1. Description ▪ Seamless integration with popular third-party flow computers ▪ Pressure types: differential (DP) and static absolute (SP) The OleumTech H Series Multivariable Transmitter is a versatile 3-in-1 instrument designed to deliver precise measurements of both differential ▪ Measurement range:...
Page 4
WARNING: If the equipment is used in a manner not specified by OleumTech, the protection provided by the equipment may be impaired. WARNING: Safety of any system incorporating the transmitter is the responsibility of the assembler of the system.
Page 5
à fortes vibrations ou là où le transmetteur est soumis à de graves chocs mécaniques. AVERTISSEMENT: si l'équipement est utilisé d'une manière non spécifiée par OleumTech, la protection fournie par l'équipement peut être altérée. Page 5...
Page 6
The standard details requirements for the selection and material qualifications. NACE does not provide product certification services. OleumTech Multivariable Transmitters use 316 SS, 316L SS and Hastelloy C in wetted metal applications and connection components, and conforms to NACE MR0175 metallurgical recommendations and requirements.
MULTIVARIABLE TRANSMITTER - USER GUIDE 5. Special Conditions of Use (Special Conditions) Conditions of Acceptability: Temperature code depends on process temperature as follows: Copies of Certificate of Compliance are available on https://hseries.oleumtech.com (Look under Resources) T-Code Ambient Temperature Process Temperature Gas, Vapor &...
Page 8
MULTIVARIABLE TRANSMITTER - USER GUIDE 6. Differential Pressure Range and Overload Lower Range Value Upper Range High & Low Pressure Nominal Range (LRV) Value (URV) Side Overload Limit 25 inH2O -25 inH2O 25 inH2O 3600 psi 250 inH2O -250 inH2O 250 inH2O 3600 psi 1000 inH2O...
Page 9
MULTIVARIABLE TRANSMITTER - USER GUIDE 8. Technical Specifications Damping Time Damping Time: 0-5 Seconds Diaphragm Time of Sensor Capsule (isolation sensor diaphragm and a. Measurement Range silicon filling oil): ≤ 0.2 Seconds DP: 25 to 4000 inH2O Start After Power Off: ≤ 6 Seconds SP (high side): 400 to 6000 psia Normal Service After Data Recovery: ≤...
Page 10
MULTIVARIABLE TRANSMITTER - USER GUIDE m. Surge Protection Environmental The transmitter has been tested to withstand a transient surge up to Operating Temperature: 2000 V (common mode) or 1000 V (normal mode) without damage -40 to 85 °C (-40 to 185 °F) / LCD -20 to 70 °C (-4 to 158 °F) (Per IEC Std.
Page 11
MULTIVARIABLE TRANSMITTER - USER GUIDE EMC Environment NO. Test Items Basic Standards Test Conditions Performance Level Radiated interference CISPR22 30 MHz - 1000 MHz Conducted interference (DC power port) CISPR22 0.15 MHz - 30 MHz Electrostatic discharge immunity test (ESD) IEC61000-4-2 4 kV (Contact), 8 kV (Air) B(Note)
MULTIVARIABLE TRANSMITTER - USER GUIDE 9. Menu Functions e. Unit a. Output Type Unit Definition Pascals Output Signal Kilopascals RS485 (3095 serial communications emulation) Megapascals b. LCD Display Units mBAR MilliBAR Pounds per square inch Display mode Details Pounds per square foot Millimeter of mercury @ 0 ℃...
Page 13
MULTIVARIABLE TRANSMITTER - USER GUIDE 10. Product Selection Guide Ordering Information Page 13...
Page 14
MULTIVARIABLE TRANSMITTER - USER GUIDE b. Flange Options (Process Connection), 1/4”-18 NPT(F) 316 SS d. Wet Parts Items Description Drain valve on rear end Diaphragm Hastelloy C of flange material 316L SS (Default) Drain valve on upper end of flange Drain valve on down end of flange Drain valve in the middle...
MULTIVARIABLE TRANSMITTER - USER GUIDE 2. PRODUCT DIMENSIONS / MOUNTING / INSTALLATION Drawings and Dimensions of HMVSxxxx (inches / mm). Page 15...
Page 16
MULTIVARIABLE TRANSMITTER - USER GUIDE b. Wall or 2” Pipe Mounting Kit (inches / mm). Housing Rotation Part number: SX1000-MK10 To improve field wiring access or provide better viewing of the LCD display, the housing and sensor can be slightly rotated from each Provided MVS Transmitter mounting bolt size: 7/16”-20UNF other.
Page 17
MULTIVARIABLE TRANSMITTER - USER GUIDE d. Cable Protection Conduit When using Explosion-proof pressure transmitters in hazardous locations, a metal Explosion-proof conduit should be used to connect the cable into the threading box, and lead to a non-hazardous location. WARNING: Do not open when an explosive atmosphere is present. Zero Point Calibration 1.
