Operation Off → On (R.C. enabled) — Input of indoor unit Terminal Stop On → Off (R.C.
  • Page 176  Forced thermostat off External Input and Output External input Input signal Command Rotary switch Off → On Thermostat off External Input and 2, B, C, D Ex IN 1 Output PCB On → Off Normal operation Ex IN 1 Compressor Room temp.
  • Page 177 ¢ Details of control output function  Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Operation 60-00 — Output of indoor unit CN47 On → Off Stop Off → On Operation External Input and —...
  • Page 178  Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Fan run 60-10 — Output of indoor unit CN47 On → Off Fan stop Off → On Fan run External Input and —...
  • Page 179 12-2. Mini duct type and Slim duct type Exterior of the indoor unit PCB and the component location differ by the type of the indoor unit as follows. • Mini duct type and Slim duct types: CN47 (Ext. out) Terminal (Ext. in) Indoor unit PCB External Input...
  • Page 180 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. •...
  • Page 181 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input External output Mode Function setting Terminal CN47 60—00...
  • Page 182 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 Function setting External input Input signal Command Off → On Operation 46—00 Terminal On → Off Stop Input Operation Indoor unit Stop Remote controller NOTES: •...
  • Page 183 • When function setting is "Operation/Stop" mode 2 Function setting External input Input signal Command Off → On Operation 46—03 Terminal Stop (Remote controller On → Off disabled) Input Operation Indoor unit Stop (R.C. disabled) Remote controller NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
  • Page 184  Indoor unit fan operation status Function setting External output Output signal Command Low → High Fan run 60—10 CN47 High → Low Fan stop Output signal Condition The indoor unit fan is operating. Low → High The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation.
  • Page 185 12-3. Wall mounted type (KGTB, KETA, and KETA-B) External Input and Output PCB SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 To CN6 on Indoor unit PCB Input External input External output Connector Input select signal Operation/Stop CN313/ Edge/Pulse Dry contact/ CN314...
  • Page 186 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 187 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  External Input and Output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 188 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External Input and Output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External Input Function...
  • Page 189  Input signal type External Input and Output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External Input and Output PCB. The width of pulse must be longer than 200 msec.
  • Page 190 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input: Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Off → On Operation External Input and 46—00...
  • Page 191 • When function setting is "Forced stop" mode – In the case of "Edge" input: Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Off → On Forced stop External Input and 46—02 60—00 / 1 CN313 Output PCB...
  • Page 192 • When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input: Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Off → On Operation Stop External Input and 46—03 60—00 / 1 CN313 (Remote...
  • Page 193 • Forced thermostat off function Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Thermostat 60—00 / 2 Off → On External Input and Output 60—09 / B CN313 Normal 60—10 / C On →...
  • Page 194  Control output function • Operation/Stop status Rotary SW on Function Output External Input and External output Command setting / signal Output PCB Off → On Operation External Input and Output 60—00 / 1 CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 195 12-4. Wall mounted type (KMTB and KMCC) With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details.
  • Page 196 • Circuit diagram example • Contact capacity: DC 24 V or more, 10 Indoor unit mA or more. Communication kit Connected unit control PCB • *: Make the distance from the PCB to Example: Switch Connector the connected unit within 10 m. •...
  • Page 197 • Optional part Part name Model name Exterior External input wire External Connect Kit UTY-XWZXZ5 Communication Kit UTY-TWBXF2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5). - 191 - 12-4.
  • Page 198 ¢ External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device.  Operation status output Air conditioner operation status signal can be output. •...
  • Page 199  Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
  • Page 200 12-5. Wall mounted type (KMCE, KMCF, KMCG, KMCG-B, KMCH, KMCH-B, KETE, KETE-B, KETF, KETF-B, KGTE, KGTF, KGTG, and KGTH) External Input and Output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312...
  • Page 201 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 202  External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select: Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 203 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
  • Page 204  External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Combination of external input and output"...
  • Page 205 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External Input and Output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input Function Rotary...
  • Page 206  Input signal type External Input and Output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External Input and Output PCB. The width of pulse must be longer than 200 msec.
  • Page 207 ¢ Details of function  Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation External Input and 46-00...
  • Page 208 • When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Forced stop External Input and 46-02 CN313 Output PCB On →...
  • Page 209 • When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation Stop External Input and 46-03 CN313 (Remote Output PCB On →...
  • Page 210 • Forced thermostat off function Rotary SW on Input Function setting / External Input External input Command signal and Output PCB Thermostat 60-00 Off → On External Input and 60-09 CN313 Output PCB Normal On → Off 60-10 operation Input Compressor Room temp.
  • Page 211  Control output function • Operation/Stop status Rotary SW on Output Function setting / External Input External output Command signal and Output PCB 60-00 / 1 Off → On Operation Output of indoor unit CN47 60-00 / 2 On → Off Stop 60-00 / 1 Off →...
  • Page 212 • Indoor unit fan operation status Rotary SW on Output Function setting / External Input External output Command signal and Output PCB Off → On Fan run 60-10 / C Output of indoor unit CN47 On → Off Fan stop 60-00 / 2 Off →...
  • Page 213 12-6. Floor type Indoor unit PCB CN 23 CN 21 CN 15 CN 14 P 190 External input External output Connector Input signal Operation/Stop CN14 Forced stop — Edge Forced thermostat off CN15 Operation status Indoor unit Error status CN20/CN21/ —...
  • Page 214 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m . •...
  • Page 215 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input Function Mode Indoor unit setting CN14 CN15...
  • Page 216 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 On → Off Stop 46-00 Input of indoor unit...
  • Page 217 • When function setting is "Operation/Stop"mode 2 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation Stop — CN14 (Remote On → Off controller disabled) 46-03 Input of indoor unit Off →...
