Installation Instructions
Models F300R to F600R
This product needs to be installed properly in order to ensure maximum functionality as well as safety.
Please make sure to read this installation manual before starting the installation.
l Installation must be performed by a dealer or installation contractor. Please note that improper installation may cause malfunction or accident.
"Operating Instructions" and this manual must be handed over to the customer after completing the installation.

1. Safety precautions

The following signs indicate that death or serious injury may be caused by failure to heed the precautions described below.
WARNING
Do not modify or disassemble.
(It could cause fire, electric shock or injury.)
Do not
disassemble
The Lossnay unit and remote controller should not be
installed where it is highly humid, like a bathroom, or
other wet place.
Prohibition of use in
(It could cause electric shock or power leakage.)
bath or shower room
Connect the product properly to ground.
(Malfunctioning or power leaks can cause electrical shock.)
Connect the
grounding wire.
Use the specified power supply and voltage.
(Use of incorrect power supply or voltage could cause fire
or electric shock.)
Select a place with sufficient strength and install the
main unit securely.
The instructions
given must be
(It could cause injury if it falls.)
followed.
(For use by dealer/contractor)
Models F940R and F1200R
The instructions
given must be
followed.
Eng-1
Contents
1. Safety precautions ...........................................1
2. Outline drawings ..............................................3
3. Standard installation examples........................4
4. Installation method ..........................................4
5. Function settings ...........................................14
7. Trial operation ................................................29
Wiring work must be performed by qualified
professionals, and be implemented safely and securely
in accordance with the engineering standards and the
extension wiring rules for electrical equipment.
(Poor connection or improper wiring work could cause
electric shock or fire.)
Install a power supply isolator at the power supply
side as per local electrical regulations. All supply
circuits must be disconnected before obtaining
access to the terminal devices. Use the specified
cable size and connect the cables securely to prevent
disconnection when they are pulled.
(If there is a defect in the connection, there is a possibility
of fire.)
Select an adequate place for the opening to introduce
outdoor air, where it will not intake the exhaust fumes
like combustion gas, or others, and there is no risk of
blockage.
(Shortage of fresh air could put the room in a state of
oxygen deficiency.)
A duct made of steel must be installed with care not
to be connected electrically with metal, wire, stainless
steel plate, or others.
(It could cause fire when power leakage occurs.)
Not suitable for use with solid-state speed controls.
2109876H65903

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TRANE F300R and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mitsubishi Electric TRANE F300R

  • Page 1: Table Of Contents

    2109876H65903 Lossnay Energy Recovery Ventilator MODELS: TLGHF0300RVX02A / LGH-F300RVX2-E (F300R) TLGHF0380RVX02A / LGH-F380RVX2-E (F380R) TLGHF0470RVX02A / LGH-F470RVX2-E (F470R) TLGHF0600RVX02A / LGH-F600RVX2-E (F600R) TLGHF0940RVX02A / LGH-F940RVX2-E (F940R) TLGHF1200RVX02A / LGH-F1200RVX2-E (F1200R) Installation Instructions (For use by dealer/contractor) Models F300R to F600R Models F940R and F1200R Contents 1.
  • Page 2 1. Safety precautions (continued) CAUTION Do not place a burning appliance in a place where it is Always use the specified suspension bolts, nuts and exposed directly to the air from the Lossnay unit. washers or correctly rated wire / chain hangers. (It could cause an accident as a result of incomplete combustion.) (Use of hardware with insufficient strength could result in Do not use at a place where it is exposed to high...
  • Page 3: Outline Drawings

    2. Outline drawings F300R to F600R Accessory parts Position where duct direction change is possible By-pass damper plate • Mounting small screws for duct Ceiling suspension fixture Air exhaust fan flanges ..........x16 (4-1/2×13/16 (4-13×20) oval) (exhaust air outlet) (return air) •...
  • Page 4: Standard Installation Examples

