BMS-TP0640ACE BMS-TP0640PWE BMS-TP5120ACE BMS-TP5120PWE • Thank you very much for purchasing the TOSHIBA Touch Screen Controller. • Please read this manual carefully beforehand for proper installation of the controller. CONTENTS 1 Precautions for Safety ......................1 2 Outline of Control System ......................2 3 Accessory parts ........................
Precautions for Safety • Ensure that all Local, National and International regulations are satisfied. • Read these “Precautions for Safety” carefully before installation. • The precautions described below include important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the controller to the customer.
When installed this Air Conditioning Control System in a Toshiba air conditioner, enables easy central control of up to 64 (for BMS-TP0640ACE, BMS-TP0640PWE) or up to 512 (for BMS-TP5120ACE, BMS- TP5120PWE) indoor units with multi-functions integrated into the controller. This system allows advanced, operation control, and power-saving operation for medium to large buildings.
Selection of Installation place WARNING Install the Touch Screen Controller securely in a place that can sufficiently withstand the weight of the controller. If the foundation is not sturdy enough, the controller may fall and cause injury. Perform specified installation work to guard the controller against earthquakes. Improper installation may cause the controller to fall.
Points for Installation Work Work flow Process Point (Before work) • Clarify work categories. Determination of installation • Determine items of detail control. condition • Determine the installation position of the Touch Screen Controller. • Create a control wiring diagram (see page 9). •...
Page 6
Points for Installation Work (continued) Management zone categories Indoor Unit Block Tenant Area Group/Unit (line address + indoor unit address) Building A Tenant A Shop A 1 0 1 1 - 1 (header unit) 1 - 2 (follower unit) 1 0 2 1 - 3 (header unit) 1 - 4 (follower unit) 1 0 3...
Connecting the Network wires Connect the Touch Screen Controller to Intelligent Servers and to an optional PC for creating monthly reports using network wires (category 5UTP straight wire), via a Switching HUB (procured on site). • Connect the Ethernet port of the controller to a port of the HUB with a network wire. •...
Connecting the Power cable CAUTION Connect a proper input AC voltage to the power input terminal block. Failure to do so may cause a failure. REQUIREMENT Power cable is not supplied for the Touch Screen Controller. Prepare a 3-pin power cable conforming to applicable safety standards.
Page 9
■ ■ ■ ■ ■ Specifications [Input] Input system : Current-driven input insulated by photo-coupler Input resistance : 3 k ohms Number of input signals External circuit power voltage : 12 to 24 V DC (±10%) [Output] Output system : Open-collector output insulated by photo-coupler Output rating : 30 V DC, 100 mA maximum Number of output signals...
Installation Touch Screen Controller Make space for installation and service. Install the Touch Screen Controller in a wall (standard) or on the dedicated stand (when available on site). In-wall installation ■ ■ ■ ■ ■ Conditions for installation ■ ■ ■ ■ ■ Attaching Fixture ■Panel cut size Space 30 mm or more between the controller and surrounding objects as the ambient temperature...
Trial Operation Item Description Check point ● Meeting with the customer on setting information Preparation Preparation of necessary documents Creation of control wiring system diagram Creation of air conditioner address table Creation of schedule table for each R.C. group/indoor name ●...
Trouble shooting Regarding faults that may occur after installation, trial operation, and adjustments of Air conditioning control system and their remedies: Faults of air conditioner • The Touch Screen Controller displays an error code and description that are the same as those displayed on the remote controller.
Other faults Description Possible causes Remedy Nothing is displayed on Touch Screen Controller is not powered on. Power on the Touch Screen Controller. the Touch Screen Backlight turns off automatically due to no Touch the Touch Screen Controller screen. touch-screen operation for 10 minutes. Controller screen.
Control Specifications Basic Functions Function Item Description ●ON/OFF Operation Master operation and setting of: - Entire building Setting Operation mode (cooling/ - Each block * heating/fan only) - Each tenant * Air flow (High/Mid/Low) - Each area * Temperature (18-29 °C) - Each R.C.