  • Page 218  Control output function • Operation/Stop status Output Mode Function setting External output Command signal Low → High Operation 60-00 CN15 High → Low Stop Output of indoor unit Off → On Operation 60-00 CN20 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 219 • Indoor unit fan operation status Output Mode Function setting External output Command signal Low → High Fan run 60-10 CN15 High → Low Fan stop Output of indoor unit Off → On Fan run 60-00 CN22 On → Off Fan stop Output signal Condition...
  • Page 220 • Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 214 - 12-6.
  • Page 221 • Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 222 13. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 223 2. Set the remote controller address. (Function setting) • Addresses will be automatically set when initially starting up this unit. In such a case, do not change the remote controller address for the indoor unit, and keep it at the initial setting of “00”.
  • Page 224 14. Remote controller 14-1. Wireless remote controller (AR-REW4E, AR-REM4E, AR- REB1E, and AR-REJ1E) ¢ Overview AR-REW4E Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop...
  • Page 225 AR-REM4E Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button RESET button NEXT button...
  • Page 226 AR-REB1E Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button CLOCK ADJUST button TIMER CANCEL button NOTE: Functions may differ by type of the indoor unit.
  • Page 227 AR-REJ1E Signal transmitter MODE button FAN button 10°C HEAT button TEMP. SWING button button SET button Economy button ON timer button OFF timer button Start/Stop button REG1U Timer SELECT button RESET button SLEEP timer button TEST RUN button Timer CANCEL button CLOCK ADJUST button NOTE: Functions may differ by type of the indoor unit.
  • Page 228 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 229 14-2. Wireless remote controller (AR-REW3E) ¢ Overview Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button...
  • Page 230 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 231 14-3. Wireless remote controller (AR-REM7E) ¢ Overview Signal transmitter MODE button FAN button 10 °C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 232 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 233 14-4. Wireless remote controller (AR-RMB1E and AR-RMB1E-B) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button...
  • Page 234 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 235 14-5. Wireless remote controller (UTY-LNTG: Optional part) and IR receiver kit with Wireless remote controller (UTY- LBTGM: Optional part) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button TEMP. SWING button button SET button Economy button ON timer button OFF timer button Start/Stop button...
  • Page 236 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 237  IR receiver (UTY-LBTGM) Unit: mm 13.6 57.4 13.6 11.5 18.5 Front view Side view Rear view Size (H × W × D) 145 × 90 × 30 Weight - 231 - 14-5. Wireless remote controller (UTY-LNTG: Optional part) and IR receiver kit with 14.
  • Page 238 14-6. Wireless remote controller (AR-RPF4E) ¢ Overview a MODE button • Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT). • Starts/ends the remote controller custom code (max. 4 types) change. b FAN SPEED button • Press the FAN SPEED button while the air conditioner is operating, to control fan speed.
  • Page 239 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 162 × 45 × 18 Weight 65.5 (without batteries)  Holder Unit: mm Top view Ø 3.9 (Hole) Hole 26.6 49.3 Front view Side view Size (H ×...
  • Page 240 14-7. Wired remote controller (UTY-RNNGM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
  • Page 241 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 242 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Front view Side view Size (H × W × D) 120 × 120 × 18 Weight Cable length (accessory) Power  Wiring specifications Cable size Wire type Remarks Remote controller cable...
  • Page 243  When connecting to Communication Kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication Kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 244 14-8. Wired Remote Controller (UTY-RVRG : Optional part) • Easy finger touch operation with LCD panel. • Screen with anti-fingerprint coating • Various information display (Room temp., Operation mode, Set temp. Fan speed, Timer) • Control up to 16 indoor units •...
  • Page 245 Temperature setting screen a Page indicator Shows the oder of pages and displayed page. b Operation On/Off button Tap to start operation or stop the air conditioner. c Bluetooth icon Displays when Bluetooth is enabled. d Information area The displayed contents differ depending on the screen and settings.
  • Page 246 ¢ System diagrams • Multiple remote control Up to 2 remote controllers can be used to operate the indoor units. I.U. I.U. – Remote controller • A: UTY-RVRG • B: Other than UTY-RVRG (2-wire type only) – Remote controller cable •...
  • Page 247 • Maximum connectable number of remote controller (2-wire type) Maximum connectable number of remote controller (2-wire type) is limited by cable size and maxi- mum cable length. When using only remote controller other than UTY-RVRG Cable size (S) Total cable length (L) L ≤...
  • Page 248 ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit When there is When there is a functional a functional grounding grounding Remote controller Remote controller Remote controller Group control: Indoor units When there is a functional grounding Remote controller - 242 - 14-8.
  • Page 249 ¢ Dimensions Unit: mm Hole: 8.2 × 20.5 Hole: 9 × 4.5 33.5 Hole: 6 × 4.5 Hole: 12.5 × 4.5 ¢ Installation space • This product cannot be installed in a wall. • Even when you install a remote controller to one of a switch box and the surface of a wall, secure the space shown in following figure.
  • Page 250 ¢ Installation For details of installation, refer to the INSTALLATION MANUAL for this product. • Connector removal Open the front case and remove the connector of the remote controller cable from the connector of the PCB on the front case (back side). Fron case (back side) Rear case Connector...
  • Page 251 • Rear case installation – When attaching to switch box: Seal the wiring hole of the remote controller cable with putty. Trap (remote controller cable) Connector Putty Self-tapping screw Rear case Trap – When attaching to the wall directly: Wall Seal the wiring hole of the remote controller cable with putty.
  • Page 252 • Remote controller cable connection – Fasten the outside covering of the connection cable with the cable tie. Cable tie – Connect the connector of the remote controller cable to the connector of the PCB on the front case (back side). Clamp Rear case Front case...