    3. Standard installation examples * Except the F940R and F1200R • Duct length Return air grille Model Distance (not Included) F300R and F380R 3.3 ft (1 m) or more F470R and F600R 8.2 ft (2.5 m) or more EA (exhaust air outlet) F940R and F1200R 9.8 ft (3 m) or more Lossnay unit •...
  • Page 5 4. Installation method (continued) 4.2 Duct works 4.1.3 Preparing the anchor bolts Mount the washers (outer diameter of >13/16 inch for 3/8-16 UNC 4.2.1 Connecting the ducts (21 mm for M10) >15/16 inch for 7/16-14 UNC (24 mm for M12) and nuts onto the pre-recessed anchor bolts (3/8-16 or 7/16-14 (1) Fasten the duct securely to the duct connecting flange, and UNC (M10 or M12)), as shown in the figure below .
  • Page 6: Electrical Installation

    4. Installation method (continued) 4.3 Electrical installation • For F940R and F1200R, thermistors are built only in the lower unit. Lossnay unit controls its operation according to the With this product, the wiring installation method will vary according to lower unit detecting temperature. Even when actual return air the design of the system.
  • Page 7 4. Installation method (continued) Wire connection diagram * TM1, TM2, TM3, TM4, TB5 shown in dotted lines are field work. * Be sure to connect the ground wire. * A power supply isolator must be installed. * Always use an isolator for the main switch power connection. * Select proper circuit breaker according to the electrical current information in the chart below.
  • Page 8 4. Installation method (continued) 4.2.3 Connecting the power supply cable (3) Connecting the power supply cable and transmission cable Pass the Power supply cable through the bush* and connect to the (1) Remove the black screws and the control box cover TM1 terminal block using the round terminals.
  • Page 9 8 When using the remote/local switching and the ON/OFF input Remote controller (level signal) 9 When connecting to the City Multi or Mitsubishi Electric Air- Confirm that the pulse input switch (SW2-2) is set to “OFF”. Conditioner Network System (MELANS) (Factory setting is “OFF”.) (Refer to function settings...
  • Page 10 4. Installation method (continued) • Only one unit can be set as main Lossnay. The operating signal When the external device has an Volt-free contact signal and pulse signal of the external device can be connected to • If the input is pulse signal, move the pulse input switch [SW2-2] Main Lossnay only.
  • Page 11 4. Installation method (continued) • Install the duct heater separated from the product by a When switching By-pass externally. distance of 2.2 yd (2 m) or more. Failure to do so may result in equipment damage due to the Establish the wire connection by inserting the optional remote transmission of residual heat from the heater.
  • Page 12 SW2: ON/OFF switch X, Y : Relay (Contact rated load: 0.1 A at 15 VDC or more, Minimum applicable load: 1 mA or less) When connecting to the City Multi, Mitsubishi Electric Air- Conditioner Network System (MELANS) Lossnay external CAUTION...
  • Page 13 4. Installation method (continued) Control via Wi-Fi interface or MELCOBEMS MINI Connect the lead wire of a Wi-Fi interface or MELCOBEMS MINI to CN105 (Red) on circuit board of Lossnay unit. Regarding the model name of the connectable Wi-Fi interface or MELCOBEMS MINI, please contact the sales company in your market.
  • Page 14: Function Settings

