  • Page 1 FX20 series Modular I/O System User Manual Ethernet/IP Version 1.1, 2025-01-07 Tianjin Elco Automation Co.,Ltd  ...
  • Page 2: Table Of Contents

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     CONTENT Product introduction .................... 3 Version change record ..................
  • Page 3 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.10. 16-channel DO NPN module wiring diagram and I/O process data 8.2.11.
  • Page 4: Product Introduction

                                                        1. Product introduction The FX20 series modular I/O system is a new generation IP20 extensible I/O product launched by Elco. It’s composed of bus adapters, I/O modules and functional modules, with a module least width of only 15mm, which is thin and compact, greatly saving space inside the control cabinet.
  • Page 5: Warranty Statement

     Use WeChat to search and subscribe the official account of "Elco Automation" to obtain the product manual.  Contact Elco sales engineers in your area to obtain the latest manual materials. 4. Warranty statement Under normal use, if the product malfunctions or is damaged, Elco will be responsible for an 18-month warranty (from and subject to the delivery date;...
  • Page 6: Safety And Tips

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Danger If not operated properly, it will result in death or serious bodily injury.
  • Page 7 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                      The programmable controller is an Open type device, please install...
  • Page 8: During Operation And Maintenance

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     power supply is stable. During operation and maintenance Caution ! ...
  • Page 9: Fx20 Product Introduction

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6. FX20 Product Introduction 6.1.
  • Page 10: Fx20 Ethernet/Ip Adapter Technical Specifications

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     System grounding Rotary code switches Set FX20 address 6.2.
  • Page 11: Fx20 Ethernet/Ip Adapter Profile Drawing

        FX20 adapter end cover FX20 adapter The FX20 series consists of adapters, I/O modules, and end cover, which is only used for protection and is shipped together with the adapter. 6.4. Introduction to the appearance of I/O modules 6.4.1.
  • Page 12 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     abnormal; Green: input “1” 00-07 Input signal indicator Off: input “0”...
  • Page 13 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6.4.1.3. 8-channel digital output modules ○...
  • Page 14 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6.4.1.4. 8-channel digital output module technical specification...
  • Page 15 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6.4.1.6. 8-channel digital relay output modules  ...
  • Page 16 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6.4.1.7. 8-channel digital relay output modules technical specification ...
  • Page 17: 16-Channel Digital Input Output Module

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6.4.2. 16-channel digital input output module 6.4.2.1.
  • Page 18 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Ordering data Model FX20-DI-BH60 Description...
  • Page 19 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Red: Module channel error Green blinking:  ...
  • Page 20: 32-Channel Digital Input Output Module

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     5%-95%,no condensation Relative humidity Work altitude...
  • Page 21 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     abnormal; 00-07,10-17 Green: output “1”...
  • Page 22 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     ○   ○   ○...
  • Page 23 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Backplane bus Backplane communication expansion interface 6.4.3.4.
  • Page 24: 4-Channel Analog Input/Output Module

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6.4.4. 4-channel analog input/output module 6.4.3.1.
  • Page 25 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     position Backplane bus Backplane communication expansion interface 6.4.3.2.
  • Page 26 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     indicator Red: I/O power supply abnormal;...
  • Page 27 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     General data Protection grade IP20...
  • Page 28 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     indicator Red: I/O power supply abnormal;...
  • Page 29 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Converting time 3 ms Measuring accuracy ±0.3%...
  • Page 30 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Red: output over range Press the device to...
  • Page 31 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     6.4.5.5. 8-channel analog input/output module profile drawing 6.4.6.
  • Page 32 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     measurement signal Red: input over range...
  • Page 33: Auxiliary Power Module

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Work altitude 0-2000 m Weight Dimension(H×W×D)...
  • Page 34 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     terminal Pulling up: assembling Used to fix the module to position;...
  • Page 35: Mechanical Installation And Disassembly

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     7. Mechanical installation and disassembly 7.1.
  • Page 36: Modules Disassembly

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     The end cover is only to protect the backplane bus interface of the end module, and it is packaged and shipped together with the adapter.
  • Page 37: Electrical Installation And Wiring

    "Connectivity System Catalog". 8.1.2. Power and signal cables The FX20 series adopts tool-free spring wiring terminals, and the wiring needs to be equipped with tube type cold pressing cable lugs. Please refer to the following figure for the stripping length and cable lug specifications: TIANJIN ELCO AUTOMATION CO.,LTD.
  • Page 38: Modules Wiring Diagram

    8.2. Modules wiring diagram 8.2.1. FX20 system power supply diagram The FX20 series backplane 5VDC power supply is provided by the adapter, and IO power supply for function module needs to provide separately. Additionally, an auxiliary power supply module can provide a larger backplane power supply current.
  • Page 39 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Warning!  Be sure to disconnect all power connections before wiring! ...
  • Page 40: Bus Adapters Wiring Diagram