  • Page 253 ¢ Specifications Input voltage DC 12 Power consumption Max. 1.0 Display 4-inch TFT LCD (480 × 480 pixels) with touch screen Usage temperature range °C 0 to 40 Usage humidity range 20 to 90 (no condensation) Storage temperature range °C -10 to 60 Storage humidity range 20 to 90 (no condensation)
  • Page 254 14-9. Wired remote controller (UTY-RLRG: Optional part) ¢ Overview a LED lamp (Operation indicator) Lights while the indoor unit is operating. Blinks when an error occurred. b FAN button Each time the button is pressed, fan speed switches as follows: Auto High Quiet...
  • Page 255 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 256 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Hole: 9 × 4.5 Hole: 12.5 × 4.5 Hole: 6 × 4.5 Front view Side view Rear view Size (H × W × D) 120 ×...
  • Page 257 NOTES: • The detailed shape and the layout of the terminal block and the PCB vary depending on the indoor unit type. • Operation may fail if it is connected to the outdoor unit or the terminal block for power sup- ply.
  • Page 258 14-10. Wired remote controller (UTY-RVNGM: Optional part) ¢ Overview a Display panel (with backlight) b Screen switch button (Left) c Menu button d Cancel button e Cursor button f Screen switch button (Right) g Power indicator h On/off button i Enter button - 252 - 14-10.
  • Page 259 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 260 ¢ Specifications Unit: mm 21.3 Front view Side view Size (H × W × D) 120 × 120 × 21.3 Weight  Wiring specifications Cable size Wire type Remarks Remote controller cable Polar 3 core Use sheathed PVC cable. 0.33 mm - 254 - 14-10.
  • Page 261 ¢ Installation (Remote control main unit) Installation space: Unit : mm or more or more or more 220 or more* NOTE: Secure enough space where a flat-blade screwdriver to remove the case can be inserted. Installation procedures: 1. Process the remote controller cable. Unit : mm 1.
  • Page 262 3. Attach the remote controller. • When attaching to switch box: a. Seal the wiring hole of the remote controller cable. b. Put a remote controller cable through the hole of the rear case. c. Fix the rear case by securing it with attached screws (2 places). •...
  • Page 263 4. Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2 N•m 1. 12V (Red) 2. Signal (White) 3.
  • Page 264 5. Attach the front case. • Insert after adjusting upper part of front case. • When insert the front case, do not pinch the cable. Front case Click! Good Prohibited Prohibited Prohibited CAUTION Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off. ¢...
  • Page 265  When connecting to Communication Kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication Kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 266 14-11. Wired remote controller (UTY-RNRGZ*: Optional part) ¢ Overview a Remote temperature sensor (inside) b On/off button Operable only while displaying the “Monitor mode” screen. c LED lamp (operation indicator) d Touch panel display e Set temperature Operating temperature can be set. f Remote controller group name g Mode Operation mode can be set.
  • Page 267 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 268 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm 20.4 Model name UTY-RNRGZ* Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) 120 × 120 × 20.4 Weight Input voltage DC 12...
  • Page 269 Terminal block Remote controller cable (Non-polar) NOTES: • The detailed shape and the layout of the terminal block and the PCB vary depending on the indoor unit type. • Operation may fail if it is connected to the outdoor unit or the terminal block for power sup- ply.
  • Page 270 14-12. Wired remote controller (UTY-RCRGZ1: Optional part) ¢ Overview a Display panel b MODE button c Menu button buttons (Set temperature buttons) e FAN button f On/off button g Wireless remote controller signal receiving section - 264 - 14-12. Wired remote controller (UTY-RCRGZ1: Optional part) 14.
  • Page 271 ¢ System diagrams • Single remote control I.U. Remote controller cable A ≤ 500 m ¢ Electrical wiring Indoor unit Remote controller - 265 - 14-12. Wired remote controller (UTY-RCRGZ1: Optional part) 14. Remote controller...
  • Page 272 ¢ Specifications Unit: mm Hole × 2 (for M4 screws) Size (H × W × D) 86 × 86 × 32 Weight  Wiring specifications Cable size Wire type Remarks Remote controller 0.33 to 1.25 mm Non polar 2-core Use sheathed twist pair cable.* cable (22 to 16 AWG) *: Use shielded cable (locally purchased) in accordance with the regional cable standard.
  • Page 273 • Pattern B 1. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove the insulation from the cut end of the cable as shown below. 20 mm Remote controller cable (Non-polar) 2.
  • Page 274 14-13. Simple remote controller (UTY-RSNGM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
  • Page 275 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 276 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm hole x 2 hole x 2 Front View Side View Rear View Size (H × W × D) 120 × 75 × 14 Weight Cable length (accessory) Power ...
  • Page 277  When connecting to Communication Kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication Kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 278 14-14. Simple remote controller (UTY-RSRG and UTY-RHRG: Optional parts) ¢ Overview a LED lamp Lights during operation. b Louver button Adjusts the airflow direction. c START/STOP button Starts and stops operation. d FAN control button Switches the fan speed as follows: Auto High Quiet...
  • Page 279 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 280 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm 30.0 30.0 Hole: 9 × 4.5 23.0 Hole: 6 × 4.5 Hole: 12.5 × 4.5 Front View Side View Rear View Size (H × W × D) 120 ×...
  • Page 281 NOTES: • The detailed shape and the layout of the terminal block and the PCB vary depending on the indoor unit type. • Operation may fail if it is connected to the outdoor unit or the terminal block for power sup- ply.
  • Page 282 15. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 15-1. Compact cassette, Mini duct, Slim duct types indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings.
  • Page 283 ¢ DIP switch setting • SW100: Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. The slide switches are normally set to make the unit number 00. Remote Switch number controller...
  • Page 284 15-2. Medium static pressure duct type By using some components on the PCB, you can change the function settings. Related components on the PCB and the applicable settings Component Setting content Drainage function setting Setting change prohibited DIP switch101 Fan delay setting Setting change prohibited ...