    5. Function settings Change the function settings from the Address setting is required when connecting to City Multi and MELANS. remote controller TZ-62DR-EA. Setting the address Please refer to the Instruction book of TZ-62DR-EA for how to set the Use the following procedure when setting the address for dedicated Lossnay.
  • Page 15 5. Function settings (continued) Setting Data Factory DIP-SW No Function setting Indicator Indicator Indicator Indicator Filter maintenance and fan available available power up setting against filter — — — — — — — — — — — — — choking power up power up power up...
  • Page 16 5. Function settings (continued) Setting Data Factory DIP-SW No Function setting Automatic ventilation mode setting 1) Setting Data 0 to 7 -- > Temperature gap 0 K (0˚F) to 7 K (12.6˚F) — — — — — — — — —...
  • Page 17 5. Function settings (continued) Auto fan speed setting without Lossnay or Automatic recovery setting after power — No.5 M-NET system controller interruption When CO sensor is connected but any remote controller is not Sets for automatic recovery following power interruption. connected, SW 5-9 has to be ON in order to operate according to DIP-SW TZ-62DR-EA...
  • Page 18 5. Function settings (continued) - To use as the after-heater output, observe the cautions listed in 4 Delay start setting for air conditioner No.9 in the page 10. starting - For heater selection, observe the cautions listed in 4 in the page Delays Lossnay operation for 30 minutes when City Multi or Mr.
  • Page 19 5. Function settings (continued) Night-purge setting 3) No.28 No.32 Pulse input setting The lowest outdoor temperature Set external input signal type from external device for TM2. Set one of conditions for Night-purge start, maximum outdoor temperature within 72 hours. DIP-SW TZ-62DR-EA Setting Setting...
  • Page 20 5. Function settings (continued) Temperature exchange efficiency No.36 No.40, 41 Outdoor temperature display setting setting Set to display outdoor temperature detected by Lossnay unit Set the 10 digit of temperature exchange efficiency which is used to thermistor. calculate supply air temperature. This function is N/A from Lossnay unit DIP-SW.
  • Page 21 5. Function settings (continued) No.43 No.46 Indoor temperature correction Exhaust fan monitor threshold Set the correction for the indoor temperature displayed on the The threshold fan speed of exhaust fan monitor output can be TZ-62DR-EA screen by function selected. No. 37 This function is N/A from Lossnay unit DIP-SW.
  • Page 22 5. Function settings (continued) Example 2 Automatic ventilation mode setting 3) No.54 By-pass/Heat recovery ventilation map in automatic ventilation The lowest indoor temperature setting mode Set one of conditions for By-pass mode in auto ventilation operation, 104(40) minimum indoor temperature. This function is N/A from Lossnay unit DIP-SW.
  • Page 23 5. Function settings (continued) Pre-heater output setting 1) No.60 No.65 Fan speed for air volume “Low” input ON temperature Set the outdoor temperature for Pre-heater output ON. Set the fan speed setting when receiving “Low” signal from remote When detecting temp. becomes the setting or less, Pre-heater output controllers (e.g.
  • Page 24 - When installing the centralized management devices (including the system controller) in Mitsubishi Electric Air-Conditioner Network System (MELANS), perform emergency stop by the centralized management devices. In this case, do not use the function No. 69...
  • Page 25 5. Function settings (continued) No.73 -78, 87, 88 Airflow Adjust the output of the fan speed. This function can also be set on the Airflow settings screen of the TZ-62DR-EA. This function is N/A from Lossnay unit DIP-SW. TZ-62DR-EA TZ-62DR-EA TZ-62DR-EA Setting Setting...
  • Page 26 5. Function settings (continued) No.83, 84 No.89, 90 Filter maintenance interval setting sensor setting - maximum side Filter cleaning sign is displayed on the remote controller according to It is possible to set the CO concentration which fan speed turn into the set interval in this function.
  • Page 27 5. Function settings (continued) No.93 sensor correction concentration can be corrected when PZ-70CSW-E or PZ- 70CSB-E is connected. In this function, the control value of CO level is corrected. On the other hand, No. 44 is change the displayed CO level only.
  • Page 28: Check Points After Installation Work

    6. Check points after installation work After installation work has been completed, check the following points once again. If any failure is detected, be sure to fix it. Check the following points before trial operation, and place a check mark in the corresponding check box.
  • Page 29: Trial Operation

    • When delay start time is set (when City Multi or Mr. Slim that is connected using a Slim-Lossnay interlocking cable starts operating), check Lossnay operation after the delay start time has passed. 3.2 For MELANS system • Check Lossnay operation by using the Mitsubishi Electric Air-Conditioner Network System (MELANS). Eng-29...
  • Page 30 When an error code blinks on the remote controller, follow the procedures shown in the installation and operating manuals provided with the remote controller. n In case of operating Lossnay unit by external input, operate after approximately 2 minutes of turning on the power for the Lossnay. Mitsubishi Electric Trane HVAC US LLC 1340 Satellite Blvd., Suwanee, GA 30024 Eng-30...