Red Arrow POLO 15W LED Installation Instructions Manual

Emergency bulkhead with microwave sensor

Advertisement

Quick Links

POLO 15W LED
Emergency Bulkhead with
Microwave Sensor
For models: POL15LEDEMS
This installation must be carried out by an electrician.
Please read these instructions carefully before installation.
Leave a copy for the user/maintenance engineer for future reference.

Specification

220-240V
15W
66pcs of 2835 LED
1100 Lumen output / 90lm in emergency mode
30,000 Hours life expectancy
4000K Colour temperature
Three years guarantee
Dimensions: Ø: 326 x D: 108mm

Description of Microwave Sensor

The microwave sensor option offers presence
detection to provide automatic control of lighting
loads. It is installed inside the luminaire so does
not affect external aesthetics or the IP Rating.
Manual adjustments on the sensor allow it to be
individually tailored to suit your application.

Safety

This is a mains powered product. It is designed to be
installed by a qualified electrician and in accordance
with the applicable building and electrical
regulations. Before installation or maintenance the
electrical supply to the product must be isolated.
Installation Instructions
Remove the diffuser & trim from the base by rotating anti-
clockwise to unlatch then pull away.
Loosen the three gear tray retaining screws, rotate the gear
tray anti-clockwise to align the screw heads with the large
aperture of the keyhole slots & remove the gear tray
away from the base. There is a retaining strap to assist with
installation.
Prepare the mains supply cable & fixing points on the chosen
mounting surface ensuring it is able to retain the weight of
the luminaire.
Red Arrow Trading
Elsworth House, Herries Road South, Sheffield, S6 1QS
Pass the mains supply cable through the hole & grommet
provided in the base, position the base to the mounting
surface & secure using the screws provided.
It is the installer's responsibility to ensure the fixing points
& cable entry point are appropriately sealed to maintain
the IP54 rating. Silicone bathroom sealant or equivalent is
recommended.
Route the mains supply cable to the terminal block on the
gear tray & terminate ensuring correct polarity is observed.
WARNING: THIS LUMINAIRE MUST BE EARTHED.
It is important that supply cables fitted to luminaires with an
electronic ballast do not run adjacent to leads connected to
the ballast output terminals so as not to affect radio
frequency interference suppression.
Secure the supply cable using the clamp provided in the base.
Refit the gear tray & secure by retightening the screws.
Refit the diffuser & trim by placing over the base & rotating
clockwise until it locks into position.
Reconnect power supply & check for correct operation.
Luminaires fitted with electronic ballasts are exempt from
insulation resistance tests as this may cause damage to the
ballast.
Further Instructions for Emergency
version
In addition to the above instructions, a secondary "un-
switched" live supply should be fed to the luminaire, in line
with the "switched" mains supply. This "un-switched" supply
MUST be taken from the same phase as the "switched"
supply & MUST be wired at the switchboard so that upon
test, it is isolated at the same time as the "switched" supply.
Route to the terminal block & terminate, ensuring correct
polarity is observed.
Connect the battery supply to the module by joining the
connectors, ensuring correct polarity is observed.
T: 0800 195 0006
E: sales@redarrowtrading.com
F: 0870 043 3946
www.redarrowtrading.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the POLO 15W LED and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Red Arrow POLO 15W LED

  • Page 1 POLO 15W LED Emergency Bulkhead with Microwave Sensor Installation Instructions p.1 For models: POL15LEDEMS This installation must be carried out by an electrician. Please read these instructions carefully before installation. Leave a copy for the user/maintenance engineer for future reference.
  • Page 2 POLO 15W LED Emergency Bulkhead with Microwave Sensor Installation Instructions p.2 For models: POL15LEDEMS • When power supply is reconnected, check the green LED fitted to the luminaire illuminates. This indicates that the batteries are charging. • The batteries should be allowed to charge for at least 24 hours before carrying out a full discharge test to check batteries are charging correctly &...
  • Page 3 POLO 15W LED Emergency Bulkhead with Microwave Sensor Installation Instructions p.3 For models: POL15LEDEMS TESTING LOG BOOK Luminaire Type: ..............Luminaire Location / No: ..........Month Test Year 1 Year 2 Year 3 Year 4 Year 5 signed date signed...
  • Page 4 POLO 15W LED Emergency Bulkhead with Microwave Sensor Installation Instructions p.4 For models: POL15LEDEMS Positioning • The luminaire with detector should be sited so that the occupants of the room fall inside the detection patterns shown in the appropriate diagram below.
  • Page 5 POLO 15W LED Emergency Bulkhead with Microwave Sensor Installation Instructions p.5 For models: POL15LEDEMS The LED setting indicator will flash to indicate the setting selected as follows: No. of Flashes Setting Length 10 seconds 1 minute 2 minutes 5 minutes...
  • Page 6 POLO 15W LED Emergency Bulkhead with Microwave Sensor Installation Instructions p.6 For models: POL15LEDEMS • Ensure luminaire is not connected in parallel with other luminaires containing MW sensors. MAINTENANCE • Cleaning should be carried out at regular intervals so as not to impair photometric performance or thermal safety of the luminaire.

This manual is also suitable for:

Pol15ledems

Table of Contents