  • Page 285 15-3. Indoor unit (setting by wireless remote controller) CAUTION This setting changes the function settings used to control the indoor unit according to the installa- tion conditions. Incorrect settings can cause a product malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 286 ¢ AR-REM4E (for Wall mounted type KGTB), AR-REW3E (for Wall mounted type KGTE, KGTF, KGTG, and KGTH), AR-REW4E (for Wall mounted type KETA[-B], KETE[-B], and KETF[-B]), and AR- REM7E (for Floor type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller.
  • Page 287  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the POWERFUL and TEMP. button, press the RESET button. POWERFUL TEMP. ( RESET Function setting mode display Select the function number by pressing the or the buttons.
  • Page 288 Press the MODE button once to transmit the function mode information. Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
  • Page 289  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 290  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the TEMP.
  • Page 291 ¢ AR-REB1E (for Wall mounted type KMCC) and AR-RMB1E(-B) (for Wall mounted type KMCE, KMCF, KMCG, KMCG-B, KMCH, and KMCH-B)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details.
  • Page 292  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the POWERFUL and SET TEMP. buttons, press the RESET button. POWERFUL SET TEMP. ( RESET Function setting mode display Select the function number by pressing the or the buttons.
  • Page 293 Press the MODE button once to transmit the function mode information. 2 short beeps Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
  • Page 294  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 295  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 296 ¢ UTY-LNTG (for Compact cassette type) or AR-REJ1E (included in UTY-LBTGM for Duct type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details.
  • Page 297  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the ECONOMY and TEMP. buttons, press the RESET button. ECONOMY TEMP. ( RESET Function setting mode display - 291 - 15-3.
  • Page 298 Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the ECONOMY button. (To return to the function number selection, press the ECONOMY button again.) Select the function number by pressing the or the...
  • Page 299 Press the button once to transmit the function setting information. 1 short beep will be emit- ted from the indoor unit or the IR receiver when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 1 short beep NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 300  Setting up each indoor unit Repeat step from 1. to 8. to set up each indoor unit. If the custom code is other than " ", steps from 1. to 2. and 8. need to be performed.  Resetting the power after setting up all indoor units Important: •...
  • Page 301  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the TEMP.
  • Page 302 ¢ AR-RPF4E (for Wall mounted type KNCA and KNCH) The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 303 STEP 2: Selecting the function number and setting value 1. Press the TEMP./SELECT ( ) buttons to select the function Function number number. To switch between the left and right digits, press the MODE button. 2. Press the FAN SPEED button to proceed the setting value. To re- turn the function number selection, press the FAN SPEED button again.
  • Page 304  Custom code setting on AR-RPF4E To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 305 15-4. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 306 ¢ UTY-RNNGM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
  • Page 307 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
  • Page 308 ¢ UTY-RLRG  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 309 Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button. Function number Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button. Setting number Example: Function number 30 Setting number 01 Error Good...
  • Page 310 ¢ UTY-RVNGM  Function setting procedure Connect the power supply of the outdoor unit. Switch to the function setting mode. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor”...
  • Page 311 Select the [Function No.] with pressing the [Cursor button (Left/Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)]. Function setting Mo 10:00AM R.C. Function Setting address Cancel: Version Error history Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button (Up/Down)].
  • Page 312 When [Cancel button] is pressed twice while “Function setting” screen is displayed, it switches to the “Submenu” screen. Function setting Mo 10:00AM R.C. Function Setting Submenu Mo 10:00AM address Date and time Screen Cancel: Filter sign Version Error history R.C. sensor control Room temp.
  • Page 313 ¢ UTY-RNRGZ*  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 314 “Function No.” screen is displayed. Set the “Function No.” with Function No. Cancel When the “OK” is touched, the display returns to the “Function Setting” screen. Touch the “Function No.” on the “Function Setting” screen. Function Setting Address [002–01] Function No. [30] Setting No.
  • Page 315 Touch the “Yes” of the verification screen. Function Setting Function setting will be performed. OK? In case of “ERROR” In case of “OK” Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Function No. [30] Setting No. [01] Setting No.
  • Page 316 ¢ UTY-RVRG  Function setting procedure Tap the menu as shown below. Enter the Admin password. Enter the Installer password. Tap “Address” on the Function Setting screen. Pull-down window of indoor unit address is displayed. Select the address of the indoor unit whose function number is to be set.
  • Page 317 Pull-down window of Function No. is displayed. Set the Function No to be set. Tap “Setting No.” on the Function Setting screen. Pull-down window of “Setting No.” is displayed. Set the Setting No. Tap “Set” on the verification screen. to return to the Initial Setting screen. - 311 - 15-4.
  • Page 318 15-5. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 319 ¢ UTY-RSNGM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
  • Page 320 Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
  • Page 321  Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 322 ¢ UTY-RSRG/UTY-RHRG  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 323 Select the item number to be set with the SET TEMP. or SET TEMP. button, and press button to switch to the setting screen. Select the “13” in Menu 2-F1 settings. Then, press the button. Select the 2-wire remote controller address with the SET TEMP. or SET TEMP.
  • Page 324 Press the button to return to the 2-wire remote controller address selection screen of step 9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item selec- tion screen.  Setting up each indoor unit Repeat the procedure from step 1 to 6, and set up the indoor units requiring function setting.
  • Page 325 15-6. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Medium Functio Compact...
  • Page 326 Wall mounted Functio Functions n no. KMCC KMCE KMCF KMCG (-B) KMCH (-B) Remote controller ● — — — — address setting Filter sign ● ● ● ● ● Ceiling height — — — — — Outlet directions — — —...
  • Page 327 Wall mounted Functio Functions n no. KGTF KGTG KGTH KNCA KNCH Remote controller — — — — — address setting Filter sign ● ● ● ● ● Ceiling height — — — — — Outlet directions — — — — —...
  • Page 328 1) Remote controller address setting (for Wall-mounted type only) NOTES: • Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. • This setting is configurable only by wireless remote controller, but not configurable by Polar 3- wired remote controller.