APPENDIX Touch Screen Controller System Configuration RS-485 Ethernet TCC-LINK Main Bus TCS-NET Relay I/F InteIligent Server (BMS-IFLSV1E) (BMS-LSV2E) Max. 512 indoor Max. 64 air conditioners units (64 units x 8) per relay I/F Touch Screen Controller per Intelligent Compact (BMS-TP0640/5120) Flash Server TCC-LINK Main Bus...
Page 23
APPENDIX System Configuration Table ... available – ... not available) Touch Screen Controller BMS-TP0640ACE BMS-TP0640PWE BMS-TP5120ACE BMS-TP5120PWE Air conditioning control Power distribution – – Indoor units connected Max. 64 units Max. 512 units Intelligent Server 1 unit Max. 4 units...
APPENDIX Wiring Specifications Power supply specifications Device Input voltage Power Power cable Remarks wire size consumption Touch Screen Controller 100 - 240 V, AC 50/60 Hz 50 VA 0.75 mm Procure on site Intelligent Server 85 - 132 V, AC 50/60 Hz 30 VA 180 - 264 V, AC 50/60 Hz TCS-NET Relay Interface...
APPENDIX Address Setting Flow Setting flow Contents Reference page. Indoor units/Outdoor units Power on page 10 Setting from main wired remote controller Manual address setting (Line/Group/Indoor address setting) Dip Switch setting on outdoor interface page 12 Line address setting P.C.board Power reset Power reset to activate line address page 12...
APPENDIX Address Setting for Component Device Intelligent Server Installing CF (Compact Flash) card WARNING • Do not insert or remove the CF (Compact Flash) card during power on of the Intelligent Server. Doing so may cause a failure. • If the CF (Compact Flash) card is not inserted properly, the Intelligent Server does not work. Insert the attached CF (Compact Flash) card fully into the CF (Compact Flash) card slot on the side of the Intelligent Server.
APPENDIX Address Setting for Component Device (continued) TCS-NET Relay Interface address setting The following settings are necessary to use TCS-NET Relay Interfaces. • SW1 Relay interface address set switch When two or more TCS-NET Relay Interfaces are used, set a different address for SW1 to avoid address duplication.
APPENDIX Air conditioner address setting (example) CAUTION To control air conditioners by the Touch Screen Controller, set the air conditioner addresses as R.C. group/indoor for each TCS-NET Relay Interface.
APPENDIX Address Setting for Air Conditioner Setting for VRF system In this air conditioner, it is required to set up address to the indoor unit before starting operation. Set up the address according to the following setup procedure. CAUTION 1. Set up address after wiring work. 2.
APPENDIX Manual setting from wired remote controller CAUTION Be sure to allocate Line (system) /Group/Indoor address one by one to match the address setting table and setup file that is prepared beforehand. If wrong value is set, a problem such as error of communication with air conditioner will occur. Dip Switch setting Header Line address...
APPENDIX Address Setting for Air Conditioner (continued) (Step 2) Note ) When setting the line address from the remote controller, do not use address 29 and 30. The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a check code [E04] (Indoor/outdoor communication circuit error) is output.
APPENDIX Line (system) address setting Header unit interface P.C. board 1. Using SW13 and 14 on the interface P.C. board of the header unit in each system, set 2 3 4 2 3 4 2 3 4 2 3 4 up the system address for each system.
APPENDIX Address Setting for Air Conditioner (continued) Indoor unit address check Step Item Operation and check contents Power - on Initial communication takes a couple of minutes. During initial communication, 7-segment display section is as follows as follows. Display [A] --- [U1], flashing Display [B] --- [ - - 0] --> [ - - i] flashing Display check After initial communications, [U1] are displayed in 7-segment display section.
APPENDIX Setup of relay connector and terminator • After trial operation for each R.C. group/indoor, set the relay connector and terminator resistor for all R.C. group/indoor which are connected from one TCS-NET relay interface. Header outdoor unit interface P.C. board <Procedure>...
Page 36
APPENDIX Address Setting for Air Conditioner (continued) TCS-NET relay Header interface Follower unit Follower unit Header unit Header unit unit U3 U4 U3 U4 U3 U4 U3 U4 U3 U4 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6...