MULTIVARIABLE TRANSMITTER - USER GUIDE 3. HARDWARE OVERVIEW 1. Enclosure All housing entries MUST be tightly SEALED using thread seal tape or sealant. Failure to seal all port entries may allow moisture to enter the transmitter housing, cause damage to internal components, and void warranty.
Page 19
MULTIVARIABLE TRANSMITTER - USER GUIDE 2. External RTD Sensor OleumTech MVS Transmitter shown with RTD Temperature Probe Assembly, 10 ft Cable SS, Part# HW5000-RTD. RTD 4-Wire Wiring Page 19...
MULTIVARIABLE TRANSMITTER - USER GUIDE 4. POWER 1. Supply Voltage • 12 to 32 Vdc Max 2. Current Consumption • ≤ 720 mW @ 24 Vdc, 30 mA 3. Grounding • To avoid ground loops, shielded twisted pair signal cable is recommended.
6. THIRD-PARTY DEVICE INTEGRATION 1. The OleumTech MVS Transmitter is compatible with several variations of the 3095 serial communications emulation. 2. Please refer to the OleumTech MVS Application Note(s) for specific third-party integration instructions that are available on the H Series Download Center.
MULTIVARIABLE TRANSMITTER - USER GUIDE 7. LOCAL LCD DISPLAY INTERFACE b. Operation in Non-Hazardous Locations: 1. LCD Function The LCD-enabled transmitter provides an external 3-button (1, 2, 3) local display interface that allows the users to fully configure the device settings and parameters.
MULTIVARIABLE TRANSMITTER - USER GUIDE 2. LCD Functions PV Full Range Calibration Press 1 + 3 until the values are in full range. Home Button: press the Home button when device is in a locked state to toggle between device status views. Trim/Calibration Reset Press and hold external button 1 until options for resetting the trim data are shown.
Page 25
MULTIVARIABLE TRANSMITTER - USER GUIDE 3. LCD Menu Flow Chart Page 25...
Page 26
MULTIVARIABLE TRANSMITTER - USER GUIDE 4. Operating Instructions To unlock the menu system, press and hold the 2 button. Once the lock icon changes to the unlocked icon, then release button 2. Use button 2 to scroll through the menu system. Use button 3 to enter submenu system and apply changes.
Page 27
MULTIVARIABLE TRANSMITTER - USER GUIDE Configure the DP Upper Range Value DP Damping Time Configure the SP Pressure Unit Configure the NoUni = No Unit 10. cmH2O Unit Options: 11. inH2O 12. ftH2O 13. cmHg 14. mmHg mbar 15. inHg 16.
Page 28
MULTIVARIABLE TRANSMITTER - USER GUIDE SP Lower Range Value SP Upper Range Value Configure the SP Damping Time Configure the SP Output Mode Gauge Pressure Local Atm Pressure Page 28...
Page 29
MULTIVARIABLE TRANSMITTER - USER GUIDE Configure the Temperature Unit Unit Options: Celsius Fahrenheit Kelvin Rankine Temperature Lower Range Value Temperature Upper Range Value Page 29...
Page 30
MULTIVARIABLE TRANSMITTER - USER GUIDE Temp Fault Output Mode Configure the Slave Address Range: 1 to 247 (2 is default) Communication Baud Rate Configure the Options: 4800 9600 (default) 19,200 34,800 57,600 115,200 Page 30...
Page 31
MULTIVARIABLE TRANSMITTER - USER GUIDE Configure the Parity Mode Options: None (default) Even Configure the Stop Position 1 Stop Position Options: 2 Stop Position Configure the Delay Before Txd Configure the Modbus Protocol Configure the Float Data Type Select 3095 FB Rosemount or 267CS ABB Modbus mapping. Page 31...
MULTIVARIABLE TRANSMITTER - USER GUIDE 8. CALIBRATION 2. Restore Factory Calibration There are multiple ways to restore factory calibration to the OleumTech 1. Calibration MVS Transmitter. To restore the device to factory calibration, simply perform a factory reset Standard Process for Differential Pressure Calibration by powering down the device, pressing and holding the external button 3, and powering on the device.
• 1. General • Keep it dry and dust-free. The H Series transmitter is easy to maintain and does not require periodic • Do not expose it to corrosive medium. system checks. Sensor generally only needs a yearly visual inspection •...
10. LIMITED WARRANTY OleumTech warrants that goods described herein and manufactured by OleumTech are free from defects in material and workmanship for two (2) years from the date of shipment. b. OleumTech warrants that goods repaired by it pursuant to the warranty...
Default Slave ID changed to 2. Changed Transmitter mounting bolt size to 7/16”-20UNF from M10. OleumTech has made a good faith effort to ensure the accuracy of the Updated calibration section with revised 3 and 5-point calibration information while also adding information in this document and disclaims the implied warranties of application notes.