  • Page 329 3) Ceiling height (for Compact cassette type only) Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 4. "Dimensions"...
  • Page 330 5) Static pressure (for Mini duct type, Slim duct type, and Medium static pressure duct type) Select the appropriate static pressure according to the installation conditions. For mini duct type: Function number Setting value Setting description Factory setting 0 Pa 10 Pa 20 Pa 30 Pa...
  • Page 331 6) Room temperature control for indoor unit sensor NOTE: If the remote sensor unit option is selected, perform this setting. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 332 7) Room temperature control for wired remote controller sensor (for other than Floor type and KN models in Wall-mounted type) Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”.
  • Page 333 10) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 11) External input control “Operation/Stop” mode or “Forced stop” mode can be selected. Function number Setting value Setting description...
  • Page 334 14) Switching functions for external output terminal (For other than 18-24KMTB, KETA[-B], and KN models in Wall-mounted type) Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦...
  • Page 335 15-7. Wired remote controller (UTY-RNNGM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
  • Page 336  SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
  • Page 337 15-8. Wired remote controller (UTY-RVNGM) Memory backup setting DIP switch 1 Dual remote controller setting ¢ Switch location ¢ DIP switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 338 15-9. Wired remote controller (UTY-RLRG) DIP switch Memory backup setting ¢ Switch location Front case (back side) Set the DIP switch to ON ¢ Dip switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 339 15-11. Simple remote controller (UTY-RSNGM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting  SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
  • Page 340 16. Accessories 16-1. Compact cassette type ¢ Models: AUXG07–14KVLA Part name Exterior Part name Exterior Operation manual Drain hose insulation Operation manual Hose band (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Template (Carton top) (small) M10 nut A Cable tie (with flange) M10 nut B...
  • Page 341 16-2. Mini duct type ¢ Models: ARXG07–14KSLAP Part name Exterior Part name Exterior Operation manual Drain hose Operation manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation Cable tie (medium) (small)
  • Page 342 16-3. Slim duct type ¢ Models: ARXG07–14KLLAP Part name Exterior Part name Exterior Operation manual Filter (small) Operation manual Drain hose (CD-ROM) Installation manual Hose band Installation template Drain hose insulation B Insulation Washer (for electrical wiring) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation...
  • Page 343 16-4. Medium static pressure duct type ¢ Models: ARXH12–14KMTAP Part name Exterior Part name Exterior Operation manual Cable tie (large) Operation manual Cable tie (medium) (CD-ROM) Installation manual Cable tie (small) Washer Drain hose insulation Coupler heat insulation Drain hose (large) Coupler heat insulation Hose band...
  • Page 344 16-5. Wall mounted type ¢ Models: ASHG07–14KMCE and ASHG07–14KMCF Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder - 338 -...
  • Page 345 ¢ Models:ASHH07–14KMCG, ASHH07–14KMCG-B, and ASHH07– 14KGTG Part name Exterior Part name Exterior Operation manual Cloth tape Self-tapping screw Installation manual (large) Self-tapping screw Remote controller (small) Battery Wall hook bracket Remote controller Filter holder holder Installation spacer Air cleaning filters Operation manual (CD-ROM) - 339 -...
  • Page 346 ¢ Models:ASHH07–14KMCH, ASHH07–14KMCH-B, and ASHH07– 14KGTH Part name Exterior Part name Exterior Operation manual Cloth tape Self-tapping screw Installation manual (large) Self-tapping screw Remote controller (small) Battery Wall hook bracket Remote controller Filter holder holder Installation spacer Air cleaning filters - 340 - 16-5.
  • Page 347 ¢ Models: ASHG07–14KETA, ASHG07–14KETA-B, ASHG07– 14KETE, ASHG07–14KETE-B, ASHG07–14KETF, and ASHG07– 14KETF-B Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder...
  • Page 348 ¢ Models: ASHG07–14KGTB, ASHG07–14KMTB, and ASHG07– 14KMCC Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder - 342 - 16-5.
  • Page 349 ¢ Models: ASHG07–14KGTE and ASHG07–14KGTF Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder ¢...
  • Page 350 ¢ Models: ASHH05–12KNCH Part name Exterior Part name Exterior Self-tapping screw Operation manual (Large) Self-tapping screw Installation manual (Small) Remote controller Wall hook bracket Remote controller Battery holder Installation spacer Cloth tape - 344 - 16-5. Wall mounted type 16. Accessories...
  • Page 351 16-6. Floor type ¢ Models: AGHG09–14KVCA Part name Exterior Part name Exterior Operation manual (CD- Operation manual ROM) Installation manual Cloth tape Self-tapping screws Wall hook bracket (large) Self-tapping screws Remote controller (small) Battery Air cleaning filters Remote controller holder - 345 - 16-6.
  • Page 352 17. Optional parts 17-1. Controllers ¢ Lineup Type Indoor unit type Wireless Remote Controller AR-REM4E AR-REM7E AR-REB1E AR-REW3E Compact cassette — — — — Mini duct — — — — Slim duct — — — — Medium static pressure duct —...
  • Page 353 Type Indoor unit type Wireless Remote Controller AR-REW4E AR-RMB1E(-B) AR-RPF4E UTY-LNTG Compact cassette — — — ◌ Mini duct — — — — Slim duct — — — — Medium static pressure duct — — — — Floor — — —...
  • Page 354 Type IR Receiver Kit with Indoor unit type Wired Remote Controller Wireless Remote Controller UTY-RNRGZ* UTY-RCRGZ1 UTY-LBTGM Compact cassette ◌ ◌ — Mini duct ◌ ◌ ◌ Slim duct ◌ ◌ ◌ Medium static pressure duct ◌ ◌ ◌ Floor —...
