Download Print this page
Hide thumbs Also See for H Series:

Advertisement

Quick Links

1. Before You Begin
This guide provides basic informa�on to assist you in ge�ng
started. Go to hseries.oleumtech.com to download the
full User Guide for detailed installa�on and other informa�on.
WARNING!
EXPLOSION HAZARD – THIS DEVICE SHALL BE REMOVED
FROM THE AREA KNOWN TO BE HAZARDOUS IF
MAINTENANCE IS REQUIRED.
TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE
ATMOSPHERES, DISCONNECT POWER BEFORE SERVICING.
Ensure installa�on of the device meets applicable state
and na�onal electrical code requirements.
The installa�on of the transmi�er should only be performed
by a qualified installer or a factory representa�ve.
2. Power
- Power supply: 20-250 Vac 50/60 Hz or 20-250 Vdc
- Power consump�on: 5 VA (AC) / 2.5 W (DC) Max.,
120 Vac/30 mA or
24 Vdc/75 mA Normal Opera�on
3. Device Controls
PWR
SIGNAL
ALARM
SENSITIVITY
L
H
L
H
FACTORY
CALIBRATED
- Power indica�on: Red LED
On = Normal, Off = Power failure
- Signal indica�on: Green LED
On = Normal, Off = Alarm
- Alarm modes
High = For overfill protec�on
Normal state: Signal LED on, relay energized
Alarm state: Signal LED off, relay de-energized
Low = For dry run protec�on
Normal state: Signal LED on, relay energized
Alarm state: Signal LED off, relay de-energized
- Sensi�vity (Op�onal) / Factory default set to max
High = Level detec�on closer to the �p of the tuning fork
Low = Level detec�on farther away from the �p of the tuning fork
Tuning Fork Level Switches - HTF174x
4. Wiring
Relay Output (SPDT) (HTF174xR)
RT2 RT1 NC
COM
NO
N-
L+
RT1, RT2: Remote-Test
(Short RT1 and RT2 terminals to verify tuning
fork opera�on a�er installa�on)
NC, COM, NO: Relay Output
N-, L+: Power Supply
: Ground Connec�on
5. Operational Reference Table
ALARM HIGH
Over ow Protection
LEVEL
STATUS
Normal
Energized
RELAY
COM
ALARM OUTPUT
(SPDT RELAY)
NO
NC
ALARM OUTPUT
COM
NO
(SSR, MOSFET)
(On)
GREEN LED
BEHAVIOR
PNP/NPN Output (HTF174xN)
RT2 RT1
COM
NO
N-
L+
RT1, RT2: Remote-Test
(Short RT1 and RT2 terminals to verify tuning
fork opera�on a�er installa�on)
COM, NO: PNP/NPN Output
N-, L+: Power Supply
: Ground Connec�on
ALARM LOW
Dry Run Protection
Alarm Triggered /
Alarm Triggered /
Normal
Fork/Power Failure
Fork/Power Failure
De-Energized
Energized
COM
COM
NO
NC
NO
NC
COM
NO
COM
NO
COM
(O )
(On)
Quick Start Guide
80-3267-001_J
PNP/NPN Transistor Output
Relay
Coil
+
+
N P N
Relay
Relay
Coil
Coil
+
N P N
De-Energized
COM
NO
NC
NO
(O )
Relay
Coil
P N P
+
P N P

Advertisement

loading
Need help?

Need help?

Do you have a question about the H Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for OleumTech H Series

  • Page 1 PNP/NPN Output (HTF174xN) PNP/NPN Transistor Output This guide provides basic informa�on to assist you in ge�ng started. Go to hseries.oleumtech.com to download the full User Guide for detailed installa�on and other informa�on. WARNING! EXPLOSION HAZARD – THIS DEVICE SHALL BE REMOVED...
  • Page 2 Failure to seal all port entries may allow moisture to enter the transmi�er housing, cause ©2023 OleumTech Corpora�on. All rights reserved. OleumTech is a registered trademark of OleumTech Corpora�on damage to internal components, and void warranty.