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.2. Bus adapters wiring diagram  ...
  • Page 41: 8-Channel Do Pnp Module Wiring Diagram And I/O Process Data40

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.4. 8-channel DO PNP module wiring diagram and I/O process data  ...
  • Page 42: 8-Channel Ssr (Ac) Output Module Wiring Diagram I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.6. 8-channel SSR (AC) output module wiring diagram I/O process data  ...
  • Page 43: 16-Channel Di Module Wiring Diagram And I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Terminal No. Address n:Starting byte of configuration 8.2.8.
  • Page 44 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Model:FX20-DO-BH00 Output Terminal No. Byte 0 Address Q n.7...
  • Page 45: 16-Channel Do Npn Module Wiring Diagram And I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.11. 32-channel DI module wiring diagram and I/O process data  ...
  • Page 46: 32-Channel Do Pnp Module Wiring Diagram And I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.12. 32-channel DO PNP module wiring diagram and I/O process data  ...
  • Page 47 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.13. 32-channel DO NPN module wiring diagram and I/O process data  ...
  • Page 48: 32-Channel Do Npn Module Wiring Diagram And I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.14. 4-channel AI module wiring diagram and I/O process data...
  • Page 49: 8-Channel Ai Module Wiring Diagram And I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Model:FX20-AO-BD60 Terminal No. Address QW n+2...
  • Page 50: 8-Channel Ao Module Wiring Diagram And I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.17. 8-channel AO module wiring diagram and I/O process data...
  • Page 51: 4-Channel Rtd Module Wiring Diagram And I/O Process Data

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     8.2.18. 4-channel RTD module wiring diagram and I/O process data...
  • Page 52: Auxiliary Power Module Wiring Diagram

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Model:FX20-AI-BD90 Terminal No. Address IW n+2...
  • Page 53: Configuration And Debugging

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9. Configuration and debugging 9.1. FX20 Ethernet/IP adapter IP address setting method...
  • Page 54 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     the default IP configuration; 9.1.2.2.
  • Page 55: Fx20 Is Configured And Test On Allen Bradley Plc Through Ethernet/Ip

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     5) Pop up successful IP setting dialog box.
  • Page 56: Configurate Fx20

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     In the toolbar, click on the "Tools" option, click on the "EDS Hardware Installation Tool", find the path to the EDS file, and select FX20-GW-EP00 for...
  • Page 57 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.1.2.2. Set the IP address of the Ethernet/IP port of the PLC. In this example, the IP of the PLC is set to 192.168.0.10, and the IP of the...
  • Page 58 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.1.2.4. Set the device name and IP address, click the “Change”...
  • Page 59 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.1.2.5. Click on the controller tag option in the control tree, select...
  • Page 60 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     16DO(NPN) FX20-DO-BH50 268697602 32 DO(PNP)...
  • Page 61: Fx20 Is Configured And Tested On Omron Plc Through Ethernet/Ip

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Thermocouple T with code‐junction  0x42  Thermocouple N with code‐junction  0x43  Thermocouple E with code‐junction ...
  • Page 62 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.3.2. Set the IP address for the built-in EtherNet/IP port of the PLC. In this example, the default IP address for the PLC is 192.168.250.1, and...
  • Page 63 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.3.4. 9.3.2.4. Double click or right-click on the newly opened interface and select "Edit"...
  • Page 64 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.3.6. In the newly popped up window, click the "Install" button, find the path to the EDS file, and select the "FX20-GW-EP00.eds"...
  • Page 65 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.3.9. Select the corresponding I/O module model from the dropdown...
  • Page 66 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     convenience, use the module model as the member’s name.
  • Page 67 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.3.13. In the "Built in Ethernet/IP Port Settings" tab, click the "Registration All"...
  • Page 68 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     Variable", "Starting Variable", "Connection Type", etc. in sequence, keeping them consistent with the previously established global variables.
  • Page 69 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     TIANJIN ELCO AUTOMATION CO.,LTD. 68  /  74...
  • Page 70: Representation Of Analog Module Values

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     9.4. Representation of analog module values The PLC processes analog values in binary format.
  • Page 71: Analog Value Representation Within The Input And Output Range Of Bipolar Voltage

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     0 mA FFFF -723.4 nA...
  • Page 72: Analog Value Representation Within The Input And Output Range Of Unipolar Voltage

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     20736 5100 15 mA 16 mA 0.00362%...
  • Page 73: Representation Of Simulated Values Within The Measurement Range Of Thermocouples

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     0 ℃ FFF6 -1 ℃...
  • Page 74: Fault Diagnosis

    FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     10. Fault diagnosis Name Status...
  • Page 75 FX20 Series Modular I/O System User Manual for EtherNet/IP                                                     3. IO module damaged, replace it. ...