  • Page 355 • *1: Optional Communication Kit (UTY-TWBXF2) is necessary for the installation. • *2: Optional Communication Kit (UTY-TWRXZ2) is necessary for the installation. • *3: Optional Communication Kit (UTY-TWRXZ3) is necessary for the installation. - 349 - 17-1. Controllers 17. Optional parts...
  • Page 356 ¢ Parts Exterior Part name Model name Summary Remote controller that provides the functions you need in a sleek design Wired Remote that uniquely transforms itself to blend Controller UTY-RVRG with any interior. (Touch Panel) Wire type: Non-polar 2-wire Easy finger touch operation with LCD Wired Remote panel.
  • Page 357 Exterior Part name Model name Summary Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, and Simple Remote temperature setting. UTY-RHRG Controller Wire type: Non-polar 2-wire Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation Simple Remote UTY-RSNGM...
  • Page 358 17-2. Cassette grille ¢ Lineup Indoor unit type Model Compact cassette UTG-UFGF-W ¢ Part Exterior Part name Model name Summary This cassette grille can be installed Cassette Grille UTG-UFGF-W appropriately on the grid type ceiling common in the office. - 352 - 17-2.
  • Page 359 17-3. Others ¢ Lineup Type Air Outlet Shutter Insulation Kit for Fresh Air Intake Half Concealed Indoor unit type Plate High Humidity UTR-YDZB UTZ-KXGC UTZ-VXAA UTR-STA Compact cassette ◌ ◌ ◌ — Mini duct — — — — Slim duct —...
  • Page 360 Type Auto Louver External Switch Indoor unit type Remote Sensor Unit Grille Kit Controller UTD-GXTA-W UTY-XSZX UTY-XSZXZ* UTY-TERX Compact cassette — — — ◌ Mini duct ◌ ◌ ◌ ◌ Slim duct ◌ ◌ ◌ ◌ Medium static pressure duct —...
  • Page 361 Type Modbus Indoor unit type KNX Convertor Network Converter Converter UTY-VKSX UTY-VTGX UTY-VTGXV UTY-VMSX Compact cassette ◌ ◌ ◌ ◌ Mini duct ◌ ◌ ◌ ◌ Slim duct ◌ ◌ ◌ ◌ Medium static pressure duct ◌ ◌ ◌ ◌ Floor ◌...
  • Page 362 Type Indoor unit type WLAN Adapter* UTY-TFSXW1 UTY-TFSXF2 UTY-TFSXZ1 UTY-TFSXH3 UTY-TFSXJ3 Compact cassette — — ◌ — — Mini duct — — ◌ — — Slim duct — — ◌ — — Medium static pressure duct — — ◌ — ◌...
  • Page 363 Type Indoor unit type Long-life Filter External Input and Output PCB Box UTD-LFDC UTZ-GXDA Compact cassette — — Mini duct — — Slim duct — — Medium static pressure duct ◌ ◌ Floor — — KMCC — — KMCE — —...
  • Page 364 ¢ Parts Exterior Part name Model name Summary Thermo-sensor for sensing the Remote Sensor temperature of arbitrary place in the UTY-XSZX Unit room. Thermo-sensor for sensing the Remote Sensor temperature of arbitrary place in the UTY-XSZXZ* Unit room. Width: 683 mm Auto Louver UTD-GXTA-W Grille Kit...
  • Page 365 Exterior Part name Model name Summary Half Concealed Used for the indoor unit installing of UTR-STA half concealed. Communication Use to connect with optional devices UTY-TWBXF2 and air conditioner PCB. Use to connect with external devices External Input and air conditioner PCB. UTY-XCSX and Output PCB Use to connect with external devices...
  • Page 366 Exterior Part name Model name Summary Remotely manage an air conditioning system using mobile devices such as smartphones and tablets. WLAN Adapter UTY-TFSXW1 Appropriate application for each region is required to use this option. For details, contact FGL sales company. Remotely manage an air conditioning system using mobile devices such as smartphones and tablets.
  • Page 367 18. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 18-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 368 Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 30 °C RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
  • Page 369 Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 30 °C Figure 18-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
  • Page 370 - 364 - 18-2. Points to remember when installing 18. Indoor unit installation precautions...
  • Page 371 Part 2. OUTDOOR UNIT (2 UNITS TYPE) MULTI-SPLIT TYPE: AOHG14KBTA2 AOHG18KBTA2...
  • Page 372 1. Specifications Type Inverter heat pump Model name AOHG14KBTA2 AOHG18KBTA2 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Wall mounted Standard combination of indoor unit ASHG07KGTB ×2 ASHG09KGTB ×2 Rated Btu/h 13,600 17,100 Cooling 1.4—4.6 1.7—5.8 Min.—Max.
  • Page 373 Specifications for ErP Lot10 Model name AOHG14KBTA2 AOHG18KBTA2 Cooling Energy efficiency class Heating (Average) Cooling 4.0 (35 °C) 5.0 (35 °C) Pdesign Heating (Average) 3.5 (-10 °C) 4.2 (-10 °C) SEER Cooling 8.70 8.60 kWh/kWh SCOP Heating (Average) 4.70 Annual energy consumption kWh/a QHE (Average) 1,296...
  • Page 374 2. Dimensions 2-1. Model: AOHG14KBTA2 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow 19.7 Drain port Ø42 150.1 Bottom view Side view (Valve part) - 368 - 2-1. Model: AOHG14KBTA2 2.
  • Page 375 2-2. Model: AOHG18KBTA2 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow 19.7 Drain port Ø42 150.1 Bottom view Side view (Valve part) - 369 - 2-2. Model: AOHG18KBTA2 2. Dimensions...
  • Page 376 3. Installation space 3-1. Models: AOHG14KBTA2 and AOHG18KBTA2 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 377  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 378  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 379 4. Refrigerant circuit 4-1. Model: AOHG14KBTA2 - 373 - 4-1. Model: AOHG14KBTA2 4. Refrigerant circuit...
