Te s t i n g ( E m e r g e n c y Ve r s i o n s )
The emergency light must be tested and inspected regularly in accordance with local codes of practice.
NOTE: For safety reasons tests should be carried out preceeding time of low risk, to allow for battery recharge.
The minimum recommended test schedule is as follows:
Commisioning - After installation, allow 36 hours to ensure full battery charge, and then interrupt the supply; check after 3 hours that the lamp is still illuminated.
1. Daily - Check that the charge indicator LED is working.
2. Monthly - Interrupt the power supply for a period sufficient to ensure each lamp is illuminated. At the end of the test, restore the supply and check the
indicator is illuminated.
3. Annually - Interrupt the supply as in 2, but for the full rated duration. Ensure the lamp is illuminated at the end of the rated duration. Restore the supply and
check the indicator is illuminated.
4. Record the date and result of each test, attending to any maintenance required in the event of a test failure.
L u m i n a i r e L o c a t i o n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D a t e Co m m i s i o n e d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Month
Test
Signed
1
Functional
2
Functional
3
Functional
4
Functional
5
Functional
6
Functional
7
Functional
8
Functional
9
Functional
10
Functional
11
Functional
Full
12
Duration
INS/EMERGENCY_TESTING_SHEET/V1
INSTALLATION INSTRUCTIONS
Emergency Testing Sheet
Year 1
Result /
Date
Action
Red Arrow Electrical Limited
Cortonwood Drive, Brampton,
Barnsley, S73 0UF
D a t e I n s t a l l e d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Year 2
Result /
Signed
Date
Action
T: 0800 195 0006
sales@redarrowelectrical.co.uk
Year 3
Result /
Signed
Date
Action
redarrowelectrical.co.uk

Advertisement

loading
Need help?

Need help?

Do you have a question about the Slimline WPS Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Red Arrow Slimline WPS Series

  • Page 1 Result / Signed Date Signed Date Signed Date Action Action Action Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Full Duration INS/EMERGENCY_TESTING_SHEET/V1 Red Arrow Electrical Limited T: 0800 195 0006 redarrowelectrical.co.uk Cortonwood Drive, Brampton, sales@redarrowelectrical.co.uk Barnsley, S73 0UF...
  • Page 2 INSTALLATION INSTRUCTIONS WPS Slimline Wallpack Product Codes: WPS30, WPS30E, WPS30PC, WPS30EPC Safety Warning • • The installation should be carried out circuit breaker being turned off before Follow the provided installation by a qualified electrician in compliance installation or any maintenance. instructions, using the fixings supplied with the current edition of the IEE or recommended.
  • Page 3 Installation Instructions For Non-Emergency Version Ensure power is isolated. Select the correct supply cable type for outdoor use and suitable for the environment in which the fitting will be used. Use a screwdriver to release the screws holding the diffuser in position. Remove the diffuser and mount the body in the desired location using the fixings provided, ensuring the IP ratings are maintained.
  • Page 4 When this fitting comes to the end of it’s life or you choose to replace it, please do not dispose of it with your normal waste. Please recycle where the facilities exist, check with your local authority for suitable options. INS/OUTDOOR/0003/WPS/V3 Red Arrow Electrical Limited T: 0800 195 0006 redarrowelectrical.co.uk Cortonwood Drive, Brampton, sales@redarrowelectrical.co.uk...

This manual is also suitable for:

Slimline wps30Slimline wps30eSlimline wps30pcSlimline wps30epc