Red Arrow ANA/30 Installation Instructions

Athena m/nm exit sign

Advertisement

Quick Links

Safety Warning

The installation should be carried out
by a qualified electrician in compliance
with the current edition of the IEE
Wiring Regulations.
Prior to installation, carry out the
necessary risk assessment considering
the people who could be at risk,
the level of risk and the precautions
required to control the risk
Ensure that the circuit supply is
isolated either by the circuit supply
fuse being removed or the applicable

Specification

Box Contents -
1 x Exit Sign c/w Blade Style Up Arrow Legend./ST Version with Self Test Functionality.
Dimensions:
H: 212 x W: 313 x D: 42mm
Material:
Polycarbonate
Colour
6500K
Temperature:
CRI:
Ra>80
LED Lifetime:
L70B50 36,000 Hrs
IP Rating:
IP20
Working
0°C to 45°C
Temperature:
5 Years
5
2.2
YR
WATT
GUARANTEE
Installation Instructions
1.
Isolate the mains supply before carrying out any installation or maintenance work.
2.
Remove the front cover from the fitting. Using a flat blade screwdriver, turn the locking screw a quarter turn anti-clockwise until it lines up with open
padlock symbol, then remove front from base.
3.
Drill out the preferred fixing points and cable entry on the base for either wall or ceiling mounting. Fix the base to the wall or ceiling in the desired location,
using the fixings supplied and passing the supply cable through the cable entry point. Ensure that a suitable grommet or similar is used at the cable entry
point.
2
INSTALLATION INSTRUCTIONS
Athena M/NM Exit Sign (/ST Version with Self Test)
Product Codes: ANA/30 & ANA/30/ST
IP20
6500K
circuit breaker being turned off before
installation or any maintenance.
Check the total load on the circuit
ensuring the luminaire does not exceed
the rating of the circuit cable, fuse or
circuit breaker.
Long-term use and voltage fluctuations
can reduce the life span of the fitting.
If the fitting incorporates control gear,
ensure careful sizing to avoid instances
of nuisance tripping of the protective
device used in the installation.
LED
230V
3
Ceiling
Follow the provided installation
instructions, using the fixings supplied
or recommended.
Keep out of reach of children.
W313mm
D42mm
Wall

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ANA/30 and is the answer not in the manual?

Questions and answers

Summary of Contents for Red Arrow ANA/30

  • Page 1 INSTALLATION INSTRUCTIONS Athena M/NM Exit Sign (/ST Version with Self Test) Product Codes: ANA/30 & ANA/30/ST Safety Warning • • The installation should be carried out circuit breaker being turned off before Follow the provided installation by a qualified electrician in compliance installation or any maintenance.
  • Page 2 Instructions for use supplied with each kit. Self Test Version Only ANA/30/ST features stand alone automatic self test operation. After the power supply has been connected and the batteries have charged for 24 hours, the fitting will perform the following tests automatically, which meet and exceed legal requirements.
  • Page 3 When this fitting comes to the end of it’s life or you choose to replace it, please do not dispose of it with your normal waste. Please recycle where the facilities exist, check with your local authority for suitable options. INS_EMERGENCY_0021_ANA_V1 Red Arrow Electrical Ltd T: 0800 195 0006 redarrowelectrical.co.uk Cortonwood Drive, Brampton, sales@redarrowelectrical.co.uk...
  • Page 4 Result / Signed Date Signed Date Signed Date Action Action Action Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Full Duration INS/EMERGENCY_TESTING_SHEET/V2 Red Arrow Electrical Ltd T: 0800 195 0006 redarrowelectrical.co.uk Cortonwood Drive, Brampton, sales@redarrowelectrical.co.uk Barnsley, S73 0UF...