  • Page 380 4-2. Model: AOHG18KBTA2 - 374 - 4-2. Model: AOHG18KBTA2 4. Refrigerant circuit...
  • Page 381 5. Wiring diagram 5-1. Model: AOHG14KBTA2 - 375 - 5-1. Model: AOHG14KBTA2 5. Wiring diagram...
  • Page 382 5-2. Model: AOHG18KBTA2 - 376 - 5-2. Model: AOHG18KBTA2 5. Wiring diagram...
  • Page 383 6. Capacity table 6-1. Combinations ¢ Model: AOHG14KBTA2  Cooling Indoor unit combination (Wall-mounted KG/KM type only) Rated capacity for Combination of indoor Total capacity each indoor unit Input power (kW) Seasonal data unit (kW) (kW) (W/W) Unit Unit Pdesign SEER Energy effi- Total...
  • Page 384  Heating Indoor unit combination (Wall-mounted KG/KM type only) Rated capacity for Combination of indoor Total capacity each indoor unit (kB- Input power (kW) Seasonal data unit (kBtu/h) tu/h) (W/W) Unit Unit Pdesign SCOP Energy effi- Total Min. Rated Max. Min.
  • Page 385 ¢ Model: AOHG18KBTA2  Cooling Indoor unit combination (Wall-mounted KG/KM type only) Rated capacity for Combination of in- Total capacity each indoor unit Input power (kW) Seasonal data door unit (kW) (kW) (W/W) Unit Unit Pdesign SEER Energy efficien- Total Min.
  • Page 386  Heating Indoor unit combination (Wall-mounted KG/KM type only) Rated capacity for Combination of indoor Total capacity each indoor unit Input power (kW) Seasonal data unit (kW) (kW) (W/W) Unit Unit Pdesign SCOP Energy effi- Total Min. Rated Max. Min. Rated Max.
  • Page 387 6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOHG14KBTA2 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 388 NOTES: • TC: Total Capacity (kW), IP: Input Power (kW) • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit) •...
  • Page 389  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.22 2.04 1.39 2.15 1.60 2.30 1.79 2.46 1.96...
  • Page 390  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.25 2.04 1.42 2.15 1.64 2.30 1.84 2.46 2.01...
  • Page 391  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.25 2.04 1.42 2.15 1.64 2.30 1.84 2.46 2.01...
  • Page 392  Medium static pressure duct type Model: ARXH12KMTAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.28 1.54 2.58 1.75 2.72 2.02 2.91 2.27...
  • Page 393  Wall mounted type Models: ASHG07KMTB, ASHG07KMCC, ASHG07KMCE, ASHG07KMCF, ASHH07KMCG, ASH- H07KMCG-B, ASHH07KMCH, and ASHH07KMCH-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80...
  • Page 394 Models: ASHG07KETA, ASHG07KETA-B, ASHG07KETE, ASHG07KETE-B, ASHG07KETF, and ASHG07KETF-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.01 2.04 1.16 2.15 1.33 2.30 1.50...
  • Page 395 Models: ASHG07KGTB, ASHG07KGTE, ASHG07KGTF, ASHH07KGTG, and ASHH07KGTH Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.01 2.04 1.16 2.15 1.33 2.30 1.50 2.46...
  • Page 396 Models: ASHH05KNCA and ASHH05KNCH Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.41 0.79 1.59 0.90 1.68 1.04 1.80 1.17 1.92 1.28 1.98 1.47...
  • Page 397  Floor type Model: AGHG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.03 1.39 2.29 1.58 2.42 1.82 2.59 2.05 2.77 2.24 2.85...
  • Page 398 ¢ Model: AOHG18KBTA2 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 4.50 0.80 5.10 0.81...
  • Page 399 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 4.50 0.78 5.10 0.79 5.30 0.80 5.70...
  • Page 400  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 401  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 402  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 403  Medium static pressure duct type Model: ARXH12KMTAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.87 1.94 3.24 2.21 3.42 2.54 3.66 2.85...
  • Page 404  Wall mounted type Models: ASHG07KMTB, ASHG07KMCC, ASHG07KMCE, ASHG07KMCF, ASHH07KMCG, ASH- H07KMCG-B, ASHH07KMCH, and ASHH07KMCH-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96...
  • Page 405 Models: ASHG07KETA, ASHG07KETA-B, ASHG07KETE, ASHG07KETE-B, ASHG07KETF, and ASHG07KETF-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63...
  • Page 406 Models: ASHG07KGTB, ASHG07KGTE, ASHG07KGTF, ASHH07KGTG, and ASHH07KGTH Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67...
  • Page 407 Models: ASHH05KNCA and ASHH05KNCH Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.41 0.79 1.59 0.90 1.68 1.04 1.80 1.17 1.92 1.28 1.98 1.47...
  • Page 408  Floor type Model: AGHG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 409 6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOHG14KBTA2 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 3.30...
  • Page 410 NOTES: • TC: Total Capacity (kW), IP: Input Power (kW) • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit) •...
  • Page 411  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66 2.60 2.54...
  • Page 412  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66 2.60 2.54...
  • Page 413  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66 2.60 2.54...
  • Page 414  Medium static pressure duct type Model: ARXH12KMTAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.11 2.06 2.01 1.95 1.90 -10.0 -11.0 2.38 2.32 2.26 2.21 2.15 -5.0 -7.0 2.65 2.58 2.52 2.46 2.39 -2.0 3.36...
  • Page 415  Wall mounted type Models: ASHG07KMTB, ASHG07KMCC, ASHG07KMCE, ASHG07KMCF, ASHH07KMCG, ASH- H07KMCG-B, ASHH07KMCH, and ASHH07KMCH-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0...
  • Page 416 Models: ASHG07KETA, ASHG07KETA-B, ASHG07KETE, ASHG07KETE-B, ASHG07KETF, and ASHG07KETF-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66...
  • Page 417 Models: ASHG07KGTB, ASHG07KGTE, ASHG07KGTF, ASHH07KGTG, and ASHH07KGTH Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66 2.60...
  • Page 418 Models: ASHH05KNCA and ASHH05KNCH Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.27 1.24 1.21 1.18 1.15 -10.0 -11.0 1.44 1.40 1.37 1.34 1.30 -5.0 -7.0 1.60 1.56 1.53 1.49 1.45 -2.0 2.03 1.98 1.94 1.89 1.84...
  • Page 419  Floor type Model: AGHG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.87 1.83 1.79 1.74 1.70 -10.0 -11.0 2.12 2.07 2.02 1.96 1.91 -5.0 -7.0 2.36 2.30 2.24 2.19 2.13 -2.0 2.99 2.92 2.85 2.78...
  • Page 420 ¢ Model: AOHG18KBTA2 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 4.00 1.63 3.90 1.67 3.80 1.70 3.70 1.73 3.60 1.77 -10.0 -11.0 4.60 1.68 4.40 1.72 4.30...
  • Page 421 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 3.20 1.22 3.10 1.24 3.00 1.27 2.90 1.30 2.90 1.32 -10.0 -11.0 3.60 1.26 3.60 1.28 3.50 1.31 3.40 1.34...
  • Page 422  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63 2.56 2.50...
  • Page 423  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63 2.56 2.50...
  • Page 424  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63 2.56 2.50...
  • Page 425  Medium static pressure duct type Model: ARXH12KMTAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.50 2.44 2.38 2.32 2.26 -10.0 -11.0 2.88 2.81 2.74 2.67 2.60 -5.0 -7.0 3.25 3.18 3.10 3.02 2.94 -2.0 4.15...
  • Page 426  Wall mounted type Models: ASHG07KMTB, ASHG07KMCC, ASHG07KMCE, ASHG07KMCF, ASHH07KMCG, ASH- H07KMCG-B, ASHH07KMCH, and ASHH07KMCH-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0...
  • Page 427 Models: ASHG07KETA, ASHG07KETA-B, ASHG07KETE, ASHG07KETE-B, ASHG07KETF, and ASHG07KETF-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63...
  • Page 428 Models: ASHG07KGTB, ASHG07KGTE, ASHG07KGTF, ASHH07KGTG, and ASHH07KGTH Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63 2.56...
  • Page 429 Models: ASHH05KNCA and ASHH05KNCH Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.19 1.16 1.13 1.10 1.07 -10.0 -11.0 1.37 1.33 1.30 1.27 1.24 -5.0 -7.0 1.55 1.51 1.47 1.44 1.40 -2.0 1.97 1.92 1.88 1.83 1.78...
  • Page 430  Floor type Model: AGHG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.04 1.99 1.94 1.89 1.84 -10.0 -11.0 2.34 2.29 2.23 2.18 2.12 -5.0 -7.0 2.65 2.59 2.52 2.46 2.40 -2.0 3.38 3.30 3.22 3.14...
  • Page 431 7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOHG14KBTA2 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 432 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.924 0.891 — — 0.962 0.931 0.899 Indoor unit is higher than outdoor unit *1 — 0.991 0.968 0.938 0.905 0.993 0.993 0.970 0.940 0.907 1.000 1.000 0.977 0.946 0.913 -2.5 1.000...
  • Page 433 7-2. Model: AOHG18KBTA2 NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Indoor unit: 5,000 Btu/h and 7,000 Btu/h Pipe length Cooling — — — 0.940 0.914 — — 0.973 0.948 0.921 Indoor unit is higher than outdoor unit *1 —...
  • Page 434 ¢ Indoor unit: 12,000 Btu/h Pipe length Cooing — — — 0.919 0.883 — — 0.962 0.926 0.891 Indoor unit is higher than outdoor unit *1 — 0.991 0.969 0.933 0.897 0.993 0.993 0.971 0.935 0.899 1.000 1.000 0.978 0.941 0.905 -2.5 1.000...
  • Page 435 8. Additional charge calculation 8-1. Model: AOHG14KBTA2 Refrigerant type Refrigerant amount ¢ Refrigerant charge Total pipe length 20 or less 30 (Max.) 20 g/m Additional charge 8-2. Model: AOHG18KBTA2 Refrigerant type Refrigerant amount 1,020 ¢ Refrigerant charge Total pipe length 20 or less 30 (Max.) 20 g/m...
  • Page 436 9. Airflow 9-1. Model: AOHG14KBTA2  Cooling 1,670  Heating 1,670 9-2. Model: AOHG18KBTA2  Cooling 1,960 1,154  Heating 2,020 1,189 - 430 - 9-1. Model: AOHG14KBTA2 9. Airflow...
  • Page 437 10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOHG14KBTA2  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 438 10-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 432 - 10-2. Sound level check point 10. Operation noise (sound pressure)
  • Page 439 11. Electrical characteristics Model name AOHG14KBTA2 AOHG18KBTA2 Voltage 230 ~ Power supply Frequency 10.9 11.6 Maximum operating current * Starting current Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 440 12. Safety devices Model Type of Protection form protection AOHG14KBTA2 AOHG18KBTA2 250 V, 5 A 250 V, 5 A Current fuse Circuit protection 250 V, 20 A 250 V, 25 A (Main PCB) 250 V, 3.15 A 250 V, 3.15 A 127 ±5 °C 125 ±10 °C Activate...
  • Page 441 13. Accessories 13-1. Models: AOHG14KBTA2 and AOHG18KBTA2 Part name Exterior Part name Exterior Installation manual Drain pipe - 435 - 13-1. Models: AOHG14KBTA2 and AOHG18KBTA2 13. Accessories...
  • Page 442 14. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 14-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.